Computed By: Eng. H.

S
Project:
Checked By: Eng. M. Gamal

Date: Approved By: Dr. H. Soliman

NOVEC 1230 Total Flooding System Calculations


Hazard Area No.1
Protected Hazard Dimensions

Name of Protected Hazard Area ambiant

Height 3.5 m

Area 30.0 m2 322.6 ft2

Volume 104 m3

Volume of Fixed Structures


0.0 m3
Impervious to Agent vapor

Design Parameters

Class of Hazard Area A

Net Volume of Hazard Area 104.3 m3

Design Temperature in Hazard Area 20 C


o

Agent Specific Volume @ 1 Atm. pressure 0.072 m3/kg

Minimum Design Concentration 4.2 % per volume

Agent Design Concentration 5.4 % per volume

Tee Count of Piping System 1.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.00

System Sizing ّ

Agent Net Capacity 82.8 kg 182.6 Ibs

Agent Net Capacity Percentage 100 % Accepted

Total Agent Flow Rate 8.3 kg/sec 18.3 Ibs/sec

Required No. of discharge Nozzels 1

Acual Flow per Nozzel 8.3 kg/sec 18.3 Ibs/sec

Nozzel and Branch Pipe Diameters 1 1/2 inch

Main Pipe Diameter 1 1/2 inch 3


Computed By: Eng. H.S
Project:
Checked By: Eng. M. Gamal

Date: Approved By: Dr. H. Soliman

Hazard Area No.2


Protected Hazard Dimensions

Name of Protected Hazard Area elect

Height 0.0 m

Area 0.0 m2 0.0 ft2

Volume 0 m3

Volume of Fixed Structures


0.0 m3
Impervious to Agent vapor

Design Parameters

Class of Hazard Area A

Net Volume of Hazard Area 0.0 m3

Design Temperature in Hazard Area 20 C


o

Agent Specific Volume @ 1 Atm. pressure 0.072 m3/kg

Minimum Design Concentration 4.2 % per volume

Agent Design Concentration 5.4 % per volume

Tee Count of Piping System 0.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.00

System Sizing ّ

Agent Net Capacity 0.0 kg 0.0 Ibs

Agent Net Capacity Percentage 0 %

Total Agent Flow Rate 0.0 kg/sec 0.0 Ibs/sec

Required No. of discharge Nozzels 0

Acual Flow per Nozzel 0.0 kg/sec 0.0 Ibs/sec

Nozzel and Branch Pipe Diameters - inch

Main Pipe Diameter - inch 2 1/2


Computed By: Eng. H.S
Project:
Checked By: Eng. M. Gamal

Date: Approved By: Dr. H. Soliman

Combined System Sizing

Agent Total Net Capacity 82.8 kg 182.6 Ibs

Container Size Minimum Fill


Container Size Selection 125 Ib 63 Ibs
455
Total Required No. of Containers 2

Agent Net Capacity in Each Container 41.4 kg


91.3 Ibs Accepted

Total Agent Flow Rate 8.3 kg/sec 18.3 Ibs/sec

Maximum Agent Flow Rate per Nozzel 9.07 kg/sec 20 Ibs/sec

Total Required No. of discharge Nozzels 1 Accepted

System Main Pipe Diameter 1 1/2 inch 3

Checking Agent Concentration in a Combind Space with Directional Valve

Name of Protected Hazard Area Tel

Height m

Area m2 0.0 ft2

Volume 0 m3

Volume of Fixed Structures


m3
Impervious to Agent vapor

Design Parameters

Class of Hazard Area

Minimum Design Concentration 4.2 % per volume

Net Volume of Hazard Area m3

Design Temperature in Hazard Area 20 C


o

Agent Specific Volume @ 1 Atm. pressure 0.072 m3/kg

Tee Count of Piping System 1.0

Hazard Area Pressure 1.0 atm

Design Safety Factor 0.00

Agent Design Concentration 100.0 % Not Accepted


Recommendation: Use Separate System for this Hazard
Computed By: Eng. H.S
Project:
Checked By: Eng. M. Gamal

Date: Approved By: Dr. H. Soliman

General Design Considerations

- Max. No. of Nozzels in the System 20


- Maximum Agent Flow Rate per Nozzel 9.07 kg/sec 20 Ibs/sec
- Maximum Discharge Time 10 sec
- Nozzel Maximum Coverage Radius 8.70 m 360o Nozzel Type
10.90 180o Nozzel Type
- Min. Nozzel Pressure 73 psi
- Maximum Ceiling Height 4.87 m
- Nozzel Max. Distance from Ceiling 0.30 m
- False Ceiling or Raised Floor Min. Height 0.30 m
- Space Min. agent percentage in combind system 10 %
- Beams that are less than 0.3 m below the slab need not be considered. Obstructions greater than 300 mm
(12”) can affect the distribution of agent and may require additional nozzles.
- The max. elevation difference between the container outlet and the furthest horizontal pipe run or discharge
nozzle (whichever is furthest) shall not exceed 9.1 m.
- The max. elevation difference between the furthest horizontal pipe runs or discharge nozzles (whichever is
furthest) shall not exceed 9.1 m.
- The agent design concentration shall be checked to insure that it is under NOAEL at maximum anticipated
temperature in the hazard space.
- Sizing is based on NFPA-2001