Académique Documents
Professionnel Documents
Culture Documents
FPN:The construction information is per NEMA WC8-1992 or ANSI/UL 1581-1998. The resistance is calculated per National Bureau of Standards Handbook 100, dated 1966, and
Handbook 109, dated 1972.
Traditionally, wire sizes have been expressed as American Wire Gage (AWG), circular mil (cmil) area, or thousands of circular mil (kcmil) area. Today, wire is available with its cross-
sectional area expressed in square millimeters (mm²) as well.
The 2002 NEC specifically requires that insulated conductors be marked with their sizes and that the sizes be expressed in either American Wire Gage or circular mil area. [See 110.6 and 310.11(A)
(4).] There are no exceptions to either of these two requirements. Because Article 310 does not specifically prohibit optional marking on insulated conductors, the Code permits square millimeter
(mm2) markings on conductors, but only if they are in addition to the required traditional markings of AWG or circular mil area.
According to the American National Standards Institute (ANSI), in SI 10-1997, Standard for Use of the International System of Units (SI): The Modern Metric System, to convert circular mils to square
meters, you would multiply circular mils by 5.067075 × 10-10. However, because square millimeters, rather than square meters, is the standard marking for wire size, and because the reciprocal is
more appropriate for this conversion, a simpler conversion factor to convert from square millimeters to circular mils (approximately) follows:
Example
What traditional wire size does the size 125 mm² approximately represent?
Solution
Conclusion If a 125-mm² wire is determined to be the minimum or recommended size conductor, it is important to understand that size 250 kcmil would be the only Table 8 conductor with equivalent
cross-sectional area. Size 4/0 AWG is simply not enough metal, so 250 kcmil would be the choice for minimum equivalency. However, it is important to note that the 250-kcmil conductor ampacity
could not be used for a 125-mm² conductor because the metric conductor size is smaller. The 4/0 AWG ampacity can be used, or the ampacity can be calculated under engineering supervision.