SecuriFire
BX-OI3
Output/input module for
SecuriLine eXtended
Beginning with edition number 20-2100001-01-021
Fig. 2 BX-OI3 interfaces * Input is always implemented as monitored, i.e. termination resis-
tance and alarm resistance are always required.
Inputs (X1)
Terminal Designation Description
1 VEXT+ Monitored ext. Power supply
2 IN3+ Input 3+
3 IN3- Input 3-
4 IN2+ Input 2+
5 IN2- Input 2-
6 IN1+ Input 1+
7 IN1- Input 1-
To be able to connect a special detector (aspirating smoke de- Use for connecting special detectors
tector, line type smoke detector etc.) to the BX-OI3, it must have If the BX-OI3 is used to connect a special detector, a correspond-
at least one potential-free contact each for alarm and fault. Re- ing detector address must be designated for it in SecuriFire Stu-
setting the special detector is done by interrupting the voltage dio. As a result, the BX-OI3 is shown and operated like an auto-
supply via the BX-OI3 relay output. If a suitable reset input is matic detector on the indication and control map of the fire alarm
available on the special detector, it can be actuated directly via control panel (e.g. MG 14/7). Multiple BX-OI3s can be grouped
the relay outputs. The voltage supply of the special detector is into a detection zone in order to simplify operation.
monitored via the opto-isolator input. This also enables connect- During first-time commissioning the fixed predefined parameter
ing devices whose fault contact does not become active when set of the connected special detector must be assigned to the BX-
there is no power supply. OI3 via SecuriFire Studio from a selection list. If your special de-
tector is not listed, please contact the Securiton support centre.
Use for connecting special detectors The maximum number of special detectors per ring is identical to
In principle, any special detector can be connected to the BX- the maximum possible number of BX-OI3s. This depends on the
OI3 provided it has two potential-free contacts for alarm and total number of connected detectors and modules, on the line
fault and that it can be reset by interrupting its voltage supply or length and on the wire cross-section of the concerned ring.
via its own reset input. To ensure reliable operation, each spe- Only four different types of special detectors can be connected per
cial detector has to be checked and then implemented with a ring. If they are already planned in SecuriFire Studio, these four
fixed defined parameter set in SecuriFire Studio. The following special detectors appear in the selection list for this ring.
table shows the checked special detectors to be connected and Because most special detectors have high power requirements, a
the parameter sets of the SecuriFire Studio to be used (Securi- power requirement calculation should always be carried out for the
Fire Studio V1.0). fire alarm control panel. If it is determined that direct power supply
from the power supply unit of the FACP is not possible, then either
Parameter set in Studio Manufacturer designation another FACP or an external power supply unit must be used.
ARDEA IP65 / EX Setronic ARDEA IP65 S-SF If an external power supply unit is used, ensure that country-
and ARDEA EEX S specific standards and directives concerning battery capacity, ap-
ARDEA J ECO 25/50 proval (e.g. VdS) etc. are observed.
ASD 51x Securiton SecuriRAS ASD
51x If power is supplied directly to the special detectors from the power
IR-Flammenmelder PM-5MPX Not released supply unit of the FACP, some special detectors can be operated
IR-Flammenmelder U7698B Not released only a few hundred metres from the fire alarm control panel due to
linienf. Wärmemelder LHD4 Not released their high quiescent current (dependent on the wire cross-section of
MINIBOOM Setronic Miniboomerang 2S the supply lines and the minimum operating voltage).
RAS 51B Securiton RAS 51B and RAS
The BX-OI3 can be mounted up to 30 m from the special
52B
detector and interface of the special detector.
RAS 54 Not released
Securiton RAS 51B/53B Not released
SPB-E Not released
ADW 511 ADW 511 and ADW 511A
UNILASER XL Kidde-Deugra UNILASER &
RAS XL
Planning
Use as O/I module
It is imperative that the technical data are strictly ob-
served.
Inputs 1 and 2 can be operated as monitored or unmonitored
inputs when using termination and alarm resistance in each
case.
The maximum number of BX-OI3s per ring depends on the
total number of connected detectors and modules, on the
line length and on the wire cross-section of the concerned
ring.
BX-OI3
External power GndExt5
External power GndExt5 VExt4
supply unit GndExt4
VExt4
supply unit VExt3
GndExt4 + - GndExt3
VExt3 VExt2
+ - GndExt3 GndExt2
VExt1
VExt2 GndExt1
GndExt2
Use as O/I module
VExt1
GndExt1
Reset - 20
Reset + 19
L1
X1
GND
SHLD
BX-OI3
1
Vext+
ASD 516
ASD 515
IN3+
IN3- Input 3
X2
IN2+
ra 15 180 Input 2 SHLD
Connection examples
IN2-
L1
Input 1
X1
IN1-
GND
a 13 L2
SHLD
BX-OI3
1
Vext+ GND
X3
ra 12 180
IN3+
1
NC GND
Fault relay r 11 Input 3
1
X2
180 IN2+
Input 2
SHLD
180
IN1+ SHLD
IN1-
Input 1
L2
180
GND
X3
not monitored
monitored
1
2 NC GND
Power supply
1
24V 1 COM Relay L1
NO
Polling of
Actuation of
Monitoring of
fire incident controls
potential-free contacts
potential-free contacts
GND
L2
SHLD
B5-PSU B5-PSU
B6-PSU B6-PSU
VExt5
VExt5
T 811 128 en d
External power GndExt5
External power GndExt5
VExt4 VExt4
supply unit GndExt4 supply unit GndExt4
VExt3 VExt3
+ - GndExt3 + - GndExt3
VExt2 VExt2
GndExt2 GndExt2
VExt1 VExt1
GndExt1 GndExt1
24V 1
Power supply 1
2 Power supply 24V
2
r 3
3
Alarm relay ra 4 180 4
a 5 180 5
a 6 6
L1
Fault relay ra
L1
7 180 7
X1
X1
GND
GND
SHLD
SHLD
r BX-OI3
1
BX-OI3 8 Vext+
1
8 180 Vext+
9 IN3+ 9 IN3+
Input 3 a 10 180 IN3- Input 3
10 IN3-
X2
IN2+
X2
11 Input 2 ra IN2-
Input 2 SHLD
IN2- SHLD 12 180
RAS 51B and RAS 52B (RAS 51B parameter set)
12 IN1+
IN1+ SHLD a 13 Input 1 SHLD
Fig. 5 Connection: ADW 511/ADW
13
IN1-
Input 1 r
IN1-
Fault relay 14 L2
14
L2 180
ra 15 GND
X3
X3
16
1
1 NC GND
16 NC GND 17
1
COM Relay L1
1
17 COM Relay L1 18 NO
NO
ADW 511
18
RAS 51B
ADW 511A
GND
L2
SHLD
GND
L2
SHLD
Data Sheet
3/6
B5/B6-DXI2 (X2)
B6-BCU (X12)
4/6
V4
G4
C4
L4
V3
Ring 2
X1
Miniboomerang
BX-OI3 G3
X2
B5-PSU Vext+
IN3+ C3
B6-PSU
L2
1 L1
IN3- Input 3 L3
GND
GND
SHLD
SHLD
V2
BX-IM4
X2
VExt5 IN2+
GndExt5 IN2-
Input 2 SHLD G2
External power
VExt4 IN1+ C2
Input 1 SHLD
Data Sheet
Input 4
Input 3
Input 2
Input 1
G1
X3
Fault relay Alarm relay supply GndExt3
1
NC C NO NC C NO _ + VExt2 NC GND C1
L1
1
8 7 6 5 4 3 2 1 GndExt2 COM Relay L1
IN3+
IN2+
IN1+
IN4-
IN3-
IN2-
IN1-
VExt1 NO
IN4+ 1
GndExt1
X1
180
180
B5-PSU
B6-PSU
180 180 VExt5
Exernal power GndExt5
VExt4
RAS XL (UNILASER XL parameter set)
supply unit
L1
GndExt4
180
180
180
180
180
180
180
180
180
180
180
Read the notice at the end of this section.
X1
GND
SHLD
BX-OI3 VExt3
1
Vext+ + - GndExt3
IN3+ CM NO CM NO CM NO CM NO CM NC NO CM NC NO
Input 3 VExt2
IN3-
X2
IN2+
X3
External PSU Power Power
RAS XL
1
NC GND Network Display Status out in
_ + _ + _ + _ + _ + _ +
1
COM Relay L1 + 0V 24V _
NO
2 x 2 x 0,8
screened
screened
1 x 4 x 0,8
max. 20 m
External Display
GND
L2
max. 1000 m
SHLD
T 811 128 en d
B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
supply unit GndExt4
VExt3
+ - GndExt3
VExt2
RTX GndExt2
+ Power supply 24V VExt1
_
Boomerang or ARDEA
ARDEA J
GndExt1
transmitter TX
Screen NA 180
JP A Fault relay C 180
RRX NC
JP B
+ NA 180
_
TX/RX
Receiver
ARDEA J
Alarm relay C 180
receiver RX
Screen
BOOMERANG
NC
L1
X1
GND
SHLD
INT8BA BX-OI3
1
Read the notice at the end of this section.
Vext+
IN3+
IN3- Input 3
JP A - delay time relay
X2
IN2+
IN2-
Input 2 SHLD
immediately 30 s 60 s 90 s
IN1+ SHLD
IN1-
Input 1
JP B - ialways remove L2
GND
X3
1
NC GND
COM Relay L1
NO
ARDEA and BOOMERANG (ARDEA IP65/Ex parameter set)
GND
L2
SHLD
BX-OI3
Data Sheet
ECO 25/50/80 (ARDEA J parameter set) REK 511 (ASD 51x parameter set)
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
SHLD
GndExt5
GndExt4
GndExt3
GndExt2
GndExt1
VExt5
VExt4
VExt3
VExt2
VExt1
VExt5
VExt4
VExt3
VExt2
VExt1
B5-PSU
B6-PSU
B5-PSU
B6-PSU
X2 X2
BX-OI3
BX-OI3
1 1
SHLD
SHLD
L1
L2
GND
GND
SHLD
SHLD
L1
L2
GND
GND
Relay
Relay
External power
Input 3
Input 2
Input 1
External power
Input 3
Input 2
Input 1
supply unit
supply unit
+ -
+ -
Vext+
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
Vext+
NC
COM
IN3+
IN2+
IN1+
IN3-
IN2-
IN1-
NO
NC
1 1
1 1 X1 X3
X1 X3
MEA 720
(max. 5 mA)
RNA
St
RA- 180
Al
RA+ 180
180
SSD MRP
NC C NO
RE- 180
515-xS 915
180
RE+ 180
Al
LOOP
+
5
LOOP+ 180
+ G N D (NC) C (NO)
St-
0V
180
REL
ECO 0V
St
Al+
Base contact
3
GND 3
+24V
_
2
OUT
IN
Fig. 10 Connection: ECO 25/50/80
+
1
+
REK 511
Fig. 11 Connection: REK 511
Technical data
Function Output/input module
Operating voltage 12 to 30 VDC
Power consumption (module’s power consumption only) 0.55 mA
Signal transmission Serial data transmission, 2-line technology
Protection type 66 with map case IP
Ambient temperature -20 to +60 °C
Connection Screw terminals max. 1.5 mm2
VdS approval G210133
EU certificate of conformity (EN 54-17/18) 0786-CPD-21011
Dimensions (H x W x D) 67 x 67 x 20 mm
1
Reference document BX-OI3, V.1.1