Data Sheet

__________________________________________________________________________________________________________________

SecuriFire
BX-OI3
Output/input module for
SecuriLine eXtended
Beginning with edition number 20-2100001-01-021

The BX-OI3 output/input module can be used as either O/I


module or as detector/detection zone for connecting special de-
tectors.

It meets the SecuiLine eXtended specification for operation on


the ring circuit of the SecuriFire fire detection system. Fig. 1 BX-OI3

Description SecuriLine eXtended (X2)


The BX-OI3 can be connected to the SecuriLine eXtended ring Terminal Designation Description
circuit of the SecuriFire fire detection system. 1 L1 Data A
The BX-OI3 can be used as either an O/I module (1 relay out- 2 GND GND A
put, 2 monitored inputs, 1 opto-isolator) or as detector/detection 3 GND GND B
zone for connecting special detectors. 4 L2- Data B
Input 1 can be programmed as checkback. 5 SHLD Screen
Addressing and parameter assignment for the BX-OI3 is per- 6 SHLD Screen
formed with PC software via the fire alarm control panel.
The BX-OI3 includes a short-circuit isolator. In the event of wire Relay output (X3)
breakage or a short-circuit, this functionality ensures that the Terminal Designation Description
fault is localised and at the same time maintains the full oper- 1 NC Data A
ability of the ring circuit. 2 COM GND A
3 NO GND B
Interfaces
Areas of application
Use as O/I module
1x relay output for actuating fire incident control (e.g. lift control
system)
2x monitored inputs*) for polling potential-free contacts (e.g. sprin-
klers)
1 opto-isolator input for polling external voltages (e.g. 5 V, 12 V)

Use for connecting special detectors


1x relay output for resetting the special detector
2x monitored inputs for polling the alarm and fault contact
1x opto-isolator input for monitoring the voltage supply of the spe-
cial detector

Fig. 2 BX-OI3 interfaces * Input is always implemented as monitored, i.e. termination resis-
tance and alarm resistance are always required.

Inputs (X1)
Terminal Designation Description
1 VEXT+ Monitored ext. Power supply
2 IN3+ Input 3+
3 IN3- Input 3-
4 IN2+ Input 2+
5 IN2- Input 2-
6 IN1+ Input 1+
7 IN1- Input 1-

Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 811 128 en d 1/6


Data Sheet

To be able to connect a special detector (aspirating smoke de- Use for connecting special detectors
tector, line type smoke detector etc.) to the BX-OI3, it must have If the BX-OI3 is used to connect a special detector, a correspond-
at least one potential-free contact each for alarm and fault. Re- ing detector address must be designated for it in SecuriFire Stu-
setting the special detector is done by interrupting the voltage dio. As a result, the BX-OI3 is shown and operated like an auto-
supply via the BX-OI3 relay output. If a suitable reset input is matic detector on the indication and control map of the fire alarm
available on the special detector, it can be actuated directly via control panel (e.g. MG 14/7). Multiple BX-OI3s can be grouped
the relay outputs. The voltage supply of the special detector is into a detection zone in order to simplify operation.
monitored via the opto-isolator input. This also enables connect- During first-time commissioning the fixed predefined parameter
ing devices whose fault contact does not become active when set of the connected special detector must be assigned to the BX-
there is no power supply. OI3 via SecuriFire Studio from a selection list. If your special de-
tector is not listed, please contact the Securiton support centre.
Use for connecting special detectors The maximum number of special detectors per ring is identical to
In principle, any special detector can be connected to the BX- the maximum possible number of BX-OI3s. This depends on the
OI3 provided it has two potential-free contacts for alarm and total number of connected detectors and modules, on the line
fault and that it can be reset by interrupting its voltage supply or length and on the wire cross-section of the concerned ring.
via its own reset input. To ensure reliable operation, each spe- Only four different types of special detectors can be connected per
cial detector has to be checked and then implemented with a ring. If they are already planned in SecuriFire Studio, these four
fixed defined parameter set in SecuriFire Studio. The following special detectors appear in the selection list for this ring.
table shows the checked special detectors to be connected and Because most special detectors have high power requirements, a
the parameter sets of the SecuriFire Studio to be used (Securi- power requirement calculation should always be carried out for the
Fire Studio V1.0). fire alarm control panel. If it is determined that direct power supply
from the power supply unit of the FACP is not possible, then either
Parameter set in Studio Manufacturer designation another FACP or an external power supply unit must be used.
ARDEA IP65 / EX Setronic ARDEA IP65 S-SF If an external power supply unit is used, ensure that country-
and ARDEA EEX S specific standards and directives concerning battery capacity, ap-
ARDEA J ECO 25/50 proval (e.g. VdS) etc. are observed.
ASD 51x Securiton SecuriRAS ASD
51x If power is supplied directly to the special detectors from the power
IR-Flammenmelder PM-5MPX Not released supply unit of the FACP, some special detectors can be operated
IR-Flammenmelder U7698B Not released only a few hundred metres from the fire alarm control panel due to
linienf. Wärmemelder LHD4 Not released their high quiescent current (dependent on the wire cross-section of
MINIBOOM Setronic Miniboomerang 2S the supply lines and the minimum operating voltage).
RAS 51B Securiton RAS 51B and RAS
The BX-OI3 can be mounted up to 30 m from the special
52B
detector and interface of the special detector.
RAS 54 Not released
Securiton RAS 51B/53B Not released
SPB-E Not released
ADW 511 ADW 511 and ADW 511A
UNILASER XL Kidde-Deugra UNILASER &
RAS XL

In preparation, not yet released:


Line type heat detector: MHD535, TSC515
Line type smoke detector: BSD535, ILIA, ECO100

Planning
Use as O/I module
It is imperative that the technical data are strictly ob-
served.
Inputs 1 and 2 can be operated as monitored or unmonitored
inputs when using termination and alarm resistance in each
case.
The maximum number of BX-OI3s per ring depends on the
total number of connected detectors and modules, on the
line length and on the wire cross-section of the concerned
ring.

2/6 T 811 128 en d BX-OI3


B5-PSU B5-PSU
B6-PSU B6-PSU
VExt5 VExt5

BX-OI3
External power GndExt5
External power GndExt5 VExt4
supply unit GndExt4
VExt4
supply unit VExt3
GndExt4 + - GndExt3
VExt3 VExt2
+ - GndExt3 GndExt2
VExt1
VExt2 GndExt1
GndExt2
Use as O/I module

VExt1
GndExt1
Reset - 20
Reset + 19
L1

X1
GND

SHLD

BX-OI3

1
Vext+

ASD 516
ASD 515
IN3+
IN3- Input 3
X2

IN2+
ra 15 180 Input 2 SHLD
Connection examples

IN2-

ASD 51x (ASD 51x parameter set)


Alarm relay r 14 180 IN1+ SHLD

L1
Input 1

X1
IN1-

GND
a 13 L2

SHLD
BX-OI3

1
Vext+ GND
X3

ra 12 180
IN3+
1

NC GND
Fault relay r 11 Input 3
1

IN3- COM Relay L1


a 10 NO

X2
180 IN2+
Input 2

Fig. 3 Use as O/I module


IN2- SHLD

Fig. 4 ASD 51x connection


L2
GND

SHLD

180

IN1+ SHLD
IN1-
Input 1
L2
180

GND

X3
not monitored
monitored

1
2 NC GND
Power supply

1
24V 1 COM Relay L1
NO
Polling of
Actuation of

Monitoring of
fire incident controls

potential-free contacts
potential-free contacts

GND
L2
SHLD

B5-PSU B5-PSU
B6-PSU B6-PSU
VExt5
VExt5

T 811 128 en d
External power GndExt5
External power GndExt5
VExt4 VExt4
supply unit GndExt4 supply unit GndExt4
VExt3 VExt3
+ - GndExt3 + - GndExt3
VExt2 VExt2
GndExt2 GndExt2
VExt1 VExt1
GndExt1 GndExt1
24V 1
Power supply 1
2 Power supply 24V
2
r 3
3
Alarm relay ra 4 180 4
a 5 180 5
a 6 6
L1

Fault relay ra
L1

7 180 7
X1

X1
GND

GND
SHLD

Read the notice at the end of this section.


Read the notice at the end of this section.

SHLD

r BX-OI3
1

BX-OI3 8 Vext+

1
8 180 Vext+
9 IN3+ 9 IN3+
Input 3 a 10 180 IN3- Input 3
10 IN3-
X2

IN2+
X2

IN2+ Alarm relay r 11


ADW 511/ADW 511A (ADW 511 parameter set)

11 Input 2 ra IN2-
Input 2 SHLD
IN2- SHLD 12 180
RAS 51B and RAS 52B (RAS 51B parameter set)

12 IN1+
IN1+ SHLD a 13 Input 1 SHLD
Fig. 5 Connection: ADW 511/ADW

13
IN1-
Input 1 r
IN1-
Fault relay 14 L2
14
L2 180
ra 15 GND
X3

Fig. 6 Connection: RAS 51B and RAS 52B


15 GND 180

X3
16
1

1 NC GND
16 NC GND 17
1

COM Relay L1
1

17 COM Relay L1 18 NO
NO
ADW 511

18

RAS 51B
ADW 511A
GND
L2
SHLD

GND
L2
SHLD
Data Sheet

3/6
B5/B6-DXI2 (X2)
B6-BCU (X12)

4/6
V4
G4
C4
L4
V3

Ring 2

X1

Miniboomerang
BX-OI3 G3

X2
B5-PSU Vext+
IN3+ C3
B6-PSU

L2
1 L1
IN3- Input 3 L3

GND
GND

SHLD
SHLD
V2

BX-IM4
X2
VExt5 IN2+
GndExt5 IN2-
Input 2 SHLD G2
External power
VExt4 IN1+ C2
Input 1 SHLD
Data Sheet

supply unit GndExt4 IN1- L2


L2 V1
Ring 1
Power VExt3
+ - GND

Input 4
Input 3
Input 2
Input 1
G1

X3
Fault relay Alarm relay supply GndExt3

1
NC C NO NC C NO _ + VExt2 NC GND C1
L1

1
8 7 6 5 4 3 2 1 GndExt2 COM Relay L1

IN3+
IN2+
IN1+

IN4-
IN3-
IN2-
IN1-
VExt1 NO

IN4+ 1
GndExt1

X1

180
180
B5-PSU
B6-PSU
180 180 VExt5
Exernal power GndExt5
VExt4
RAS XL (UNILASER XL parameter set)

supply unit

L1
GndExt4

180
180
180
180
180
180
180
180
180
180
180
Read the notice at the end of this section.

X1
GND

SHLD
BX-OI3 VExt3

1
Vext+ + - GndExt3
IN3+ CM NO CM NO CM NO CM NO CM NC NO CM NC NO
Input 3 VExt2
IN3-

Fig. 7 Connection: RAS XL


GndExt2

X2
IN2+

Please read the notice at the end of this section.


Input 2 VExt1
IN2- SHLD

MINIBOOMERANG (MINIBOOM parameter set)


Pre Pre Al 1 Al 2 Stö Isolate GndExt1
IN1+ SHLD Al 1 Al 2 Trouble
IN1-
Input 1

Fig. 8 Connection: MINIBOOMERANG


L2
GND

X3
External PSU Power Power

RAS XL

1
NC GND Network Display Status out in
_ + _ + _ + _ + _ + _ +

1
COM Relay L1 + 0V 24V _
NO

2 x 2 x 0,8

screened
screened

1 x 4 x 0,8

max. 20 m
External Display

GND
L2
max. 1000 m

SHLD

T 811 128 en d
B5-PSU
B6-PSU
VExt5
External power GndExt5
VExt4
supply unit GndExt4
VExt3
+ - GndExt3
VExt2
RTX GndExt2
+ Power supply 24V VExt1
_

Boomerang or ARDEA
ARDEA J
GndExt1

transmitter TX
Screen NA 180
JP A Fault relay C 180

RRX NC
JP B
+ NA 180
_

TX/RX
Receiver
ARDEA J
Alarm relay C 180

receiver RX
Screen

BOOMERANG
NC
L1

X1
GND

SHLD

INT8BA BX-OI3
1
Read the notice at the end of this section.

Vext+
IN3+
IN3- Input 3
JP A - delay time relay
X2

IN2+
IN2-
Input 2 SHLD
immediately 30 s 60 s 90 s
IN1+ SHLD
IN1-
Input 1
JP B - ialways remove L2
GND
X3
1

NC GND

Fig. 9 Connection: ARDEA and BOOMERANG


1

COM Relay L1
NO
ARDEA and BOOMERANG (ARDEA IP65/Ex parameter set)

GND
L2
SHLD

BX-OI3
Data Sheet

ECO 25/50/80 (ARDEA J parameter set) REK 511 (ASD 51x parameter set)

GND GND GND GND


L1 L2 L1 L2
SHLD SHLD SHLD

GndExt5

GndExt4

GndExt3

GndExt2

GndExt1
SHLD
GndExt5

GndExt4

GndExt3

GndExt2

GndExt1

VExt5

VExt4

VExt3

VExt2

VExt1
VExt5

VExt4

VExt3

VExt2

VExt1

B5-PSU
B6-PSU
B5-PSU
B6-PSU

X2 X2

BX-OI3
BX-OI3
1 1

SHLD
SHLD

L1
L2
GND
GND
SHLD
SHLD

L1
L2
GND
GND

Relay
Relay

External power

Input 3
Input 2
Input 1
External power

Input 3
Input 2
Input 1

supply unit
supply unit

+ -
+ -

Vext+

COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
Vext+

NC
COM
IN3+

IN2+

IN1+
IN3-

IN2-

IN1-

NO
NC
1 1
1 1 X1 X3
X1 X3

MEA 720
(max. 5 mA)

RNA
St
RA- 180
Al
RA+ 180
180
SSD MRP

NC C NO
RE- 180
515-xS 915

180
RE+ 180

Al
LOOP

+
5
LOOP+ 180

+ G N D (NC) C (NO)
St-
0V

180
REL
ECO 0V

St
Al+

Base contact
3

GND 3
+24V

_
2

OUT

IN
Fig. 10 Connection: ECO 25/50/80
+
1

+
REK 511
Fig. 11 Connection: REK 511

The voltage supply of the special detector is monitored


by means of an opto-isolator on the BX-OI3 out-
put/input module. This also enables connecting de-
vices whose fault contact does not become active
when there is no power supply. When connecting the
voltage supply, ensure that it is conveyed from the
power supply unit via the reset contact of the BX-OI3
directly to the special detector and then from this back
to the voltage monitor on the BX-OI3. Only in this way
can it be ensured that also the voltage supply between
BX-OI3 and special detector is monitored.

Article numbers / spare parts


Short designation Art. number CH Art. number
BX-OI3 Output/input module 115.249 774 20-2100001-01-03
GEH MOD IP66 IP66 map case for BX-OI3 403.239 917 FG020234
MM SM M20 M20 step nipple 428.242 578 MM000181
MM ANB M16 M16 mounting screw union -- MM000185
MM GM M16 M16 counter-nut -- MM000186

BX-OI3 T 811 128 en d 5/6


Data Sheet

Technical data
Function Output/input module
Operating voltage 12 to 30 VDC
Power consumption (module’s power consumption only) 0.55 mA
Signal transmission Serial data transmission, 2-line technology
Protection type 66 with map case IP
Ambient temperature -20 to +60 °C
Connection Screw terminals max. 1.5 mm2
VdS approval G210133
EU certificate of conformity (EN 54-17/18) 0786-CPD-21011
Dimensions (H x W x D) 67 x 67 x 20 mm

Relay output 1 Pc.


Relay Bistable, one coil
Type of contact Change-over contact
Switching voltage 230 V
Switching current 0.1-2000 mA
Breaking capacity 60 (0.25 A at 230 V) W
Switching frequency max. 3.125 Hz
(a relay can change its state every 160 ms per ring, provided no other command has to be performed)
Connection Screw terminals max. 2.5 mm2

Monitored inputs 2 Pc.


Connection IN1- and IN1+, IN2- and IN2+, potential-free contacts
Polling current 10 mA
Polling voltage 3-6 V
Termination resistance 180 Ω
Alarm resistance 180 Ω
Line resistance Max. 30 Ω
Polling impulse 100 μs
Polling cycle 66 ms
Input filter 10 μs
Periodic duration >8 s
(switching states which last longer than 330 ms and whose repetition time is greater than 8 s are recorded)
Line length Max. 30 m
Connection Screw terminals max. 1.5 mm2

Opto-isolator input 1 Pc.


Connection IN3- and IN3+, potential-dependent signals
Voltage range 0 to 30 V
Input resistance 4,900 Ω
Input current Max. 6 mA
Galvanic separation By opto-isolator
Line length Max. 1,000 m
Connection Screw terminals max. 1.5 mm2

Input voltage monitoring 1 Pc.


Connection IN3- and VEXT
Voltage range 0 to 30 V
Input resistance 10 kΩ
Monitoring current Approx. 1.9 at 24 V mA
Galvanic separation By opto-isolator
Line length Max. 1,000 m
Connection Screw terminals max. 1.5 mm2

Changes to Index d: new article number

1
Reference document BX-OI3, V.1.1

6/6 T 811 128 en d, 06.05.2014 Rd BX-OI3


First edition: 26.11.2010 Bed/ksa
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton