Vous êtes sur la page 1sur 2

Overhead Conductors

Electric Utility

TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089

Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded

ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED


(MECHANICAL PROPERTIES)

CODE
WORD (1)

CONDUCTOR SIZE
AWG OR
kcmil
mm2

STRANDING
NO. X DIA. INCHES
AL

STEEL

CROSS-SECTION
SQ. INCHES
TOTAL

AL

APPROX. WEIGHT
LB/1000 FT (2)

O.D.
INCHES

mm

TOTAL

AL

STEEL

PERCENT
BY MASS

RATED
STRENGTH

AL

LB

kN

STEEL

Turkey

13.3

6x0.0661 1x0.0661 0.0240 0.0206 0.198

5.04

36.1

24.5

11.6

67.90 32.10

1160

5.16

Swan

21.1

6x0.0834 1x0.0834 0.0382 0.0328 0.250

6.36

57.4

38.9

18.4

67.89 32.11

1830

8.14

Swanate

21.1

7x0.0772 1x0.1029 0.0411 0.0328 0.257

6.54

67.0

38.9

28.0

58.13 41.87

2300

10.2

Sparrow

33.6

6x0.1052 1x0.1052 0.0608 0.0522 0.316

8.01

91.2

61.9

29.3

67.87 32.13

2800

12.5

Sparate

33.6

7x0.0974 1x0.1299 0.0654 0.0522 0.325

8.24

106.6

61.9

44.7

58.08 41.92

3510

15.6

Robin

42.4

6x0.1181 1x0.1181 0.0767 0.0657 0.354

9.00

115.0

78.1

36.9

67.88 32.12

3480

15.5

Raven

1/0

53.5

6x0.1327 1x0.1327 0.0968 0.0830 0.398

10.1

145.1

98.5

46.6

67.87 32.13

4250

18.9

Quail

2/0

67.4

6x0.1489 1x0.1489 0.1219 0.1045 0.447

11.3

182.9 124.2

58.7

67.89 32.11

5280

23.5

Pigeon

3/0

85.0

6x0.1672 1x0.1672 0.1537 0.1317 0.502

12.7

230.6 156.5

74.0

67.89 32.11

6660

29.6

Penguin

4/0

107.2

6x0.1878 1x0.1878 0.1939 0.1662 0.563

14.3

290.8 197.4

93.4

67.88 32.12

8400

37.4

Owl

266.8

135.2

6x0.2109 7x0.0703 0.2368 0.2096 0.633

16.1

341.0

249

92

73.01 26.99

9500

42.3

Waxwing

266.8

135.2 18x0.1217 1x0.1217 0.2210 0.2094 0.609

15.5

289.0

250

39

86.43 13.57

7000

31.1

Spoonbill

266.8

135.2 22x0.1101 7x0.0612 0.2300 0.2095 0.624

15.9

320.0

250

70

78.20 21.80

8800

39.1

Scaup

266.8

135.2 24x0.1054 7x0.0703 0.2366 0.2094 0.633

16.1

342.0

250

92

73.11 26.89 10100

44.9

Partridge

266.8

135.2 26x0.1013 7x0.0788 0.2437 0.2095 0.642

16.3

366.0

250

116

68.42 31.58 11300

50.3

STANDARD PACKAGES (3)


WT LENGTH
REEL DESIG. kg
M
NR 30.22
COIL
NR 36.22
COIL
RW 40.18
NR 30.22
COIL
RW 48.24
NR 36.22
NR 30.22
COIL
RW 48.24
NR 30.22
COIL
RW 48.24
NR 36.22
NR 30.22
COIL
RW 48.24
NR 36.22
NR 30.22
COIL
RW 48.24
NR 36.22
NR 30.22
RW 48.24
NR 36.22
NR 30.22
RW 48.24
NR 36.22
NR 30.22
RM 68.38
RW 60.32
RW 48.24
RM 68.38
RW 66.36
RW 50.32
RM 68.38
RW 60.32
RW 50.32
RM 68.38
RW 66.36
RW 60.32
RW 60.32

268
88
401
100
544
272
109
803
401
268
100
544
272
109
801
401
268
100
803
401
268
100
803
401
268
801
401
268
803
401
268
2237
1118
559
1882
1882
941
1275
1275
851
1481
1481
989
1719

4980
1646
4700
1169
5459
2729
1091
5910
2955
1970
735
3429
1714
686
4681
2341
1560
582
3715
1858
1237
462
2947
1474
981
2338
1169
780
1853
927
617
4407
2204
1102
4377
4377
2188
2668
2668
1778
2902
2902
1935
3148

(1) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(2) Due to rounding, total values may be slightly greater or slightly less than the sum of the component values.
(3) Weights shown are for conductor only and do not include the reel. Normal length and shipping tolerances apply.
Dimensions and weights not designated minimum or maximum are nominal values and subject to manufacturing tolerances. In this context, weight means mass.

74

Electric Utility

Overhead Conductors

TransPowr ACSR Bare Overhead Conductor to CAN/CSA C61089

Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded

ACSR, ALUMINUM CONDUCTOR, STEEL-REINFORCED, CONCENTRIC-LAY-STRANDED


(ELECTRICAL PROPERTIES)

CODE
WORD (4)

CONDUCTOR SIZE
AWG OR
kcmil
mm2

STRANDING
NO. X DIA. INCHES
AL

STEEL

CROSS-SECTION
SQ. INCHES
TOTAL

AL

INCHES

mm

RESISTANCE (5)
GEOMETRIC INDUCTIVE CAPACITIVE
OHMS/1000 FT
MEAN
REACTANCE REACTANCE
DC
AC
AC AMPACITY RADIUS OHM/1000 FT MEGAOHM
@ 20C @ 25C @ 75C 75C (6)
FT
(7)
1000 FT (7)

O.D.

Turkey

13.3

6x0.0661 1x0.0661 0.0240

0.0206

0.198

5.04

0.658

0.671

0.804

95

0.0064

0.1163

0.7512

Swan

21.1

6x0.0834 1x0.0834 0.0382

0.0328

0.250

6.36

0.414

0.422

0.505

125

0.0080

0.1109

0.7148

Swanate

21.1

7x0.0772 1x0.1029 0.0411

0.0328

0.257

6.54

0.414

0.422

0.505

125

0.0085

0.1096

0.7104

Sparrow

33.6

6x0.1052 1x0.1052 0.0608

0.0522

0.316

8.01

0.260

0.265

0.318

165

0.0101

0.1056

0.6785

Sparate

33.6

7x0.0974 1x0.1299 0.0654

0.0522

0.325

8.24

0.260

0.265

0.318

165

0.0107

0.1043

0.6741

Robin

42.4

6x0.1181 1x0.1181 0.0767

0.0657

0.354

9.00

0.206

0.210

0.252

190

0.0113

0.1029

0.6603

Raven

1/0

53.5

6x0.1327 1x0.1327 0.0968

0.0830

0.398

10.1

0.163

0.167

0.200

220

0.0127

0.1003

0.6421

Quail

2/0

67.4

6x0.1489 1x0.1489 0.1219

0.1045

0.447

11.3

0.130

0.132

0.158

250

0.0143

0.0976

0.6240

Pigeon

3/0

85.0

6x0.1672 1x0.1672 0.1537

0.1317

0.502

12.7

0.103

0.105

0.126

285

0.0161

0.0950

0.6059

Penguin

4/0

107.2

6x0.1878 1x0.1878 0.1939

0.1662

0.563

14.3

0.0816

0.0833

0.100

325

0.0180

0.0923

0.5877

Owl

266.8

135.1876

6x0.2109 7x0.0703 0.2368

0.2096

0.633

16.1

0.0647

0.0661

0.0791

385

0.0202

0.0896

0.5695

Waxwing

266.8

135.2

18x0.1217 1x0.1217 0.2210

0.2094

0.609

15.5

0.0649

0.0664

0.0794

410

0.0197

0.0903

0.5756

Spoonbill

266.8

135.2

22x0.1101 7x0.0612 0.2300

0.2095

0.624

15.9

0.0650

0.0664

0.0795

410

0.0207

0.0891

0.5717

Scaup

266.8

135.2

24x0.1054 7x0.0703 0.2366

0.2094

0.633

16.1

0.0650

0.0664

0.0795

415

0.0212

0.0886

0.5695

Partridge

266.8

135.2

26x0.1013 7x0.0788 0.2437

0.2095

0.642

16.3

0.0651

0.0665

0.0796

415

0.0217

0.0880

0.5673

(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75C at 60 Hz and the following conditions: 32C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90 to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42 northern latitude, sea level elevation, 90 azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.

75

Vous aimerez peut-être aussi