NORME: CM66
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 1 Barre_1 POINT: 7 COORDONNEE: x = 1.00 L = 3.20 m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 11 EFF /1/ 1*1.35 + 2*1.35 + 3*1.35 + 4*1.35 + 5*1.35 + 6*1.35 + 7*1.35 + 8*1.35 +
9*1.35 + 10*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=725.67 Lz=3.20 m Muz=870.03
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*1.33 + 1.00*1.00*2.28 + 1.00*160.42 = 164.32 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*1.60 = 2.46 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.88| = |-1.36| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=78.77 MPa
lD_inf=2.21 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-2.72 = | -2.72 | < 275.00 MPa (3.611)
1.54*Tauz = |1.54*-0.59| = |-0.91| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.32 Sig D=74.23 MPa
lD_inf=3.00 m C=2.26 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.34 + 1.00*-2.72 + -2.65 = | -5.71 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.04| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.67 = 1.03 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.38 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=177.85 Lz=3.20 m Muz=213.24
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*5.44 + 1.00*1.01*37.40 + 1.01*3.04 = 46.24 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.08| = |-0.12| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*7.99 = 12.31 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.04 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2522.74 Lz=3.20 m Muz=3024.60
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.38 + 1.00*1.00*0.02 + 1.00*3.70 = 4.10 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.09| = |-0.14| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.03 = 0.04 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=1.87 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2415.37 Lz=3.20 m Muz=2895.86
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.40 + 1.00*1.00*1.49 + 1.00*1.18 = 3.07 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.02| = |-0.02| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.24| = |-0.37| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.81 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2499.03 Lz=3.20 m Muz=2996.17
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.39 + 1.00*1.00*0.02 + 1.00*0.32 = 0.72 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.02 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.00 = 0.00 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.17 Sig D=79.09 MPa
lD_sup=2.15 m C=2.80 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.00 + 1.00*-0.64 + -1.33 = | -1.97 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.02 = 0.02 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.15 = 0.23 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.31 Sig D=74.57 MPa
lD_inf=2.94 m C=1.86 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.03 + 1.00*1.00*0.62 + 1.00*5.90 = 6.55 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.09 = 0.14 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.44 = 0.68 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.82 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=453.42 Lz=3.20 m Muz=543.62
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*2.13 + 1.00*1.00*7.28 + 1.00*0.17 = 9.61 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.01 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-1.88| = |-2.89| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.90 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2047.62 Lz=3.20 m Muz=2454.96
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.47 + 1.00*1.00*0.34 + 1.00*2.88 = 3.70 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.10| = |-0.15| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.06 = 0.09 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.65 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=1370.20 Lz=3.20 m Muz=1642.78
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.71 + 1.00*1.00*8.45 + 1.00*0.27 = 9.43 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.02 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*2.02 = 3.11 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.31 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=458.87 Lz=3.20 m Muz=550.16
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*2.11 + 1.00*1.00*10.34 + 1.00*4.44 = 16.94 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.09 = 0.13 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*2.14 = 3.29 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.96 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=261.36 Lz=3.20 m Muz=313.35
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*3.70 + 1.00*1.01*7.89 + 1.00*7.67 = 19.35 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.33| = |-0.50| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*1.36 = 2.09 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=4259.32 Lz=3.20 m Muz=5106.64
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.23 + 1.00*1.00*0.30 + 1.00*29.00 = 29.54 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.72| = |-1.12| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.05 = 0.08 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.08 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2046.70 Lz=3.20 m Muz=2453.86
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.47 + 1.00*1.00*24.25 + 1.00*0.20 = 24.94 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.02 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*4.49 = 6.91 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=1.91 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=148.65 Lz=3.20 m Muz=178.22
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*6.50 + 1.00*1.01*0.23 + 1.01*121.34 = 129.15 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-3.18| = |-4.89| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*2.13 = 3.27 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.72 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=96.22 Lz=3.20 m Muz=115.37
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.02 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*10.05 + 1.00*1.02*37.06 + 1.01*1.95 = 49.72 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.18| = |-0.28| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-5.33| = |-8.21| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.92 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=119.31 Lz=3.20 m Muz=143.05
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*8.10 + 1.00*1.01*10.58 + 1.01*114.25 = 134.34 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*1.73 = 2.66 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-2.94| = |-4.52| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=215.90 Lz=3.20 m Muz=258.85
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*4.48 + 1.00*1.01*2.43 + 1.01*63.33 = 70.65 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*1.14 = 1.76 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.94| = |-1.44| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.80 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=503.86 Lz=3.20 m Muz=604.10
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*1.92 + 1.00*1.00*3.79 + 1.00*52.62 = 58.47 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.34 = 0.52 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-1.26| = |-1.94| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=260.93 Lz=3.20 m Muz=312.84
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*3.70 + 1.00*1.01*19.75 + 1.00*0.04 = 23.61 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-5.69| = |-8.76| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=1.77 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=230.45 Lz=3.20 m Muz=276.30
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*4.19 + 1.00*1.01*10.06 + 1.01*0.01 = 14.34 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.12| = |-0.19| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*1.52 = 2.34 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.79 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=128.78 Lz=3.20 m Muz=154.39
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*7.51 + 1.00*1.01*4.70 + 1.01*53.02 = 65.84 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-1.57| = |-2.41| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-2.16| = |-3.33| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
en y: en z:
Ly=3.20 m Muy=462.96 Lz=3.20 m Muz=555.06
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*2.09 + 1.00*1.00*6.30 + 1.00*0.34 = 8.76 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*1.43 = 2.20 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.89 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=219.47 Lz=3.20 m Muz=263.13
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*4.40 + 1.00*1.01*13.55 + 1.01*0.02 = 18.08 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-2.23| = |-3.44| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
en y: en z:
Ly=3.20 m Muy=2905.82 Lz=3.20 m Muz=3483.88
Lfy=6.40 m ky=1.11 Lfz=3.20 m kz=1.09
Lambda y=46.30 Lambda z=42.29
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k*SigN = 1.11*0.33 = 0.37 < 275.00 MPa (3.411)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=1.30 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=1152.54 Lz=3.20 m Muz=1381.82
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.84 + 1.00*1.00*7.83 + 1.00*1.52 = 10.20 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.04| = |-0.07| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.60| = |-0.93| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2905.82 Lz=3.20 m Muz=3483.88
Lfy=6.40 m ky=1.11 Lfz=3.20 m kz=1.09
Lambda y=46.30 Lambda z=42.29
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k*SigN = 1.11*0.33 = 0.37 < 275.00 MPa (3.411)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.70 MPa
lD_inf=1.47 m C=1.03 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.02 + 1.00*-0.46 + -4.22 = | -4.69 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.07 = 0.11 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.38| = |-0.59| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.03 Sig D=73.58 MPa
lD_inf=1.08 m C=1.10 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.04 + 1.00*-0.40 + -2.65 = | -3.10 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.05| = |-0.08| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.27 = 0.42 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.06 Sig D=72.63 MPa
lD_inf=1.50 m C=1.25 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.05 + 1.00*1.00*0.64 + 1.00*1.61 = 2.31 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.04| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.42 = 0.64 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.03 Sig D=73.53 MPa
lD_inf=1.10 m C=1.76 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.03 + 1.00*1.00*0.52 + 1.00*0.01 = 0.56 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.35| = |-0.54| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.10 Sig D=71.14 MPa
lD_inf=2.01 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 1.84 + 1.00*1.00*138.67 + 1.00*93.74 = 234.25 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-2.05| = |-3.16| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-7.06| = |-10.88| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.16 MPa
lD_sup=1.28 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.69 + 1.00*-5.04 + -114.87 = | -120.60 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*2.21 = 3.40 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.95 = 1.46 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.64 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=254.48 Lz=3.20 m Muz=305.10
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*3.80 + 1.00*1.01*16.29 + 1.01*0.50 = 20.69 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.02| = |-0.03| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*3.87 = 5.97 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.01 MPa
lD_inf=1.72 m C=1.20 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.49 + 1.00*1.00*16.62 + 1.00*20.45 = 37.55 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.18| = |-0.28| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-6.59| = |-10.15| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.15 Sig D=69.60 MPa
lD_inf=2.47 m C=1.23 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 1.81 + 1.00*1.00*45.16 + 1.00*49.89 = 96.86 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*1.68 = 2.58 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*15.31 = 23.58 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2584.27 Lz=3.20 m Muz=3098.37
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kFZ*SigFZ = 1.00*0.37 + 1.00*0.56 = 0.93 < 275.00 MPa (3.521)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=1.87 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=8906.05 Lz=3.20 m Muz=10677.75
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.11 + 1.00*1.00*0.00 + 1.00*1.46 = 1.58 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.03 = 0.04 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.12| = |-0.19| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=2905.82 Lz=3.20 m Muz=3483.88
Lfy=6.40 m ky=1.11 Lfz=3.20 m kz=1.09
Lambda y=46.30 Lambda z=42.29
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k*SigN = 1.11*0.33 = 0.37 < 275.00 MPa (3.411)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.34 MPa
lD_sup=1.20 m C=1.48 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.64 + 1.00*1.00*17.50 + 1.00*19.25 = 37.39 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-1.36| = |-2.09| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-21.84| = |-33.64| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.60 MPa
lD_sup=3.44 m C=1.64 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.34 + 1.00*1.00*0.01 + 1.00*9.16 = 9.52 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.09| = |-0.14| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.46| = |-0.71| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
CALCUL DES STRUCTURES ACIER
----------------------------------------------------------------------------------------------------------------------------------------
NORME: CM66
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 49 Poutre1-12_49 POINT: 7 COORDONNEE: x = 1.00 L = 3.44 m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 11 EFF /1/ 1*1.35 + 2*1.35 + 3*1.35 + 4*1.35 + 5*1.35 + 6*1.35 + 7*1.35 + 8*1.35 +
9*1.35 + 10*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.03 MPa
lD_sup=1.72 m C=2.93 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.06 + 1.00*1.00*1.79 + 1.00*15.44 = 17.29 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.12| = |-0.19| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.20| = |-0.30| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.01 Sig D=74.46 MPa
lD_sup=0.46 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.18 + 1.00*1.00*4.36 + 1.00*1.39 = 5.93 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.04| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-2.26| = |-3.48| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.02 Sig D=73.79 MPa
lD_sup=0.97 m C=2.11 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.03 + 1.00*-1.09 + -17.28 = | -18.40 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.24| = |-0.37| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.07| = |-0.10| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.06 Sig D=72.62 MPa
lD_sup=1.50 m C=2.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.19 + 1.00*1.00*2.54 + 1.00*6.38 = 9.11 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.06| = |-0.09| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.12 = 0.18 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.12 Sig D=70.35 MPa
lD_inf=2.25 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.03 + 1.00*-28.81 + -34.04 = | -62.88 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.91| = |-1.40| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*2.44 = 3.76 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.33 MPa
lD_inf=1.20 m C=1.28 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.22 + 1.00*1.00*38.86 + 1.00*12.36 = 51.45 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.33| = |-0.51| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*9.14 = 14.08 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.06 Sig D=72.48 MPa
lD_inf=1.56 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.04 + 1.00*1.00*83.36 + 1.00*0.69 = 84.10 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.06| = |-0.09| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-15.52| = |-23.90| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.67 MPa
lD_inf=1.48 m C=2.24 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -1.27 + 1.00*-46.75 + -0.61 = | -48.63 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.05| = |-0.07| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*13.19 = 20.32 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.72 MPa
lD_inf=1.46 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-3.89 = | -3.89 | < 275.00 MPa (3.611)
1.54*Tauz = |1.54*-0.77| = |-1.18| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.03 Sig D=73.58 MPa
lD_inf=1.08 m C=1.15 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.11 + 1.00*-1.75 + -1.76 = | -3.63 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.35 = 0.53 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.02 Sig D=73.92 MPa
lD_sup=0.88 m C=2.89 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.06 + 1.00*1.00*1.41 + 1.00*17.73 = 19.20 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.45 = 0.69 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.25 = 0.39 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.01 Sig D=74.30 MPa
lD_sup=0.61 m C=2.85 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.01 + 1.00*-1.37 + -11.31 = | -12.70 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.24| = |-0.37| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.35| = |-0.55| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.03 Sig D=73.52 MPa
lD_inf=1.11 m C=1.04 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.28 + 1.00*-0.39 + -19.87 = | -20.53 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.47| = |-0.72| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.29 = 0.45 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=654.37 Lz=3.20 m Muz=784.54
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*1.48 + 1.00*1.00*3.24 + 1.00*6.22 = 10.96 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.06| = |-0.09| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-1.21| = |-1.86| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.10 Sig D=71.14 MPa
lD_sup=2.01 m C=1.31 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 4.08 + 1.00*1.00*150.62 + 1.00*44.56 = 199.27 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-1.24| = |-1.92| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*29.12 = 44.84 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.06 Sig D=72.40 MPa
lD_inf=1.59 m C=1.34 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.87 + 1.00*-1.59 + -65.03 = | -67.49 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.90| = |-1.39| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-0.49| = |-0.76| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.16 MPa
lD_inf=1.28 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-63.16 = | -63.16 | < 275.00 MPa (3.611)
1.54*Tauz = 1.54*14.27 = 21.98 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.92 MPa
lD_inf=1.38 m C=2.00 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -2.95 + 1.00*-107.56 + -19.98 = | -130.49 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.08 = 0.12 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-25.02| = |-38.53| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.01 MPa
lD_inf=1.73 m C=2.55 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.18 + 1.00*1.00*207.67 + 1.00*20.93 = 228.77 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.53| = |-0.81| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*40.47 = 62.33 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.15 Sig D=69.60 MPa
lD_sup=2.47 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.30 + 1.00*1.00*83.55 + 1.00*57.06 = 140.91 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*1.92 = 2.95 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-8.86| = |-13.65| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.09 Sig D=71.48 MPa
lD_inf=1.90 m C=1.18 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 3.75 + 1.00*1.00*53.37 + 1.00*6.51 = 63.62 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.14| = |-0.22| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-24.76| = |-38.13| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.33 MPa
lD_inf=1.20 m C=1.37 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 2.90 + 1.00*1.00*83.70 + 1.00*3.32 = 89.92 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.14| = |-0.21| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-22.65| = |-34.88| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.15 Sig D=69.60 MPa
lD_inf=2.47 m C=1.02 kD=1.08
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 4.31 + 1.08*1.00*96.41 + 1.00*23.00 = 131.40 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.97| = |-1.49| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*38.08 = 58.65 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.01 MPa
lD_inf=1.72 m C=2.55 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -4.00 + 1.00*-118.11 + -18.49 = | -140.61 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.30 = 0.46 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*14.30 = 22.02 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.09 MPa
lD_inf=1.70 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.34 + 1.00*-187.46 + -26.52 = | -214.32 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.44 = 0.68 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*16.38 = 25.23 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.10 Sig D=71.14 MPa
lD_inf=2.01 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.24 + 1.00*1.00*45.44 + 1.00*44.64 = 90.32 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*1.05 = 1.62 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-6.52| = |-10.04| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.10 Sig D=71.14 MPa
lD_sup=2.01 m C=1.86 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 2.30 + 1.00*1.00*115.21 + 1.00*22.82 = 140.33 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.69| = |-1.06| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-30.39| = |-46.80| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.67 MPa
lD_inf=1.48 m C=1.03 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.97 + 1.00*1.00*20.45 + 1.00*19.31 = 40.78 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.41 = 0.63 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*14.80 = 22.79 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.70 MPa
lD_inf=1.47 m C=2.44 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.11 + 1.00*-1.13 + -16.41 = | -17.65 | < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.22 = 0.34 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*0.54 = 0.83 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.67 MPa
lD_inf=1.48 m C=1.36 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.91 + 1.00*1.00*31.83 + 1.00*0.20 = 32.93 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.07| = |-0.10| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*14.69 = 22.62 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.05 Sig D=72.67 MPa
lD_inf=1.48 m C=1.07 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 1.11 + 1.00*1.00*17.04 + 1.00*9.64 = 27.79 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.27| = |-0.41| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-12.67| = |-19.52| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.01 MPa
lD_inf=1.72 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-5.42 = | -5.42 | < 275.00 MPa (3.611)
1.54*Tauz = 1.54*0.91 = 1.40 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.04 Sig D=73.33 MPa
lD_inf=1.20 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.71 + 1.00*1.00*50.58 + 1.00*15.93 = 67.22 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.19| = |-0.29| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-18.74| = |-28.86| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.09 Sig D=71.47 MPa
lD_inf=1.91 m C=1.10 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 2.10 + 1.00*1.00*53.48 + 1.00*1.62 = 57.20 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.07| = |-0.10| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-24.05| = |-37.03| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.15 Sig D=69.60 MPa
lD_inf=2.47 m C=1.08 kD=1.04
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 6.00 + 1.04*1.00*143.21 + 1.00*29.36 = 183.63 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-1.22| = |-1.88| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*46.60 = 71.76 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.07 Sig D=72.02 MPa
lD_sup=1.72 m C=1.50 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -4.50 + 1.00*-47.14 + -6.72 = | -58.35 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-2.11| = |-3.25| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*47.34 = 72.91 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.78 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=526.01 Lz=3.20 m Muz=630.65
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*1.84 + 1.00*1.00*5.39 + 1.00*0.06 = 7.31 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-1.36| = |-2.10| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.65 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=449.43 Lz=3.20 m Muz=538.83
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*2.15 + 1.00*1.00*7.09 + 1.00*0.39 = 9.66 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-1.70| = |-2.62| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.82 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=65.63 Lz=3.20 m Muz=78.69
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.02 Lambda z=42.29 kFz=1.02
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*14.73 + 1.00*1.02*34.34 + 1.02*80.36 = 131.93 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-1.56| = |-2.39| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-8.85| = |-13.63| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.74 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=399.81 Lz=3.20 m Muz=479.35
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.00 Lambda z=42.29 kFz=1.00
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*2.42 + 1.00*1.00*7.57 + 1.00*0.50 = 10.52 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.02| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*1.88 = 2.89 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_sup=3.20 m C=2.78 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=158.16 Lz=3.20 m Muz=189.62
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*6.11 + 1.00*1.01*8.01 + 1.01*2.49 = 16.72 < 275.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.06| = |-0.09| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-2.03| = |-3.12| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.18 Sig D=209.33 MPa
lD_inf=3.20 m C=2.57 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
Ly=3.20 m Muy=139.30 Lz=3.20 m Muz=167.02
Lfy=6.40 m k1y=1.00 Lfz=3.20 m k1z=1.00
Lambda y=46.30 kFy=1.01 Lambda z=42.29 kFz=1.01
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*6.94 + 1.00*1.01*45.32 + 1.01*1.46 = 54.25 < 275.00 MPa
(3.731)
1.54*Tauy = 1.54*0.05 = 0.08 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*10.47 = 16.12 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=1.00 B=1.00 D=1.01 Sig D=74.41 MPa
lD_inf=0.51 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-0.48 = | -0.48 | < 275.00 MPa (3.611)
1.54*Tauz = |1.54*-0.27| = |-0.42| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.59 MPa
lD_inf=3.44 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-6.58 = | -6.58 | < 275.00 MPa (3.611)
1.54*Tauz = 1.54*0.92 = 1.42 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.31 Sig D=74.57 MPa
lD_inf=2.94 m C=1.89 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.05 + 1.00*1.00*8.59 + 1.00*6.73 = 15.37 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.10 = 0.15 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*1.10 = 1.69 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.50 Sig D=68.75 MPa
lD_inf=3.92 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-8.54 = | -8.54 | < 275.00 MPa (3.611)
1.54*Tauz = |1.54*-1.05| = |-1.62| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.52 Sig D=68.12 MPa
lD_sup=4.03 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 4.46 + 1.00*1.00*158.88 + 1.00*41.84 = 205.19 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.46| = |-0.71| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-16.29| = |-25.09| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.52 Sig D=68.12 MPa
lD_sup=4.03 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -1.16 + 1.00*-236.83 + -33.50 = | -271.49 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.47| = |-0.73| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-22.86| = |-35.20| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.58 MPa
lD_sup=3.44 m C=2.56 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -1.16 + 1.00*-236.36 + -33.40 = | -270.91 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.47| = |-0.73| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-22.86| = |-35.21| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.54 MPa
lD_inf=3.45 m C=1.41 kD=1.04
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.62 + 1.04*240.49 + 20.88 = 269.83 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.27| = |-0.41| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-10.52| = |-16.20| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.39 Sig D=71.87 MPa
lD_inf=3.39 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.54 + 1.00*-240.94 + -15.17 = | -256.65 | < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.20| = |-0.30| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*17.58 = 27.07 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.58 MPa
lD_sup=3.44 m C=2.72 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 4.46 + 1.00*1.00*158.54 + 1.00*41.74 = 204.75 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.46| = |-0.71| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-16.29| = |-25.09| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
CALCUL DES STRUCTURES ACIER
----------------------------------------------------------------------------------------------------------------------------------------
NORME: CM66
TYPE D'ANALYSE: Vérification des pièces
----------------------------------------------------------------------------------------------------------------------------------------
FAMILLE:
PIECE: 260 solive 1-1_260 POINT: 7 COORDONNEE: x = 1.00 L = 3.45 m
----------------------------------------------------------------------------------------------------------------------------------------
CHARGEMENTS:
Cas de charge décisif: 11 EFF /1/ 1*1.35 + 2*1.35 + 3*1.35 + 4*1.35 + 5*1.35 + 6*1.35 + 7*1.35 + 8*1.35 +
9*1.35 + 10*1.50
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAU:
S 275 fy = 275.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.54 MPa
lD_inf=3.45 m C=1.33 kD=1.09
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 2.77 + 1.09*1.00*163.23 + 1.00*5.37 = 185.45 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.08 = 0.13 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-6.23| = |-9.59| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.76 MPa
lD_inf=3.41 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 1.27 + 1.00*1.00*163.28 + 1.00*9.07 = 173.62 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.12 = 0.18 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*12.04 = 18.54 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.24 Sig D=76.84 MPa
lD_inf=2.55 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*SigFy + SigFz = -0.27 + 1.00*-238.43 + -125.28 = | -363.99 | > 275.00 MPa (3.731)
1.54*Tauy = 1.54*2.25 = 3.46 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-37.58| = |-57.88| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil incorrect !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.35 Sig D=73.18 MPa
lD_inf=3.17 m C=2.09 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.94 + 1.00*1.00*239.20 + 1.00*56.07 = 296.21 > 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.72| = |-1.10| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*44.74 = 68.90 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil incorrect !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.40 Sig D=71.51 MPa
lD_inf=3.45 m C=2.33 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.10 + 1.00*1.00*114.41 + 1.00*16.39 = 130.90 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.17| = |-0.26| < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-26.40| = |-40.65| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.09 Sig D=82.34 MPa
lD_inf=1.50 m C=2.94 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.48 + 1.00*1.00*114.42 + 1.00*61.80 = 176.70 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*1.78 = 2.75 < 275.00 MPa (1.313)
1.54*Tauz = 1.54*38.74 = 59.65 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.09 Sig D=82.34 MPa
lD_sup=1.50 m C=1.40 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.67 + 1.00*1.00*199.10 + 1.00*6.34 = 206.11 < 275.00 MPa (3.731)
1.54*Tauy = |1.54*-0.24| = |-0.37| < 275.00 MPa (1.313)
1.54*Tauz = 1.54*11.57 = 17.82 < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.14 Sig D=80.26 MPa
lD_sup=1.93 m C=1.90 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 0.97 + 1.00*1.00*199.29 + 1.00*19.05 = 219.32 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*0.56 = 0.87 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-16.05| = |-24.72| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.15 Sig D=79.85 MPa
lD_inf=2.01 m C=1.88 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
kD*SigFy = 1.00*-2.25 = | -2.25 | < 275.00 MPa (3.611)
1.54*Tauz = |1.54*-0.54| = |-0.83| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
PARAMETRES DE DEVERSEMENT:
z=0.00 B=1.00 D=1.24 Sig D=76.84 MPa
lD_sup=2.55 m C=1.91 kD=1.00
----------------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT:
en y: en z:
----------------------------------------------------------------------------------------------------------------------------------------
FORMULES DE VERIFICATION:
SigN + kD*kFy*SigFy + kFz*SigFz = 1.92 + 1.00*1.00*105.12 + 1.00*103.00 = 210.03 < 275.00 MPa (3.731)
1.54*Tauy = 1.54*1.95 = 3.00 < 275.00 MPa (1.313)
1.54*Tauz = |1.54*-3.93| = |-6.06| < 275.00 MPa (1.313)
----------------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!