PARAMETRES DE DEVERSEMENT:

----------------------------------------------------------------------------------------------------------------------------- -----------
PARAMETRES DE FLAMBEMENT:

en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-12.19 = | -12.19 | < 235.00 MPa (3.611)
1.54*Tauz = 1.54*0.26 = 0.40 < 235.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------- -----------
DEPLACEMENTS LIMITES

Flèches (REPERE LOCAL):


uy = 0.0 cm < uy max = L/200.00 = 0.5 cm Vérifié
Cas de charge décisif: 13 DEP /1/ 1*1.00 + 2*1.00 + 3*1.00 + 4*1.00 + 5*1.00
uz = 0.0 cm < uz max = L/200.00 = 0.5 cm Vérifié
Cas de charge décisif: 13 DEP /1/ 1*1.00 + 2*1.00 + 3*1.00 + 4*1.00 + 5*1.00

Déplacements (REPERE GLOBAL): Non analysé


----------------------------------------------------------------------------------------------------------------------------- -----------
Profil correct !!!

CALCUL DES STRUCTURES ACIER


----------------------------------------------------------------------------------------------------------------------------------------
NORME: CM66
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------- -----------
FAMILLE:
PIECE: 5 Solive_5 POINT: 3 COORDONNEE: x = 1.00 L = 1.00 m
----------------------------------------------------------------------------------------------------------------------------- -----------
CHARGEMENTS:
Cas de charge décisif: 10 EFF /1/ 1*1.33 + 2*1.33 + 3*1.33 + 4*1.50 + 5*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
ACIER E24 fy = 235.00 MPa
----------------------------------------------------------------------------------------------------------------------------- -----------

PARAMETRES DE LA SECTION: UPN 100


ht=10.0 cm
bf=5.0 cm Ay=8.50 cm2 Az=6.00 cm2 Ax=13.50 cm2
ea=0.6 cm Iy=206.00 cm4 Iz=29.30 cm4 Ix=2.81 cm4
es=0.9 cm Wely=41.20 cm3 Welz=8.49 cm3
----------------------------------------------------------------------------------------------------------------------------- -----------
CONTRAINTES:
SigFy = -43006.66/41.20 = -10.24 MPa
----------------------------------------------------------------------------------------------------------------------------- -----------

PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------- -----------
PARAMETRES DE FLAMBEMENT:

en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-10.24 = | -10.24 | < 235.00 MPa (3.611)
1.54*Tauz = 1.54*0.22 = 0.33 < 235.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------- -----------
DEPLACEMENTS LIMITES

11