Technical Data Torques at different running times
Short-time duty S2 - 15 min, with 3-phase AC-motors

Type Output Max. adjustable Motor Torques1) at 100 % UN


speed torque Power for running time
2 min 5 min 10 min 15 min
[rpm] [Nm] [kW] [Nm] [Nm] [Nm] [Nm]
4 30 30 30 30
0.02
5.6 30 30 30 30
8 30 30 30 30
0.04
11 30 30 30 30
16 30 30 30 30
0.06
22 30 30 30 30 30
SA 07.2
32 30 30 30 30
0.10
45 30 30 30 30
63 30 30 30 25
0.20
90 30 30 30 25
125 30 30 25 20
0.30
180 25 25 25 20 18
4 60 60 60 60
0.03
5.6 60 60 60 60
8 60 60 60 60
0.06
11 60 60 60 55
16 60 60 60 55
0.12
22 60 60 60 60 50
SA 07.6
32 60 60 50 35
0.20
45 60 60 45 30
63 60 50 45 40
0.40
90 60 50 40 35
125 60 50 35 30
0.50
180 50 50 45 30 25
4 120 120 120 120
0.06
5.6 120 120 120 120
8 120 120 120 120
0.12
11 120 120 120 110
16 120 120 120 95
0.25
22 120 120 120 95 75
SA 10.2
32 120 120 120 100
0.40
45 120 120 110 85
63 120 120 95 80
0.70
90 120 110 80 70
125 120 115 80 60
1.00
180 100 100 85 60 50
4 250 250 250 250
0.12
5.6 250 250 250 250
8 250 250 250 250
0.25
11 250 250 250 250
16 250 250 250 240
0.45
22 250 250 250 250 220
SA 14.2
32 250 250 250 210
0.75
45 250 250 220 190
63 250 250 200 170
1.40
90 250 250 190 150
125 250 200 140 110
1.80
180 200 200 150 110 90
4 500 500 500 500
0.20
5.6 500 500 500 500
8 500 500 500 450
0.40
11 500 500 500 400
16 500 500 400 300
0.80
22 500 500 500 380 280
SA 14.6
32 500 500 340 260
1.60
45 500 500 340 260
63 500 380 230 170
3.00
90 500 380 230 170
125 500 330 200 160
3.30
180 400 400 300 180 140
4 1,000 1,000 1,000 1,000
0.40
5.6 1,000 1,000 1,000 1,000
8 1,000 1,000 800 600
0.80
11 1,000 1,000 800 600
16 1,000 1,000 600 450
1,000 1.50
22 1,000 1,000 600 450
SA 16.2
32 1,000 800 500 400
3.00
45 1,000 800 500 400
63 1,000 600 350 300
5.00
90 1,000 600 350 300
125 800 550 350 250
800 6.00
180 700 450 300 200
1) Refer to notes on page 2.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.182/003/en Issue 1.20 Page 1/2


SA 07.2 – SA 16.2
Technical Data Torques at different running times
Short-time duty S2 - 15 min, with 3-phase AC-motors

General information
For detailed technical data refer to Technical data Multi-turn actuators SA 07.2 – SA 16.2 for open-close duty with 3-phase AC motors.

Notes on table on page 1


1) Torque Available torque at constant load for the indicated running time at an ambient temperature of +20°C.

Features and functions


Type of duty Short-time duty S2
For operation with constant load during a defined running time, the duration of the load is reduced so that the
thermal equilibrium is not reached. This is observed for all values specified.
Once the running time according to table has been reached applying the max. available torques, allow for suf-
ficient time at actuator standstill to ensure that the device cools down to ambient temperature.

Service conditions
Ambient temperature The specified torques at constant load for the indicated running times are valid for an ambient temperature of
20 °C.
For higher ambient temperatures, the running times of the torques mentioned in the table decrease accordingly.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.182/003/en Issue 1.20 Page 2/2