Académique Documents
Professionnel Documents
Culture Documents
ELECTRICAL ROOM 01 / GF
200AT/250AF 1 39.6 39.6 11.88 55.44 106.92
DP-FCU-1 20 A 4 5.1 20.4 6.12 28.56 55.08 468
30 A 14 8.1 113.4 34.02 158.76 306.18
UPS-1 1 2520
40 kVA 2,730
BATTERY RACK 1 210
ELECTRICAL ROOM 02 / GF
630AT/800AF 1 92 92 27.6 128.8 248.4
100AT/100AF 1 25.5 25.5 7.65 35.7 68.85
SMDP1-LP 701
63AT/100AF 7 15.3 107.1 32.13 149.94 289.17
40AT/100AF 3 11.7 35.1 10.53 49.14 94.77
ELECTRICAL ROOM 03 / GF
630AT/800AF 1 92 92 27.6 128.8 248.4
100AT/100AF 1 25.5 25.5 7.65 35.7 68.85
SMDP2-LP 698
SMDP2-LP 63AT/100AF 8 15.3 122.4 36.72 171.36 330.48 698
40AT/100AF 1 11.7 11.7 3.51 16.38 31.59
25AT/100AF 1 6.9 6.9 2.07 9.66 18.63
ELECTRICAL ROOM 04 / GF
125AT/160AF 1 36 36 10.8 50.4 97.2
DP-FCU-6 20 A 8 5.1 40.8 12.24 57.12 110.16 251
30 A 2 8.1 16.2 4.86 22.68 43.74
UPS-2 1 2520
40 kVA 2,730
BATTERY RACK 1 210
ELECTRICAL ROOM 05 / GF
2000AT/2000AF 1 330 330 99 462 891
SMDP-S. POOL 1600AT/1600AF 1 253 253 75.9 354.2 683.1 1,969
80AT/100AF 8 18.3 146.4 43.92 204.96 395.28
I.N Panel's Name Main Breaker Branch Breaker QTY CB Loss T. Loss BUSSBAR CABLE Net. Total Heat Loss (Watt)
MDB's ROOM / GF
4500AT/5000AF 1 700 700 210 980 1890
2000AT/2000AF 1 330 330 99 462 891
1 MDB-1 1600AT/1600AF 1 253 253 75.9 354.2 683.1 4,552
1000AT/1000AF 1 219 219 65.7 306.6 591.3
630AT/630AF 2 92 184 55.2 257.6 496.8
5,496
I.N Equipment Name QTY RMU Loss Total Losses Heat Loss (Watt)
I.N Equipment Name QTY TR Loss Total Losses Heat Loss (Watt)
I.N Equipment Name QTY CB Loss T. Loss BUSSBAR CABLE Net. Total Heat Loss (Watt)