Project Name:NAS

External Static Pressure Calculation-AHU-CP-GF-11


SEC DESCRIPTION
NO

PIPE / FITTING

AIR
FLOW
L/S

VELOCIT VELOCITY
LENGTH
DUCT
TOTAL
SECTION
Y
PRESSURE
Fitting loss
PRESSURE PRESSURE PRESSURE
Coefficient
LOSS
LOSS
LOSS
Width Height
m/s
Pa
m
DUCT
SIZE(mm)

SUPPLY SIDE
1

Pa / m

Transition

1270

10

400

5.00

15.05

Duct

1270

800

400

4.36

11.40

0.42
1.52

Pa

Pa

6.32
0.34

Sound Attenuator 1270

0.52
50.00

Elbow (45)

1270

600

350

4.36

11.40

0.31

3.53

Tee Main

1270

800

400

4.36

11.40

0.04

0.46

Duct

1114

800

350

4.42

11.87

Tee Branch

1114

800

350

4.42

11.87

60.83
2

1.52

0.38
0.74

0.58
8.78
9.36

Duct

958

600

400

4.30

11.22

VCD

958

600

400

4.30

11.22

Tee Main

958

600

400

4.30

11.22

2.61

0.391

1.02
8.00

0.05

0.56
9.58

Duct

802

600

350

4.14

10.43

Elbow (90)

802

600

350

4.14

10.43

2.57
0.51

0.398

1.02
5.32

Tee Main

802

600

350

4.14

10.43

0.05

0.52
6.87

Duct

646

600

300

3.94

9.43

Tee Main

646

600

300

3.94

9.43

4.03
0.04

0.401

1.62

0.38
1.99

Duct

490

550

250

3.93

9.45

Tee Main

490

550

250

3.93

9.45

3.41

0.477
0.07

1.63
0.66
2.29

Duct

334

400

250

3.60

7.86

Tee Main

334

400

250

3.60

7.86

Duct

178

350

200

2.76

4.65

Tee Main

178

350

200

2.76

4.65

3.34

0.481
0.16

1.61
1.26
2.86

3.34

0.369
0.19

1.23
0.88
2.12

Duct

156

350

200

2.42

3.57

Elbow (90)

156

350

200

2.42

3.57

3.48
0.51

0.29

1.01
1.82

Tee Branch

1114

350

200

2.42

3.57

0.73

2.61

Diffuser

156

300

300

10.00
15.44
111.34
SAFETY MARGIN 20%

22.27
GRAND TOTAL

133.60

TOTAL EXTERNAL STATIC PRESSURE REQUIRED FOR FAN IS 134Pa

PAGE : 1 OF 4

Project Name:SOUND STAGES COMPLEX AT DUBAI STUDIO CITY


External Static Pressure Calculation-AHU-CP-GF-19
SEC DESCRIPTION
NO

PIPE / FITTING

AIR
FLOW
L/S

VELOCIT VELOCITY
LENGTH
DUCT
TOTAL
SECTION
Y
PRESSURE
Fitting loss
PRESSURE PRESSURE PRESSURE
Coefficient
LOSS
LOSS
LOSS
Width Height
m/s
Pa
m
DUCT
SIZE(mm)

Pa/m

Pa

Pa

SUPPLY SIDE
1

Transition

6109

1500

600

8.00

38.5

Duct

6109

1500

600

7.61

35.2

0.42
3.7

16.17
0.53

Sound Attenuator 6109


Tee main

6109

1.96
50.00

1500

600

7.61

35.2

0.04

1.41
69.54

Duct

5702

1500

600

7.10

31

Tee main

5702

1500

600

7.10

31

1.85

0.47
0.04

0.87
1.23
2.10

Duct

4887

1500

600

6.09

22.53

Tee main

4887

1500

600

6.09

22.53

2.12

0.35
0.04

0.74
0.90
1.64

Duct

4480

1300

650

5.82

20.58

Tee branch

4480

1300

650

5.82

20.58

VCD

4480

1300

650

5.82

20.58

3.85

0.33
0.97

1.27
19.96
15.00
36.23

Duct

2036

950

450

5.25

16.76

Tee main

2036

950

450

5.25

16.76

Duct

1629

900

400

5.02

15.31

Tee main

1629

900

400

5.02

15.31

6.32

0.41
0.05

2.59
0.84
3.43

3.97

0.42
0.11

1.67
1.68
3.35

Duct

1222

800

400

4.19

10.68

Tee main

1222

800

400

4.19

10.68

3.91

0.32
0.04

1.25
0.43
1.68

Duct

815

700

300

4.32

11.34

Tee main

815

700

300

4.32

11.34

3.89

0.44
0.1

1.71
1.13
2.85

Duct

407

500

250

3.57

7.76

Tee branch

407

500

250

3.57

7.76

Diffuser

407

450

450

2.14

2.79

5.57

0.42
0.73

2.34
5.66
10
18.00
138.82

SAFETY MARGIN 20%

27.76
GRAND TOTAL

166.58

TOTAL EXTERNAL STATIC PRESSURE REQUIRED FOR FAN IS 167 Pa

PAGE : 2 OF 4

Project Name:NAS
External Static Pressure Calculation-AHU-CP-GF-09
SEC DESCRIPTION
NO

PIPE / FITTING

AIR
FLOW
L/S

VELOCIT VELOCITY
DUCT
LENGTH
TOTAL
SECTION
Y
PRESSURE
Fitting loss PRESSURE
PRESSURE PRESSURE
Coefficient
LOSS
LOSS(pa)
LOSS
(pa/m)
Width Height
m/s
Pa
m
DUCT
SIZE(mm)

SUPPLY SIDE
1

Transition

1425

850

400

5.00

15.05

Duct

1425

850

400

4.62

13.00

0.42
3

6.32
0.37

Sound Attenuator 1425


Tee branch

1425

1.11
50.00

850

400

4.62

13.00

0.72

9.36
66.79

Duct

1188

700

400

3.85

9.03

Elbow (45)

1188

700

400

3.85

9.03

2.35
0.31

0.26

0.61
2.80

Tee Main

1188

700

400

3.85

9.03

0.04

0.36
3.77

Duct

1069

700

400

4.15

10.46

Tee branch

1069

700

400

4.15

10.46

VCD

1069

700

400

4.15

10.46

1.98

0.34
1.14

0.67
11.92
40.00
52.59

Duct

475

500

300

3.43

7.15

Tee Main

475

500

300

3.43

7.15

3.23

0.34
0.04

1.10
0.29
1.38

Duct

356

450

250

3.44

7.21

1.89

0.41

0.77

Elbow (90)

356

450

250

3.44

7.21

0.51

3.68

Tee Main

356

450

250

3.44

7.21

0.1

0.72
5.17

Duct

238

350

250

2.92

5.19

Tee Main

238

350

250

2.92

5.19

2.19

0.35
0.08

0.77
0.42
1.18

Duct

119

250

200

2.54

3.93

3.16

0.37

Elbow (90)

119

250

200

2.54

3.93

0.47

Tee branch

119

250

200

2.54

3.93

0.73

Diffuser

119

225

225

2.51

3.82

1.17
1.85
2.87
10.00
15.89
146.78

SAFETY MARGIN 20%

29.36
GRAND TOTAL

176.13

TOTAL EXTERNAL STATIC PRESSURE REQUIRED FOR FAN IS177 Pa

PAGE : 3 OF 4

Project Name:NAS
External Static Pressure Calculation-AHU-CP-GF-11
SEC DESCRIPTION
NO

PIPE / FITTING

AIR
FLOW
L/S

VELOCIT VELOCITY
LENGTH
DUCT
TOTAL
SECTION
Y
PRESSURE
Fitting loss
PRESSURE PRESSURE PRESSURE
Coefficient
LOSS
LOSS
LOSS
Width Height
m/s
Pa
m
DUCT
SIZE(mm)

RETURN SIDE
1

Pa / m

Pa

Grile

410

1000

250

1.95

2.32

Plenum box

410

1000

250

1.95

2.32

Firedamper

410

1000

250

1.95

2.32

0.19

0.44

Transition

410

400

300

3.66

8.15

1.73

14.10

Duct

410

400

300

3.66

8.15

Elbow (90)

410

400

300

3.66

8.15

Plenum box

410

450

350

3.66

8.15

Pa

10.00
0.1

0.09

2.2

0.44
0.48

1.78

0.01

0.97
3.91

0.22

0.40
29.83

SUPPLY SIDE
2

Transition

410

400

300

4.16

10.38

Duct

410

400

300

3.66

8.15

Transition

410

400

300

3.66

8.15

Firedamper

410

1000

250

1.95

2.32

Plenum box

410

1000

250

1.95

2.32

Grile

410

1000

250

1.95

2.32

1.73
1.12

17.96
0.44

1.73

14.10

0.19
0.1

0.49
0.44

0.09

0.01
10.00
43.00
72.82

SAFETY MARGIN 20%

14.56
GRAND TOTAL

87.39

TOTAL EXTERNAL STATIC PRESSURE REQUIRED FOR FAN IS87Pa

PAGE : 4 OF 4

Vous aimerez peut-être aussi