INTECONT PLUS
Weighfeeder
Operation Manual
BV-H2215 GB
Contacts, Copyright
Service: 24h Emergency hotline: +49 (0) 172 - 650 17 00 Discontinuous Weighing Technology
+49 (0) 171 - 255 11 95 Continuous Weighing Technology
Email: service.process@schenck.net
Business Segments:
Vibrating Machines
Service Tel.: +49 (0) 61 51 32 - 10 75
Service Fax: +49 (0) 61 51 32 - 30 96
E-Mail: bvs.process@schenck.net
©Copyright 2003
SCHENCK PROCESS GmbH
Measuring and Process Systems
Landwehrstrasse 55, D-64293 Darmstadt
http://www.schenck-process.com
All rights reserved. Any reproduction of manual, regardless of method, without prior permission by
SCHENCK PROCESS GmbH in writing, even by excerpt, is prohibited.
Subject to change without prior notice.
INTECONT PLUS VDB
Contents
1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power ON · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4
Signal Lamps· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4
Normal Display · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5
Event Messages · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 7
Function Distributor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9
Keyboard Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10
Activate/Deactivate EasyServe · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10
Feeder · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 11
Printing· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 11
Zero Setting · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13
Read Parameters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 14
Batching Mode· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 14
3. Control Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4. Operating Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6. Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7. Setting Programs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Calibration Functions· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 30
Belt Circuit LB · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 30
Tare TW · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 31
Weight Check CW · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 33
0338
Simulation Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 34
Set Time · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 35
8. Service Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9. Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Select Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Enter Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Hardware Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Parameter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
System Messages S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Electrical System E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Calibration C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Maximum H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Minimum L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Signal Lamps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
11. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Mechanical Prerequisites · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 80
Electrical Prerequisites · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 81
Enter Parameters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 81
Control · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 83
Functional Check· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 84
Calibration · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 84
Linearization · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 88
Test Plug · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 88
12. Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Batching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Applications: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
0338
0338
1. Overview
What Is The INTECONT: Display:
INTECONT PLUS is designed as measuring and 5 x 7 - dot matrix with 6 mm character height
evaluation system for
Upper display left : running message
Belt Weighers right : set feed rate in kg/h or t/h
Solids Flow Meters
Mass Flow Meters Lower display left : event messages
Mass Flow Feeders right: selectable
Weighfeeders feed rate, belt speed, etc.
Loss-in-weight Feeders Display can be changed over to American units.
The system is supplied in 3 variants:
LEDs:
1. Without option card (standard)
2. With option card VFE 610V 2 green and 3 red LEDs
for additional input/outputs and printer
3. With option card for fieldbus Green LEDs : Ready
VSS021V : Modbus/S5 Red LEDs : Error or limit value messages
VPB 020V: Profibus
VCB020V: DeviceNet
O P = 1 0 0 0 kg/h
E1 I = 1 0 0 0 kg/h
0338
O
correction of zero point and range.
DEL Acknowledge event message, n Highly resolving analog-to-digital converter.
delete input The integrated method is designed to efficiently
B9 Enter parameters
Some Definitions:
Y = Controller output in mA
ON = Scale is active.
Outputs for control of belt and
prefeeder drives, connection of
totalizing counter and analog
display unit are available.
RELEASE = Release
0338
2. Operation
Power ON Signal Lamps
Message E1
b (green) CPU OK
lit if microprocessor is ready to
operate.
E1
P = 2 5 0 0 kg/h
I = 0 kg/h
X (red) ALARM
flashes if an Alarm is available.
In addition, the event code is
shown in lower display line.
ALARM:
Red lamp Xand symbol E1 flash.
Acknowledge message before
MAX (red) MAX LIMIT VALUE
lit if feed rate limit value is
exceeded up.
starting scale.
WARNING:
Signal lamp X remains dark, READY: The two green signal lamps
light and no Alarm is available.
0338
Left Rotating point as running message. 1) With belt weighers controlled for constant belt load,
Scale is started, amount fed out and feed counter 1 is displayed in place of setpoint. All
rate are acquired. setpoint inputs are omitted.
In STOP state (point stands still) only belt 2) Related to nominal value
load and belt speed are measured. 3) If serial or analog setpoint is preselected
4) If percental evaluation of serial or analog setpoint is
Special features in addition to running preselected
message: 5) See “Batching Mode”.
blank = Gravimetric mode
V= Volumetric mode Display formats and units of Z1, Z2, Z3, P, Pe and I
In start-up and clearance can be selected separately.
modes, “V” flashes.
o= Keyboard mode
If Keyboard and Volumetric modes are
active at the same time, “V” is framed by Operation In Normal Mode
keyboard symbol.
g Start scale.
Condition : External release signal
Right Effective setpoint P 1)
If “=” flashes, Simulation mode is active. available; if not,
message S2 is output.
No Alarm available.
Lower Display START source set to OP
or Keyboard mode
Left Event reported by alphanumeric code, selected.
e.g. E1 for power failure. Feature : Rotating point in left field
Right Selectable display of upper display.
B Stop scale.
Feature : Point stands still after a
selectable counter
P = 10 0 0 kg/h tracking time.
E1 I = 6 0 0 0 kg/h Belt load and belt speed
continue being
measured.
J Change setpoint.
TU Select display
1 Desired digit
Enter desired digits.
Counter Z1 Z1 = 5000 kg P =- - - - - - - - - - - - - - - kg/h
Counter Z2 Z2 = 6000 kg or
Counter Z3 Z3 = 1000 kg Pr =- - - - - - - - - - %
Feed rate
Feed rate
I
Ir
=
=
1000
50.00
kg/h
% 2) O Delete digit.
Belt load Q = 10.000 kg/m
0338
Belt load
Belt speed
Deviation
Qr
V
Xd
=
=
=
50.0
0.0500
0.10
%
m/s
%
2)
2)
f Acknowledge input.
N Abort input.
Old setpoint remains stored.
TU Select lower display
(see “Normal Displays”).
G
Percental (relative) setpoint Pr:
Call further functions, e.g. Display Event,
Pr can be used to percentally evaluate an external Calibration.
N
setpoint Pe (e.g. serial).
Exit function distributor.
f Acknowledge input.
N Abort input.
O P = 100.0 kg/h
-- I = 0 kg/h
0338
For troubleshooting details, see chapter “Event n WARNING 2 Display permanent, not
Messages”. underscored.
Acknowledgement:
Not required.
P = 1000 kg
n IGNORE No monitoring of events, save
E1 I = 0 kg/h
MIN/MAX messages and
deviation via contact outputs and
signal lamps.
flashes.
Totalization cuts off, scale is not G Call function distributor.
operable.
Start:
TU Scroll “Display Events” into lower display
field (normally not required).
First remove cause of fault and
acknowledge message. f Select function.
Acknowledgement:
If cause has not been removed
yet, flashing stops, underscores
are deleted, but message is still
available.
If fault is remedied after
acknowledgement, message
automatically effaces.
0338
Maximum H H1 I-MAX
H2 Load > MAX
1. E v ent s S 2 = N 0 7 H3 v > MAX
No Release H4 L/C Input > MAX
List of Events
Min/Max outputs independent of event class,
The list is organized by display priority. active also with IGNORE.
Limit values are reported as
long as event is available
System Message S S1 Memory Error * provided that scale is active.
S2 No Release
S3 Maint. STR-meter
S4 Maintenance Int. Elec Control deviation see Min/Max outputs
S7 Simulation Active
S8 Setpoint Limited Signal lamps See Min/Max outputs
S9 Data Link Host
Abort Batch
function selected last. If an event is Deselect Batch
available, the “Display Events” function is Print Batch
displayed.
S = Calibrating functions accessible after
f Start function.
password input.
Prompt is output after call of function.
TU
Display Test 1. All display elements rhythmically
START/STOP Feeder flash.
Volumetric/Gravimetric
f
2. Version number is displayed for
Volum. Synchron. approx. 10 s.
START/STOP Keyb. Mode
>0 : Zero Set Test terminates automatically.
Select Batch B
Activate/Deact. EasyServe
Programming
Calibrating Function S I N T E C O N T P L U S
Read Parameters
Enter Parameters S
Load Default Param. S
Print Parameters Example:
Print Status Report
VDB : Weighfeeder
START/STOP Simulation 20600-00 : Version number
Tare
Weight Check
Imp/Belt Circuit
0338 Set Time
Print Parameters
Feeder
Lets you print complete parameter list with actual
The “START/STOP Feeder” function lets you start and values.
stop material prefeeder. Parameters deviating from default are identified by *.
In started state, the prefeeder is controlled through the As appendix, a list of all possible event messages and
INTECONT. current hardware equipment is printed.
In Stop state, material flow is interrupted and scale
can be tared, etc.
GT Call function distributor.
f
Call function distributor.
Select “Start Feeder” or “Stop Feeder” Start function.
N
function.
PRINT PARAMETERS
Printing
INTECONT PLUS VDB 20600-00 353
f Start function.
N Abort printing.
If printer has a big data buffer, abort is
not effected immediately.
Batch Report
03.03.03 11:45:10
Counter 1 12000 kg
Counter 2 90000 kg
Events
C8 Slip Error M14
Print Events
STATUS REPORT INTECONT® PLUS
25.11.02 13:37:12
30.04.03 11:45:21 L2 W1 à Load < MIN
Software : VDB 20600-0 913
30.04.03 11:59:01 L2 W1 ß Load < MIN
Hardware version
Option card version
:1
:1
Station address :1
-------------------------------
Mode OP : NO
Mode Simulation : NO
Scale ON : YES
Volumetrisch : NO
Alarm : NO
Parameter J 02 lets you determine whether available Voltage ON-time :6h
Scale ON-time :2h
event messages are printed or not. Counter 1 : 23 t
Counter 2 : 23 t
Counter 3 : 120 t
L2 : Event code Belt Slip : 0.00 %
Belt Skew : 0.20 cm
-----------------------------------------------------------
W1 : Message class, e.g. WARNING 1 Events after last status report
1 * E01 Power Failure
3 * S02 No Release
> : Event occurred
f Start function.
Belt Skew:
Belt off-centre run in cm.
0338
Program complete:
Zero Setting
During zero setting, all totalizing counters stop Upper display : Deviation of zero point from
operating. previous zero setting operation
in % of nominal belt load
Conditions: 1. Select Volumetric Mode.
2. Make sure conveyor belt is totally dev = + : error increased
cleared. dev = - : error decreased
If a prefeeder is present, use “Stop
Feeder” function. Lower display : Deviation of zero point from basic
tare in % of nominal belt load.
3. Make sure conveyor belt is running.
Taring program corrects basic tare
A respective hint is output
during calibration.
automatically.
To call:
The result can be accepted or rejected. If rejected, it
G
still serves for information.
Call “Zero Setting” program.
TU Start function.
f Acquire result.
Scale zero point is corrected.
Program running:
Event Messages:
0338
Z1 = 400 kg
reliability.
f
display field and acknowledge.
is displayed left of running
Tf
message.
Select “Read Parameters” sub-function.
Lower display:
1. Zb = Batch setpoint
2. ZI = Batch actual value
Amount already
Dialog Behaviour
Block: A
discharged
3. Zd = Batch residual value
Amount not yet
discharged
TU
Zd = Zb-ZI
Scroll through parameter blocks A, B...
N Return to blocks.
0338
Zb = . . . . . . kg
f
first prompts for input of feed rate Select “Deselect Batch” function.
setpoint
P = - - - - - kg/h Acknowledge.
19 Enter feed rate setpoint. The “Select Batch” function lets you reactivate
N
batching mode.
Skip input. The old ZI, Zd and Zb values can be viewed again.
Old feed rate setpoint is maintained.
0338 Program automatically prompts for input
Abort Batch
Lets you abort a running batch, i.e. Batching Batch Report
immediately stops.
Batching mode remains selected. 03.03.03 11:45:10
Batch setpoint 1000 kg
Batch setpoint 998 kg
New batch starts upon next start command, old batch Counter 1 12000 kg
is not resumed. Counter 2 90000 kg
f Acknowledge.
This function requires the option card to be present. Batch setpoint : Amount to be batched
Batch must be completed or aborted.
Print is possible only in batching mode. Batch act. value : Amount batched (actual value)
f Start function.
N Abort printout.
0338
3. Control Overview
O P = 100.0 kg/h
-- I = 0 kg/h
gB START/STOP Message S2
unless scale has been released via digital input.
T
Select function.
4. Operating Principle
Belt Load
Feed Rate
I in kg/s
v in m/s
Q in kg/m
QB in kg
Leff in m
0338
Q V
ACT
+
Y Xd ACT
R
-
SET
Vh206225_gb.cdr
Qo
Feed rate is controlled for setpoint by variation of belt The drive requires an external power stage with
load. Belt speed is normally constant. armature voltage or speed control, etc., to be
present.
1. Gravimetric
Controlled mode as described above
2. Volumetric
Q V
Uncontrolled mode, i.e. belt speed or prefeeder are
controlled in proportion to setpoint. Feed rate value
measured or belt load actual value are not
- ACT considered.
Y Xd
R
+ SET
Vh206224_gb.cdr
kg/hr
Control sources:
1. Setpoint via
Keyboard
Analog
Serial
2. START/STOP via Keyboard
Serial
Contact
3. Reset counter (and/or) Keyboard
Serial For constructional reasons, the weighing platform is
4. Acknowledge event (and/or) Keyboard located at the point of material discharge direct.
Contact Therefore, if belt load varies, the measured feed rate
Serial does not exactly corrspond to the feed rate at the
point of discharge.
The “Keyboard Mode” control function lets you shift A special speed-dependent delay element shifts the
items 1 and 2 from selected sources to keyboard, and measurement to the discharge point.
vice versa. To do so, no special load transducers are required;
however, the additional use of the automatic belt
influence compensation is reasonable.
Automatic Belt Influence Compensation (BIC)
Measurement at the point of discharge also controls
Even the best of conveyor belts is not perfectly even; the material flow at the point of discharge.
particularly in welding points, the belt will be heavier
and stiffer. The figure above shows the situation over
one belt circuit in exaggerated fashion.
Batching
0 Start batch
1 Abort batch at any time
and
2 resume.
3 Continuously decrease setpoint until preset batch
amount is reached.
0338
5. Technical Data
n Panel-mounting unit VEG 20600/20610 n Surface-mounting unit: with panel mounting unit
VEG 20...
Front panel : 96 x 288 mm
Panel cut-outs : 88 x 282, wall thickness n Wall-mounting housing
max. 10 mm
Mounting depth : min. 225 mm Measuring
(including 50 mm for systems: width x height x depth
connectors) 410x330x236mm
Protected to : IP 20, front to IP 65 Feeding
Material : plastic grey to RAL 7022 systems: width x height x depth
Display : fluorescent, 2 lines of 20 500x600x300mm
characters, 6 mm high Protected to : IP 65
Keyboard : flexible membranes with Material : steel sheet, 1.5 mm, grey
tactile touch Voltage supply : 90...264V/50Hz...60Hz
Signal lamps : LEDs, 2 x green, 3 x red
Power supply : 24 V(DC) +50 % -25%,
max. 1 A, Extension : Feed unit controller
no fuse, pole-reversal
protective circuit n Environment
Ext. power supply : 90...264V/ 50HZ...60HZ Temperature : -25 °C ... +45 °C,
tested to -40°C
Humidity Class F:(DIN 40 040) *
Interference
immunity to IEC 801
Interference
P = 100.00 kg/h suppression : to VDE 871, EN 55 011
I= 0 kg/h
n Storage temperature
n Connectors
n Control outputs
If error message “CPU Not OK” is output, all contacts n External totalizing pulse counter
open.
Frequency : max. 10 Hz
n Control Pulse length : selectable 50...1000 ms
Output : 24 V, max. 100 mA
Number : 5 optionally active low or
Base card : 3 active high,
Option card : 2 galvanically isolated,
Type : 24 V(DC) +/-30 %, 5 mA, short-circuit-proof, limited to
galvanically isolated apr. 350 mA,
negative amounts are stored
internally and must be
n Control inputs (NAMUR) compensated by positive
amounts before new pulse is
Number : 2 output.
Type : NAMUR (DIN 19234), This ensures integral
short-circuit and cable accuracy also with minimal
breakage monitoring belt load.
0338
Number : 1
Type : RS232; RS422 or RS 485
max. 19200 baud
Data format : 8 data bits, 1 stop bit, odd
parity changeable to even or
no
Isolation : galvanically non-isolated
Connectors : Phoenix MSTB, contact
spacing 3.5 mm, max. 1.5
mm or 9-pole D-Sub HD20
2
0338
6. Characteristics
n Power Failure
Special function used to operate your system Switching threshold, relay outputs and event
without mechanical equipment, e.g. for plant class can be defined individually for all 6
testing. possibilities.
Zero setting is performed with empty conveyor belt can be defined individually for feed rate, belt load,
using an automatic program. speed, and deviation.
a) Using material
Number Name Default
Enter check result into INTECONT, and R04 DO I-MIN DO1
measurement value will be corrected. R05 DO I-MAX DO2
R01 DO ALARM DO3
b) Using check weight R02 DO Prefeeder ON DO6
R03 DO Feeder ON DO7
A special check program lets you check R11 DO Full Feed —-
normalisation or, if certain technical data are R12 DO Dribble Feed —-
not exactly known (lever ratio, belt inclination, M15 DO Slip Event —
etc.), correct them. M16 DO Belt Skew —
M17 DO Belt Slip —
In subsequent operation, this program can be R06 DO Q-MIN —
used to detect mechanical changes, e.g. R07 DO Q-MAX —
platform distorsion after settling of foundation. R08 DO v-MIN —
R09 DO v-MAX —
n Digital Inputs R10 DO Batch Active —
R13 DO Feeder ON D04
R14 DO Deviation D05
Number Name Default
R15 DO Volum. Mode —-
Q03 DI Ackn. Events DI1
Q01 Release DI5
B06 START Source — (OP)
Q02 DI Stop Batch —-
M04 Source Sensor DI6
B03 Tacho Source DI7
Q05 DI Volum. Sync. —
0338
7. Setting Programs
The function distributor lets you access all setting Programming and Calibration functions lead to further
programs. menus you can move through using cursor keys.
f Start function.
Deselect Batch
Print Batch
E = If an event is available
Display Results E
Display Check
START/STOP Feeder
Service Values
Volumetric/Gravimetric
Volum. Synchronous
START/STOP Keyb. Mode
>0 : Zero Set
Select Batch B
START/STOP EasyServe
Programming
Calibration Functions S
Print FMZ
Read Parameters
Enter Parameters S
Load Default Par. S
Print Parameters
Print Status Report
START/STOP Simulation
Taring
Weight Check
Imp/Belt Circuit
0338 Set Time
There are 3 setting programs designed to ease initial Call setting program LB: IMP/BELT only
calibration and recalibration.
1. upon initial calibration
1. Pulses/Belt Circuit LB 2. after mounting new belt or considerably varying belt
2. Taring TW tension
3. Weight Check CW 3. after having changed Parameter B 04 (Charact.
Val.-vs) or B 05 (Nominal Speed) (regardless of
Upon initial calibration, perform functions in the above whether scale operates with or without speed
order of sequence. mesurement).
All programs can be reached using the CALIBRATION
function and are protected from unauthorized use by Program acquires the number of speed transducer
password. pulses for one belt circuit and uses the number of
pulses as belt circuit code for the following programs:
During program run until acknowledgement a. Zero Setting >0<
1. no totalization takes place b. Taring TW
2. analog outputs are set to elevation values c. Weight Check CW
3. no event messages are suppressed
The operating sequence is the same for all programs. Upon initial calibration, call setting program LB first.
Sequence:
Display shows one of the setting programs, e.g. TW:
Tare. Gf Call function distributor,
Calibration functions, password
(see “Calibration Functions”).
Calibration Functions
TU Scroll LB: Imp/Belt into lower
display field.
TW: Taring
f Start program.
f Start setting program. Setting programs do not control belt drive, prefeeder
and operating mode.
N Return to normal displays.
For apr. 2 min., Calibration
If any condition is not met, setting program aborts
and a corresponding message is output.
menu can be recalled without
password input.
0338
Program running:
Tare TW
Gf
2. SELECT VOLUM. if Volumetric mode is not
selected Function distributor, Calibration functions,
Attention! password (see “Calibration Functions”).
If a belt circuit sensor is present (M03 = YES),
program sequence slightly differs.
TU Scroll “TW: Tare” into lower display field.
Running
f Start program.
message
Complete
: E-PROG active (lower display)
N Abort at any time.
message : ... - I/B
Values flickers upon every belt
0338 circuit.
Program complete:
Special Messages:
0338
Program running
Weight Check CW
No automatic correction takes place. Upper display : Residual run time in % of total run
time
Conditions:
Lower display : Continuously meaned SET/ACT
1. Tare or set to zero. measuring result
2. Enter check weight into Parameter C 08.
Check weight should amount to 30...100 % of
nominal platform load Q0.
Q0 = q0 * Leff Program complete
q0 = Nominal Belt Load (Parameter D 01)
Leff = Eff. Platform Length (Parameter C 05)
3. Apply check weight in provided location.
4. Make sure scale operates in Volumetric mode.
>. CW: 1200,34 kg
A corresponding hint is output automatically. COR 0.99915
5. Deselect Batching mode.
Sequence:
f Start program.
fN Exit program.
Since result is not acquired automatically,
the two keys are equivalent.
Special hints:
Evaluating result:
Simulation Mode
Error < 1 % : KOR = 0.99...1.01
Scale OK, no further action The Simulation Mode lets you check all scale
required. functions without material at the time of
Error < 5 % : KOR = 0.95...1.05 commissioning.
During simulation, scale is cannot operate in normal
Enter KOR value into Parameter D
mode.
02 .
This makes good sense only if
parameter has not yet considered
Gf Function distributor, Calibration functions,
password (see “Calibration Functions”).
TU
result of check using material.
Error > 5 % : KOR < 0.95 or KOR > 1.05 Scroll “START Simulation” into lower
Multi-percent deviations suggest display field.
wrong data input (e.g. belt
inclination not exactly known, lever
f Start program.
arms) and/or mechanical faults
(misalignment, distorsions).
Display : Event message S7
Check does not consider Parameter “Span In upper line, the “=” symbol
Correction" D 02, so that check program will flashes.
indicate same error quotient KOR after check. Function can be cut off in the same way (STOP
Simulation).
Features:
0338
Set Time
f Call menu.
0338
0338
8. Service Values
The Service table includes detailed system 6. Inputs switching conditions
information. Call does not affect weighing functions.
I+ : DI = 1 1 1 1 1 + 0
Displays: 7. EL = 22 h
1. VDB 20600-00 3563 Version number
Voltage ON-time
2. HW = 1 Hardware version
3. Opt.K: 0 (no option card)
Monitoring: Parameter K 01, Message S4
1 (option card available)
8. ED = 19 h
O Z1 = 1500100 kg
ON-time of scale and conveyor belt
Opt..K : 1
Condition : Totalization ON
Monitoring : Parameter K 03, Message
S3
0338
11. vap = 0.883168 mV/V 17. Pulses of sensor area Imp.S. = 386
Unnormalised output value of load cell Measured pulses of sensor area. If belt sensor
amplifier, delayed by shift to point of discharge is properly mounted, the following value
(CPD) should result:
12. bic = 2.34001 mV/V Imp.S. = 0.5 * Sensor length * 0.01 * vs-Char. Value
25. Y = 4.59 mA
Controller output
0338
0338
9. Parameterization
Some parameters can be set in accordance with Enter numeric value, e.g. nominal feed rate.
requirements (e.g. display formats), others have to be
taken from Spec Sheet supplied.
During parameter input, all functions are maintained.
However, during operation, only parameters with no Call Parameter Menu
influence on measurement, e.g. display filters, should
be changed. G Call function distributor.
Default Values
TUf Scroll PROGRAMMING into
lower display field and
All parameters are preset with default values. These
acknowledge.
are proven suggestions and can normally used as
defined.
The default values can be loaded using sub-function
TUf Select ENTER PARAMETER
function.
Bf
“Load Default Parameters”.
Enter password 07734.
Identification
The parameters are organised into function blocks A, Display shows title of first parameter block.
B, ... and, within a block, described by
name
number 1, 2, 3 ..
and
value.
Values differing from default are identified by a * Dialog Behaviour
Block: A
before the block letter.
0338
TU Selection parameter:
value flashes.
Rated Data Scroll desired value into lower
Block: B
display field.
B9 Numeric parameters:
TU Move through blocks A, B ... up
and down.
Feature - - - - - - - - - - - - - - - -
Enter value using number keys.
f
Block letter flashes.
f Select block.
Acknowledge input.
Next parameter is displayed.
O
Display shows parameter
selected last. Delete digits.
0338
OP
G Select PROGRAMMING function,
call DEFAULT PARAMETERS.
v
—
B1 YES = 1
NO = 0
DI I+ DI1-DI7 HI, LO
AI I+
Power Failure
As you can see, with “Fieldbus” (FB), “Operator
Panel” (OP), “Speed” (v) and “Not Assigned” (—) no Parameters remain stored for an unlimited period of
additional input is required. time.
“Digital Inputs” (DI) and “Digital Outputs” (DO) require
unit, channel and level to be indicated.
With “Analog Input” (AI), the unit is firmly set to I+.
Sample:
Description Source
B06 START Source OP
Alternatives FB, DI
6
right) let you shift between source,
channel and level.
0338
07 Lin.-I3 75.00 % Q
08 Lin.-S4 100.00 % Q
09 Lin.-I4 100.00 % Q
10 Lineariz. error W2 (B 09)
01 Release DI I+.DI5 HI
02 DI Stop batch —
03 DI Ackn. Events DI I+.DI1 HI
04 DI Volumetric ON —
05 DI Volum. Sync. —
01 DO ALARM DO I+.DO3 HI
02 DO Prefeeder ON DO I+.DO6 HI
03 DO Feeder ON DO I+.DO7 HI
04 DO I-MIN DO I+.DO1 HI
05 DO I-MAX DO I+.DO2 HI
06 DO Q-MIN —
07 DO Q-MAX —
08 DO v-MIN —
09 DO v-MAX —
10 DO Batch active —
11 DO Full feed —
12 DO Dribble feed —
13 DO Feeder ON DO I+.DO4 HI
14 DO Deviation DO I+.DO5 HI
15 DO Volum. Mode —
01 Station address 1
02 Physics RS232
03 EasyServe Baudr. 19200
04 Format Data 8-O-1
0338
A 01 Language A 02 Units
Range: DEUTSCH Default: DEUTSCH Range: SI Default: SI
ENGLISH* NON-SI
AMERICAN ENG*
FRANCAIS Lets you change over displays and parameter inputs
ESPANOL from SI units to American units.
ITALIANO
Selection holds for all displays, event messages and American SI unit Conversion*
parameters. lb kg 1 lb = 0.453593 kg
t t 1 t = 0.907185 t = 2000 lb
f m 1 f = 0.3048 m
* identical inch cm 1 inch = 2,54 cm
B 05 Nominal Speed
Range: 0.001...50.0 m/s Default: 0.1000 m/s
B 06 START Source
Range: OP Default: OP
FB
DI
Note
To start/stop totalization, there is no single solution: G06 defines the totalizing counter tracking time.
If Parameter “Release” Q01 is set to “- -” , no release
OP : From INTECONT keyboard is required.
FB : Via fieldbus interface
DI : Using digital input. Default value is DI3.
You can also use any other free digital
input. Digital input operates
edge-controlled, i.e. if scale fails after
Alarm, remove START signal and re-apply.
0338
0338