E96-424
®
WARNING
INSTRUCTION MANUALS
DO NOT INSTALL, MAINTAIN, OR OPERATE THIS EQUIPMENT WITHOUT READING, UNDERSTANDING,
AND FOLLOWING THE PROPER Elsag Bailey INSTRUCTIONS AND MANUALS; OTHERWISE, INJURY OR
DAMAGE MAY RESULT.
AVERTISSEMENT
MANUELS D’OPÉRATION
NE PAS METTRE EN PLACE, RÉPARER OU FAIRE FONCTIONNER L’ÉQUIPEMENT SANS AVOIR LU,
COMPRIS ET SUIVI LES INSTRUCTIONS RÉGLEMENTAIRES DE Elsag Bailey. TOUTE NÉGLIGENCE À
CET ÉGARD POURRAIT ÊTRE UNE CAUSE D’ACCIDENT OU DE DÉFAILLANCE DU MATÉRIEL.
PERTURBATIONS DU PROCÉDÉ
L’ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L’ASPECT
SÉCURITAIRE DES ÉQUIPEMENTS CONTRÔLÉS PAR CE PRODUIT. L’AJUSTEMENT ET/OU L’EXTRAC-
TION DE CE PRODUIT PEUT OCCASIONNER DES À-COUPS AU PROCÉDÉ CONTRÔLE LORSQU’IL EST
INSÉRÉ DANS UNE SYSTÈME ACTIF. CES À-COUPS PEUVENT ÉGALEMENT OCCASIONNER DES
BLESSURES OU DES DOMMAGES MATÉREILS.
NOTICE
I-E96-424A
®
Preface Original
List of Effective Pages Original
iii through vi Original
1-1 through 1-5 Original
2-1 through 2-8 Original
3-1 Original
4-1 through 4-2 Original
5-1 Original
A-1 through A-3 Original
B-1 through B-3 Original
C-1 through C-3 Original
D-1 through D-2 Original
E-1 through E-3 Original
F-1 through F-2 Original
G-1 through G-2 Original
H-1 through H-4 Original
I-1 through I-3 óOriginal
When an update is received, insert the latest changed pages and dispose of the super-
seded pages.
NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-
gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in the
outer margin next to the figure caption. The date the update was prepared will appear beside the
page number.
I-E96-424A
®
Safety Summary
SPECIFIC We strongly recommend that you turn the cabinet power off before
CAUTIONS doing any termination unit wiring. Failure to do so could result in
equipment damage. Do not apply power until you verify all wire con-
nections. (p. 2-6)
Sommaire de Securite
vi I-E96-424A
Table of Contents
Page
SECTION 1 - INTRODUCTION ....................................................................................................1-1
OVERVIEW ..................................................................................................................1-1
INTENDED USER .........................................................................................................1-1
HARDWARE DESCRIPTION..........................................................................................1-2
FEATURES...................................................................................................................1-2
INSTRUCTION CONTENT .............................................................................................1-3
HOW TO USE THIS MANUAL .......................................................................................1-3
GLOSSARY OF TERMS AND ABBREVIATIONS .............................................................1-3
REFERENCE DOCUMENTS..........................................................................................1-4
NOMENCLATURE ........................................................................................................1-5
SPECIFICATIONS .........................................................................................................1-5
I-E96-424A iii
®
List of Tables
iv I-E96-424A
List of Figures
No. Title Page
I-E96-424A v
SECTION 1 - INTRODUCTION
OVERVIEW
INTENDED USER
CONTROLWAY
MFP
OTHER MODULES
DSO
OTHER SLAVES
TDI
DIGITAL
OUTPUTS T00641A
OVERVIEW
I-E96-424A 1-1
INTRODUCTION ®
HARDWARE DESCRIPTION
5. Two on-board fuses (F1 and F2) to protect the E1/E2 power
supplies and field devices connected to the termination unit.
FEATURES
Versatile The design of the TDI allows it to be used with a variety of INFI
90 modules. It can be used to input digital or analog signals to
the INFI 90 system, or output digital or analog signals to field
devices. These signals provide control and monitoring capabili-
ties to the system.
System Protection Fused power inputs protect INFI 90 module circuitry and pro-
cess field devices.
HARDWARE DESCRIPTION
1-2 I-E96-424A
INTRODUCTION
INSTRUCTION CONTENT
Maintenance Has a maintenance schedule for the termination unit and other
INFI 90 assemblies.
Term Definition
Controlway High speed version of the module bus. The redundant peer-to-peer communication
link that provides the communication path for point and status data transfer between
intelligent modules within a process control unit.
INSTRUCTION CONTENT
I-E96-424A 1-3
INTRODUCTION ®
Term Definition
Master Module One of a series of controller modules designed to direct field processes through a
slave module. The multi-function processor is an example.
Module Bus The serial communication link between a process control module and other process
control modules.
Module Mounting A card cage that provides electrical and communication support for INFI 90 modules.
Unit
Process Control Rack type industrial cabinet that contains master, slave and communication mod-
Unit ules, and their communication paths.
Termination Unit Provides input/output connection between plant equipment and the INFI 90 process
modules. The termination unit is a flat circuit board for panel mounting.
REFERENCE DOCUMENTS
REFERENCE DOCUMENTS
1-4 I-E96-424A
INTRODUCTION
NOMENCLATURE
Nomenclature Hardware
Modules
Cables
Mounting
Tools
SPECIFICATIONS
Environmental
NOMENCLATURE
I-E96-424A 1-5
SECTION 2 - INSTALLATION
INTRODUCTION
SPECIAL HANDLING
NOTE: Always use Bailey's Field Static Kit (P/N 1948385A2 - con-
sists of wrist strap, ground cord assembly, alligator clip) when work-
ing with modules. The kit is designed to connect a technician and
the static dissipative work surface to the same ground point to pre-
vent damage to the modules by electrostatic discharge.
SETUP/PHYSICAL INSTALLATION
Figure 2-1 shows the TDI and the location of the dipshunt
sockets (XU1 to XU17), terminal blocks (TB1 to TB4), cable
connector (P1), system power connectors (E1, E2 and E3) and
fuses (F1 and F2).
INTRODUCTION
I-E96-424A 2-1
INSTALLATION ®
3 3 3 3
A2 A6 B6 B2
4 4 4 4
5 5 5 5
A3 A7 B7 B3
6 6 6 6
XU17
1
7 7 2 7 7
3
4
A4 A8 5
B8 B4
6
8 8 7
8 8
8
F2 F1
E3
E2 E1
T00642A
Physical Installation
1. Insert the TDI circuit board tabs into the termination panel
standoff slots; slide the circuit board into position.
Installing Dipshunts
SETUP/PHYSICAL INSTALLATION
2-2 I-E96-424A
INSTALLATION
TABS
STANDOFF
MOUNTING SCREWS
TB1 TB4
TB2 TB3
TB3 TB2
TB4 TB1
T00643A
SETUP/PHYSICAL INSTALLATION
I-E96-424A 2-3
INSTALLATION ®
E1 E2 E COM
1 16
2 15
3 14
4 13 TERMINAL
P1 BLOCKS
5 12
6 11 TB1-TB4
7 10
8 9
E1 E CO M
DIPSHUNTS
XU1-XU16 T00644A
E1 E2 E CO M E1 E2 E CO M
1 16 1 16
2 15 2 15
16 3 14 TB3 3 14 TB3
4 13 1 4 13 3
P1 POINT P1 POINT
13 5 12 17 5 12
2 5A 4 6A
6 11 6 11
7 10 7 10
8 9 8 9
E1
1 16
2 15
18 3 14
4 13
P1
5 12
6 11
34 7 10
8 9
DIPSHUNT
XU17
E1 E2 E CO M E1 E2 E CO M
1 16 1 16
2 15 2 15
32 3 14 TB2 3 14 TB2
4 13 1 4 13 3
P1 POINT P1 POINT
31 5 12 33 5 12
2 5B 4 6B
6 11 6 11
7 10 7 10
8 9 8 9
SETUP/PHYSICAL INSTALLATION
2-4 I-E96-424A
INSTALLATION
5. Repeat steps two through four until all required sockets are
configured.
Installing Fuses
Cable Connections
1. Insert the hooded end of the cable into the module mount-
ing unit backplane slot assigned to the master/slave module.
The cable should latch securely in place. P3 of the master/
slave module in the module mounting unit connects to this end
of the cable.
P1
NKTU01
MASTER/SLAVE MODULE P3 P1 NTDI01 16 I/O POINTS
P2
T00646A
NOTES:
1. Proper polarity wiring is required for DC signals.
2. There are only 30 pins on the master/slave module P3 connec-
tor; the termination unit can handle 16 I/O points. When using points
7 and 8 of each group, the positive (+) side of these points share a
pin (A7 - A8 and B7 - B8). Refer to Table 2-1.
PRE-OPERATING ADJUSTMENTS
P1 PIN OUT
PRE-OPERATING ADJUSTMENTS
I-E96-424A 2-7
INSTALLATION ®
NKTU01 NKTU01
P31 P12 P31 P12
1 −− −− −− −− −− −− 1 J −− −− −− −− −− −− 22
A −− −− −− −− −− −− 2 9 −− −− −− −− −− −− 23
2 −− −− −− −− −− −− 3 K −− −− −− −− −− −− 24
B −− −− −− −− −− −− 4 10 −− −− −− −− −− −− 25
3 −− −− −− −− −− −− 5 L −− −− −− −− −− −− 26
C −− −− −− −− −− −− 6 11 −− −− −− −− −− −− 27
4 −− −− −− −− −− −− 7 M −− −− −− −− −− −− 28
D −− −− −− −− −− −− 8 12 −− −− −− −− −− −− 29
5 −− −− −− −− −− −− 13 N −− −− −− −− −− −− 30
E −− −− −− −− −− −− 16 13 −− −− −− −− −− −− 31
6 −− −− −− −− −− −− 17 P −− −− −− −− −− −− 32
F −− −− −− −− −− −− 18 14 −− −− −− −− −− −− 33
7 −− −− −− −− −− −− 19 R −− −− −− −− −− −− 34
H −− −− −− −− −− −− 20 15 −− −− −− −− −− −− 35
8 −− −− −− −− −− −− 21 S −− −− −− −− −− −− 36
NOTES:
1. P3 on master/slave module
2. P1 on NTDI01
INTRODUCTION
MAINTENANCE SCHEDULE
Task Interval
Clean and tighten all power and Every six months or during plant
grounding connections shutdown, whichever occurs first
Use a static safe vacuum cleaner to Every six months or during plant
remove dust from: shutdown, whichever occurs first
Modules
Module Mounting Unit
Fan Assembly
Power Entry Panel
Termination Units/Modules
INTRODUCTION
I-E96-424A 3-1
SECTION 4 - REPAIR/REPLACEMENT PROCEDURES
INTRODUCTION
• Chip puller.
REPLACEMENT PROCEDURES
A TDI does not have any active components. This limits any
replacement requirements due to failure. To remove a TDI:
5. Remove the two screws securing the TDI to the field termi-
nation panel and slide the termination unit out. The screws
secure the termination unit to the field termination panel, be
sure to hold the termination unit while removing the screws.
6. Either remove the dipshunts from the old TDI and install
them in the new one, or configure and install new dipshunts
exactly as configured on the old termination unit. Refer to the
appropriate appendix for dipshunt strappings.
NOTE: Cut the dipshunt straps using a standard shunt cutting tool.
Always make sure that the cut straps are completely broken and that
adjacent straps are not touching.
INTRODUCTION
I-E96-424A 4-1
REPAIR/REPLACEMENT PROCEDURES ®
8. Insert the TDI circuit board tabs into the termination panel
standoff slots; slide the circuit board into position. Refer to Fig-
ure 2-2.
REPLACEMENT PROCEDURES
4-2 I-E96-424A
SECTION 5 - SUPPORT SERVICES
INTRODUCTION
When you order standard parts from Bailey Controls, use part
numbers and descriptions from the Spare Parts List Table 5-1.
You must order parts without commercial descriptions from
the nearest Bailey Controls sales office.
TRAINING
TECHNICAL DOCUMENTATION
You can obtain additional copies of this manual from the near-
est Bailey Controls sales office at a reasonable charge.
INTRODUCTION
I-E96-424A 5-1
APPENDIX A - ANALOG SLAVE OTPUT MODULE
(IMASO01)
INTRODUCTION
+24 VDC
E1 E2 ECO M
1
2
+ 3
+
4
FEEDBACK P3 P1 LOAD
5
– –
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M DIPSHUNTS
XU1-XU7,
XU9-XU11,
XU13-XU16
INTRODUCTION
I-E96-424A A-1
ANALOG SLAVE OTPUT MODULE (IMASO01) ®
+24 VDC
E1 E2 ECO M
1
2
+ 3
+
4
P3 P1 LOAD
5
FEEDBACK – –
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M DIPSHUNTS
XU1-XU7,
XU9-XU11,
XU13-XU16
XU12
24 VDC Power to Slave XU12
1 2 3 4 5 6 7 8
XU17
Signal Routing for Channels XU17
6 and 13 1 2 3 4 5 6 7 8
T00649A
INTRODUCTION
A-2 I-E96-424A
ANALOG SLAVE OTPUT MODULE (IMASO01) ®
1 + + + +
AO1 XU13 AO5 XU9 AO12 XU5 AO8 XU1
2 – – – –
3 + + + +
AO2 XU14 AO6 XU10 AO13 XU6 AO9 XU2
4 – – – –
TERMINAL
NUMBER
5 + + + +
AO3 XU15 AO7 XU11 AO14 XU7 AO10 XU3
6 – – – –
7 + + + +
AO4 XU16 NC XU12 NC XU8 AO11 XU4
8 – – – –
T00650A
INTRODUCTION
A-3 I-E96-424A
APPENDIX B - DIGITAL I/O SLAVE MODULE
(IMDSM05)
DIGITAL I/O SLAVE MODULE (IMDSM05)
+5 +24
VDC VDC
E1 E2 ECO M
1
2
3
– –
4 FIELD
P3 P1 CONTACT
5
+ +
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M
DIPSHUNTS
XU1-XU16
+5 +24
VDC VDC
E1 E2 ECO M
1
2
3
– –
4 FIELD
P3 P1 CONTACT
5
+ +
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M
DIPSHUNTS
XU1-XU16
T00652A
Powering an Exter- 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
nal Load
T00652A
Sinking an External 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Load
T00652A
Isolated Outputs 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
T00652A
NOTES:
1. When using the 24 VDC Logic I/O, System Powered Contact Input or Two Wire Isolated
Output configurations, some of the I/O points are connected internally on the termination unit:
A5(-)and A6(-), A7(-) and A8(-), B5(-) and B6(-), and B7(-) and B8(-).
2. When using the Powering An External Load configuration, all positive connection points are in-
ternally wired on the termination unit to the +24 VDC I/O power.
1 – – – –
A1 XU13 A5 XU9 B5 XU5 B1 XU1
2 + + + +
3 – – – –
A2 XU14 A6 XU10 B6 XU6 B2 XU2
4 + + + +
TERMINAL
NUMBER
5 – – – –
A3 XU15 A7 XU11 B7 XU7 B3 XU3
6 + + + +
7 – – – –
A4 XU16 A8 XU12 B8 XU8 B4 XU4
8 + + + +
T00653A
NOTE: When using the Sinking An External Load configuration, make external connections to the negative terminals only.
+5 VDC
E1 E2 ECO M
1
2
3
+ +
4 FIELD
P3 P1 CONTACT
5
– –
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M
DIPSHUNTS
XU1-XU16
INTRODUCTION
I-E96-424A C-1
DIGITAL SLAVE INPUT MODULE (IMDSI02) ®
XU17
1 2 3 4 5 6 7 8
XU17
1 2 3 4 5 6 7 8
XU17
1 2 3 4 5 6 7 8
T00654A
NOTE: Each TDI input point dipshunt configuration must match the DSI input jumper configuration.
INTRODUCTION
C-2 I-E96-424A
DIGITAL SLAVE INPUT MODULE (IMDSI02)
1 + + + +
A1 XU13 A5 XU9 B5 XU5 B1 XU1
2 – – – –
3 + + + +
A2 XU14 A6 XU10 B6 XU6 B2 XU2
4 – – – –
TERMINAL
NUMBER
5 + + + +
A3 XU15 A7 XU11 B7 XU7 B3 XU3
6 – – – –
7 + + + +
A4 XU16 A8 XU12 B8 XU8 B4 XU4
8 – – – –
T00655A
NOTE: When using the System Powered contact configuration, the polarities shown in Figure C-2 should be reversed.
INTRODUCTION
I-E96-424A C-3
APPENDIX D - DIGITAL SLAVE OUTPUT MODULE
(IMDSO01/02/03)
DIGITAL SLAVE OUTPUT MODULE (IMDSO01/02/03)
+5 VDC E1 E2 ECO M
1
+ 2
3
+ +
4
P3 P1 LOAD
5
– –
– 6
7 TERMINAL
8 BLOCKS
SOLID STATE
TB1-TB4
RELAY DIPSHUNTS
E1 E CO M
XU1, XU3, XU5,
XU7, XU9, XU11,
XU13, XU15
Dipshunt Configuration
Application/Signal Type
XU1, 3, 5, 7, 9, 11, 13, 15
Externally Powered 1 2 3 4 5 6 7 8
T00657A
NOTES:
1. XU17 does not require a dipshunt for this application.
2. Care must be taken when powering solid state relay loads through the E1 and E2 connectors.
The traces on the termination unit allow for two amperes for all outputs driven from either E1 or E2.
Exceeding this current can damage the termination unit printed circuit board. Where higher current
is required, use the externally powered configuration.
1 – – – –
DO1 XU13 DO3 XU9 DO7 XU5 DO5 XU1
2 + + + +
4
TERMINAL
NUMBER
5 – – – –
DO2 XU15 DO4 XU11 DO8 XU7 DO6 XU3
6 + + + +
8
T00658A
+5 VDC
E1 E2 ECO M
1
2
+ 3
+
4
P3 P1 LOAD
5
– –
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M
DIPSHUNTS
XU1-XU16
INTRODUCTION
I-E96-424A E-1
DIGITAL SLAVE OUTPUT MODULE (IMDSO04) ®
XU17
1 2 3 4 5 6 7 8
XU17
1 2 3 4 5 6 7 8
XU17
1 2 3 4 5 6 7 8
T00661A
NOTE:
1. XU17 does not require a dipshunt for this application.
2. Care must be taken when powering solid state relay loads through the E1 and E2 connectors.
The traces on the termination unit allow for two amperes for all outputs driven from either E1 or E2.
Exceeding this current can damage the termination unit printed circuit board. Where higher current
is required, use the externally powered configuration.
INTRODUCTION
E-2 I-E96-424A
DIGITAL SLAVE OUTPUT MODULE (IMDSO04)
1 + + + +
A1 XU13 A5 XU9 B5 XU5 B1 XU1
2 – – – –
3 + + + +
A2 XU14 A6 XU10 B6 XU6 B2 XU2
4 – – – –
TERMINAL
NUMBER
5 + + + +
A3 XU15 A7 XU11 B7 XU7 B3 XU3
6 – – – –
7 + + + +
A4 XU16 A8 XU12 B8 XU8 B4 XU4
8 – – – –
T00655A
INTRODUCTION
I-E96-424A E-3
APPENDIX F - PULSE INPUT SLAVE MODULE
(IMDSM04)
INRODUCTION
+5 VDC
E1 E2 ECO M
1
2
3
+ +
4 FIELD
P3 P1 CONTACT
5
– –
6
7 TERMINAL
8 BLOCKS
TB1/TB4
E1 E CO M DIPSHUNTS
XU1-XU4,
XU13-XU16
INRODUCTION
I-E96-424A F-1
PULSE INPUT SLAVE MODULE (IMDSM04) ®
Dipshunt Dipshunt
Application/Signal
Configuration Configuration
Type
XU1-XU4, X13-X16 XU7
System Powered from 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
E1
T00663A
T00663A
NOTE: XU7, in this application, connects 24 VDC I/O power to the IMDSM04 preamplifiers. If the
reamplifiers are not used, a dipshunt is not required for XU7.
DIPSHUNT DIPSHUNT
TB4 USED TB1 USED
1 + +
DI1 XU13 DI5 XU1
2 – –
3 + +
DI2 XU14 DI6 XU2
4 – –
TERMINAL
NUMBER
5 + +
DI3 XU15 DI7 XU3
6 – –
7 + +
DI4 XU16 DI8 XU4
8 – –
INRODUCTION
F-2 I-E96-424A
APPENDIX G - FREQUENCY COUNTER SLAVE
MODULE (IMFCS01)
FREQUENCY COUNTER SLAVE MODULE (IMFCS01)
E1 E2 E CO M
1
2
– 3
+ –
4 FIELD
P3 P1 DEVICE
– 5
+
+ 6
7 TERMINAL
8 BLOCK
TB4
E1 ECO M
DIPSHUNT
XU13
DIPSHUNT
TB4 USED
1 –
INPUT XU13
2 +
4
TERMINAL
NUMBER
5
Figure H-1, H-2, H-3 and H-4 show an NTDI01 point configu-
ration dipshunt without strapping, and the signal path from
the HSS to the field device for a termination unit application.
Figure H-5 shows the terminal assignment and polarity for
each of the I/O signals. Refer to this figure when connecting
field wiring to the NTDI01. Refer to Table H-1 to determine the
dipshunt strapping to configure your application.
+5 VDC
E1 E2 ECO M
1
2
3
+ +
4 FIELD
P3 P1 CONTACT
5
– –
6
7 TERMINAL
8 BLOCKS
TB3/TB2
E1 E CO M DIPSHUNTS
XU5, XU9,
XU11
INTRODUCTION
I-E96-424A H-1
HYDRAULIC SERVO SLAVE MODULE (IMHSS01) ®
+5 VDC
E1 E2 ECO M
1
2
+ 3
+
4
P3 P1 LOAD
5
– –
6
7 TERMINAL
8 BLOCK
TB2
E1 E CO M
DIPSHUNT
XU7
E1 E2 E CO M
1
2
+ 3
+ +
4 FIELD
P3 P1 DEVICE
– 5
– –
6
7 TERMINAL
8 BLOCK
TB1
E1 ECO M DIPSHUNTS
XU2, XU3
INTRODUCTION
H-2 I-E96-424A
HYDRAULIC SERVO SLAVE MODULE (IMHSS01)
E1 E2 E CO M
1
2
– + 3
+
4 FIELD
+ P3 P1 DEVICE
5
– –
6
7 TERMINAL
8 BLOCK
TB1/TB4
E1 ECO M
DIPSHUNTS
XU1, XU4,
XU13, XU14
1 + + + + LVDT PRI
SERVO 1 RAISE LOWER
XU13 XU9 XU5 XU1
OUTPUT INPUT INPUT
2 – – – – DRV OUT
LVDT
3 + 1
SERVO 2 SEC. 1
OUTPUT XU14 XU2
4 – 2 INPUT
TERMINAL
NUMBER
5 + TRIP + EMER. 1 LVDT
BIAS XU11 XU7 SEC. 2
MAN. XU3
6 – INPUT – OUTPUT 2 INPUT
7 + SIM
MODE
XU4
8 – OUTPUT
T00672A
INTRODUCTION
I-E96-424A H-3
HYDRAULIC SERVO SLAVE MODULE (IMHSS01) ®
Dipshunt
Application/Signal Type
Configuration
All Types XU17
1 2 3 4 5 6 7 8
LVDT Secondary 2
Simulation Mode
Servo 1 Drive
Servo 2 Drive
Digital Inputs
XU1, XU4, XU13, XU14
Lower, Raise and Trip Bias 1 2 3 4 5 6 7 8
24 VDC Field Powered Contacts
1 2 3 4 5 6 7 8
System Powered from E2 (24 VDC)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
T00673A
INTRODUCTION
H-4 I-E96-424A
APPENDIX I - LOGIC MASTER MODULE (IMLMM02)
INTRODUCTION
+5 VDC
E1 E2 ECO M
1
2
3
+ +
4 FIELD
P3 P1 CONTACT
5
– –
6
7 TERMINAL
8 BLOCKS
TB1/TB2
E1 E CO M
DIPSHUNTS
XU1-XU8
INTRODUCTION
I-E96-424A I-1
LOGIC MASTER MODULE (IMLMM02) ®
+5 VDC
E1 E2 ECO M
1
2
– 3
–
4
P3 P1 LOAD
5
+ +
6
7 TERMINAL
8 BLOCKS
TB3/TB4
E1 E CO M
DIPSHUNTS
XU9-XU16
Outputs Inputs
Application/Signal Dipshunt Application/Signal Dipshunt
Type Configuration Type Configuration
Isolated Output/Field XU9-XU16
Field Powered Input XU1-XU8
Powered Output 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
All XU17
All XU17
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
T00676A
NOTES:
1. When using the Field Powered Input, Isolated Output or Field Powered Output configurations, some of the I/O points are connected in-
ternally on the termination unit: A5(-) and A6(-), A7(-) and A8(-), B5(-) and B6(-), and B7(-) and B8(-).
2. When using the Powering An External Load configuration, all positive connection points are internally wired on the termination unit to the
+24 VDC I/O power.
INTRODUCTION
I-2 I-E96-424A
LOGIC MASTER MODULE (IMLMM02)
1 – – + +
A1 XU13 A5 XU9 B5 XU5 B1 XU1
2 + + – –
3 – – + +
A2 XU14 A6 XU10 B6 XU6 B2 XU2
4 + + – –
TERMINAL
NUMBER
5 – – + +
A3 XU15 A7 XU11 B7 XU7 B3 XU3
6 + + – –
7 – – + +
A4 XU16 A8 XU12 B8 XU8 B4 XU4
8 + + – –
T00677A
NOTES:
1. When using the Sinking An External Load configuration, make external connections to the positive terminals only.
2. When using the System Powered Input from E1/E2 configuration, the polarities indicated in Figure I-3 for TB1 and TB2 should be reversed.
INTRODUCTION
I-E96-424A I-3