Tab-A TGN-01,03,05 3 4 0.8 0.9 0.91 1 55 220 77.15887 61.7271 1.11326 2.44918 0.417
Tab-A1 TGN-02,04,06 3 4 0.8 0.9 0.91 1 55 220 99.52934 79.6235 1.43603 3.15926 0.417
Tab-B TGN-07,09,11 3 4 0.8 0.9 0.91 1 35 220 100.9517 80.7614 0.9269 2.03917 0.417
Tab-C TGN-08,10,12 3 4 0.8 0.9 0.91 1 100 220 144.4795 115.584 1.89507 4.16916 0.2085
Tab-D TGN-13,15,17 3 4 0.8 0.9 0.91 1 85 220 82.20938 65.7675 0.91656 2.01643 0.2085
Tab-E TGN-14,16,18 3 4 0.8 0.9 0.91 1 80 220 118.4679 94.7743 1.24311 2.73485 0.2085
Tab-F TGN-19,21,23 3 4 0.8 0.9 0.91 1 90 220 99.84235 79.8739 3.53306 7.77273 0.625
Tab-G TGN-20,22,24 3 4 0.8 0.9 0.91 1 110 220 141.8121 113.45 1.53624 3.37973 0.287
Tab-Man TGN-25,27,29 3 3 1 0.8 0.91 1 130 220 49.26 49.26 #N/A #N/A #N/A
Tab-Lav TGN-30,32,34 3 4 0.8 0.9 0.91 1 20 220 68.78029 55.0242 0.81194 1.78628 0.417
Tab-AA1 TGN-31,33,35 3 4 0.8 0.9 0.91 1 120 220 390.9033 312.723 2.49356 5.48584 0.0845
ASENSOR TGN-36,38,40 3 4 0.8 0.9 0.91 1 45 220 43.79 35.03 1.88 4.15 1.52
TOTAL 3 4 0.8 0.9 0.91 1 35 220 1367.93 1094.34 1.02 2.24 0.03
MATERIAL
mm AREA TOTAL ALUMINIO=2 AWG AREA AWG AREA AWG AREA Watts A B
77.15887 150 136.5 1 T-51mm 600.2 1 3 - 1/0 429 1 - 1/0 143 1 - 8 28.2 26430 6600 9290
99.52934 150 136.5 1 T-51mm 618.8 1 3 - 1/0 429 1 - 1/0 143 1 - 6 46.8 34092.78 4350 19952.78
100.9517 150 136.5 1 T-51mm 618.8 1 3 - 1/0 429 1 - 1/0 143 1 - 6 46.8 34580 10380 12640
144.4795 300 273 2 T-78mm 1237.6 1 6 - 1/0 858 2 - 1/0 286 2 - 6 93.6 49490 22250 13306
82.20938 300 273 2 T-63mm 1200.4 1 6 - 1/0 858 2 - 1/0 286 2 - 8 56.4 28160 11620 8220
118.4679 300 273 2 T-78mm 1237.6 1 6 - 1/0 858 2 - 1/0 286 2 - 6 93.6 40580 15500 15000
141.8121 200 182 1 T-51mm 850.8 1 3 - 3/0 603 1 - 3/0 201 1 - 6 46.8 48576.3 24825.43 12325.43
61.58 #N/A #N/A 1 T-51mm 850.80 1 3 - 3/0 603.00 1 - 3/0 201.00 1 - 6 46.80 15000
68.78029 150 136.5 1 T-51mm 600.2 1 3 - 1/0 429 1 - 1/0 143 1 - 8 28.2 23560 10060 8260
390.9033 620 564.2 2 F DE R 3128.4 1 6 - 350 2304 2 - 350 768 2 - 8 56.4 133900 44633.33 44633.33
DESB. 15.99
1367.93 1550 1410.5 5 F DE R 8,685.00 1 15 - 350 5,760.00 5 - 350 1,920.00 5 - 3/0 1,005.00 468569.1 163659 155238
10540 3 125 1
1590 3 125 2
9360 3 125 3
13934 3 175 4
8320 3 125 5
10080 3 175 6
9150 3 100 7,9,11
9640.347 3 175 8,10,12
15000 3 175 13,15,17
5240 3 70 14,16,18
44633.33 3 500 19,20,21
3 50 22,24,26
%
POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) 3 175
CONDUCTOR PARA PUESTA A TIERRA 6 AWG - KCM TABLA 250-94
POLOS CAPACIDAD
CAPACIDAD DEL
INTERRUPTOR(ITM) #REF! #REF!
CONDUCTOR PARA PUESTA A TIERRA #REF! AWG - KCM TABLA 250-94
FORMULAS UTILIZADAS
Corriente
W
Trifásicos 3F- 3 o 4 Hilos In=
√3×Ef ×F .P .
W
Bifásicos 2F-3 Hilos In=
2×Efn×F . P .
W
Monofásicos 1F-2 Hilos In=
Efn×F .P.
Caída de tensión
173×I× L×Z
Trifásicos 3F- 3 o 4 Hilos e%=
Ef ×1000
I T ó F≥Ia≥Ipc y I T ó F≤Ipc
El inmediato Superior (Cuando Ipc <= 800 Amp.) 210-22 c), 240-3 b)
I T ó F≥Ia≥Ipc y I T ó F≤Ipc
Calculo de In de motores
IT ó F = IT ó F ó FDE Motor Mayor + ( S In Resto de los Motores x F.D. ) + ( S In Cargas Continuas x 1.25) + ( S In Carga No Continuas. X F.D. )
MEMORIA DE CALCULO
NOMENCLATURAUTILIZADA.
W = Carga (Watts)
In= A= Corriente Nominal (amperes)
V o E = Voltaje
Efn = Voltaje Fase-Neutro (volts) = 256V.
Eff = Voltaje Fase-Fase (volts) = 440V.
F.P. = Factor de Potencia (%)
F.T. = Factor de Temperatura
F.A. = Factor de Agrupamiento
F= Fase
H= Hilos
C/F = No. De conductores por fase
AWG o KCM.= Calibre del conductor
tierra = Cable de tierra física aislada
AREA = Area del conductor (mm2)
n = Eficiencia del motor = 90 %.
M = Distancia (mts.)
e% = Caída de tensión (%) = 5.0% máximo total
INT. = Capacidad del Interruptor
F.D. = Factor de demanda
Z = Impedancia del conductor
Ipc = Corriente Permisible del conductor
Id= Corriente Demandada
It = Corriente del Termo magnético.
Inc = Corriente nominal del conduc
Ia=In = Corriente del nominal
carga continua= es aquella en la que se espera que la corriente electrica circule por mas de tres horas
carga no continua= es aquella en la que se espera que la corriente electrica no circule por mas de tres horas
DIMENSIONES DE TUBERIA CONDUIT Y AREA DISPONIBLE PARA LOS CONDUCTORES
TAMAÑO mas de 2
NOMINAL cond.
mm. Fr=40%
16mm 78
21mm 137
27mm 222
35mm 387
41mm 526
53mm 867
63mm 1236
78mm 1904
91mm 2555
103mm 3282
129mm 5163
155mm 7456
FDECREMENT FDECREMENT
TEMPAMBIENTE AL 60 o C AL 75 o C
25 1.08 1.05
30 1.00 1
35 0.91 0.94
40 0.82 0.88
45 0.81 0.82
50 0.58 0.75
55 0.41 0.67
60 0.58
70 0.47
80
CONDUCTORES FACTOR DE
ACTIVOS CORRECCION
1 1
2 1
3 1
4 0.80
5 0.80
6 0.80
7 0.70
8 0.70
9 0.70
10 0.50
11 0.50
12 0.50
13 0.50
14 0.50
15 0.50
16 0.50
17 0.50
18 0.50
19 0.50
20 0.50
21 0.45
22 0.45
23 0.45
24 0.45
25 0.45
26 0.45
27 0.45
28 0.45
29 0.45
30 0.45
31 0.40
32 0.40
33 0.40
34 0.40
35 0.40
36 0.40
37 0.40
38 0.40
39 0.40
40 0.40
41 0.35
42 0.35
FACTORES DE CORRECCION POR AGRUPAMIENTO
TABLA 310 - 15(B)(3)(A)
CEDULA DE CABLEADO
CONDUCTORES CANALIZACION
TAMAÑO
NOMBRE CANTIDAD mm2 AWG CANTIDAD TIPO
COMERCIAL
4 53.48 1/0
T1 1 2" EMT
1 8.36 8
4 13.3 6
T2 1 1" EMT
1 5.26 10
4 13.3 6
T3 1 1" EMT
1 2.08 14
4 5.26 10
T4 1 1/2" EMT
1 2.08 14
4 5.26 10
1 2.08 14
T5 1 12" CHAROLA
4 13.3 6
1 5.26 10
4 5.26 10
1 2.08 14
4 13.3 6
T6 1 12" CHAROLA
1 5.26 10
4 53.48 1/0
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 5.26 10
T7 1 12" CHAROLA
4 53.48 1/0
1 8.36 8
4 5.26 10
1 2.08 14
4 5.26 10
1 2.08 14
4 13.3 6
1 5.26 10
4 53.48 1/0
T8 1 12" CHAROLA
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10
1 2.08 14
8 13.3 6
2 5.26 10
4 53.48 1/0
T9 1 12" CHAROLA
1 8.36 8
4 5.26 10
1 2.08 14
4 13.3 6
1 2.08 14
4 5.26 10