Vous êtes sur la page 1sur 6

Carnet de câbles de projet : Réaménagement de lycée préparatoire seres - sise à commune Seres - Gouvernorat Kef -

Non enterré Enterré


Nbr
Longueur Nbre Puissance Section U Ib In R part X part R tot X tot
Rep Tenant Aboutissant Cos ϕ Sin ϕ 1/Rend câble/ K1p K2m K3t Kn Ks Kh Ktot1 K4p K5m K6sl K7t Kn Ks Kh Ktot2 LS
(m) phases (KW) (mm²) (V) (A) (A) mΩ mΩ mΩ mΩ
phase
A1 transf TGBT 15 m 3 150 kW 1 0.00 1 1 150 mm² 400 V 217 A 250 A 1.9 1.2 15.6 43.5 0.76 1.00 1.13 0.89 1.00 1.00 1.00 0.76 D
A2 TGBT AE.01 50 m 3 60 kW 1 0.00 1 1 6 mm² 400 V 87 A 100 A 154.3 4.0 169.8 47.5 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A3 TGBT AE.02 50 m 3 49 kW 0.8 0.60 1 1 6 mm² 400 V 88 A 100 A 154.3 4.0 169.8 47.5 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A4 TGBT AE.LG 40 m 3 16 kW 0.8 0.60 1 1 6 mm² 400 V 29 A 32 A 123.4 3.2 139.0 46.7 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A5 TGBT ST 80 m 3 10 kW 0.85 0.53 1 1 6 mm² 400 V 17 A 20 A 246.8 6.4 262.4 53.9 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A6 TGBT GE 20 m 3 60 kW 1 0.00 1 1 70 mm² 400 V 87 A 100 A 5.3 1.6 20.9 55.5 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A7 TGBT fr 60 m 3 5 kW 0.85 0.53 1 1 4 mm² 400 V 8A 10 A 277.7 4.8 293.2 58.7 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A8 TGBT AE.02 50 m 3 36 kW 0.85 0.53 1 1 25 mm² 400 V 61 A 63 A 37.0 4.0 52.6 62.7 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A9 TGBT Onduleur 40 m 3 30 kW 0.85 0.53 1 1 16 mm² 400 V 51 A 63 A 46.3 3.2 61.9 45.5 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A10 Onduleur AE.Ext 70 m 3 9 kW 0.85 0.53 1 1 10 mm² 400 V 15 A 16 A 129.6 5.6 145.2 51.1 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A11 AE.ONG AE.PON 100 m 3 0 kW 0.85 0.53 1 1 10 mm² 400 V 0A 2A 185.1 8.0 200.7 53.5 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
A12 AE.ONG AE.Sinfo1 120 m 3 0 kW 0.85 0.53 1 1 10 mm² 400 V 0A 2A 222.1 9.6 237.7 63.1 0.64 0.58 1.13 0.96 1.00 1.00 1.00 0.40 D
106.779661

2IbL(ƪcos/S+Xsin)
1 1 1 Transformateur 160 kVA
I'z Icc ∆U part ∆U tot ∆U/U Equilibrage U mono 230 V
K Coef mon/tri OK?
(A) (KA) (V) (V) % N P1 P2 P3 U tri 400 V projeteur.com
0.76 327 A 1.73 6 kA 0.84 V 0.84 V 0.21% OK x x x x R cuivre 22.5 mΩ x mm²/m/ (Section)
0.40 248 A 1.73 1 kA 28.13 V 28.97 V 7.24% Non x x x x R alum 36 mΩ/mm²/m/ (Section)
0.40 248 A 1.73 1 kA 23.34 V 24.18 V 6.04% Non x x x x X 0.08 mΩ/m ,
0.40 79 A 1.73 2 kA 6.10 V 6.94 V 1.73% OK x x x x ƪ Cuivre 18.51 mΩ,mm²/m
0.40 50 A 1.73 1 kA 7.60 V 8.44 V 2.11% OK x x x x ƪ Alum 29.41 mΩ,mm²/m
0.40 248 A 1.73 4 kA 0.96 V 1.81 V 0.45% OK x x x x R réseau 0.035 mΩ
0.40 25 A 1.73 1 kA 4.26 V 6.06 V 1.52% OK x x x x X réseau 0.351 mΩ
0.40 156 A 1.73 3 kA 4.27 V 6.08 V 1.52% OK x x x x R transfo 13.7 mΩ
0.40 156 A 1.73 3 kA 4.37 V 5.21 V 1.30% OK x x x x X transfo 41.9 mΩ
0.40 40 A 1.73 2 kA 3.62 V 4.47 V 1.12% OK x x x x
0.40 5A 1.73 1 kA 0.00 V 0.84 V 0.21% OK x x x x
0.40 5A 1.73 1 kA 0.00 V 6.94 V 1.73% OK x x x x
Calibres des disjoncteurs
IB IN
0 2
2 6
6 10
10 16
16 20
20 25 nom et prenom age moyenn
25 32 ali 15
32 40 sa 20
40 50 de 18
50 63
63 80
80 100
100 125
125 160
160 200
200 250
250 315
315 400
400 500
500 630
630 800
800 1000
1000 1250
1250 1400
1400 1600
1600 2000
2000 2500
Sections des cables

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Valeurs des tensions de court-circuit, des résistances et des réactanc
dans un diélectrique liquide (NFC52-11

P (kVA) 50 100 160 250 400 500


Ucc (%) 4 4 4 4 4 4
R (mΩ) 43.7 21.9 13.7 8.7 5.5 5.5
X (mΩ) 134.1 67 41.9 26.8 16.8 16.8
résistances et des réactances des transformateurs immergés
ctrique liquide (NFC52-112-X)

630 800 1000 1250 1600 2000 2500


4 4 6 6 6 6 6
3.5 4.1 3.3 2.6 2.1 1.6 1.3
10.6 12.6 10 8.1 6.3 5 4

NFC15-105 Page 48