Académique Documents
Professionnel Documents
Culture Documents
INTERNATIONALE IEC
71-1
INTERNATIONAL
Septieme edition
1993-12
Coordination de l ' i s o l e m e n t
Partie 1 :
D e f i n i t i o n s , principes et regles
I n s u l a t i o n co-ordination
Part 1 :
N u rn e r o d e reference
Reference n u m b e r
CEI/IEC 7 1 - 1 : 1993
V a l i d i t e de la presente p u b l i c a t i o n V a l i d i t y of t h i s p u b l i c a t i o n
Le contenu technique des publications de la CEI est cons T he technical content of IEC publications is kept under
tamment revu par la CEI afin qu'il reflete l'etat actuel de constant review by the IEC , thus ensuring that the content
Des renseignements relatifs a la date de reconfirmation de Information relating to the date of the reconfirmation of the
la publication sont disponibles aupres du Bureau Central de publication is available from th e IEC Central Off ice.
laCEI.
Les renseignements relatifs a ces revisions, a l'etablis Information on the revrsron w ork, the issue of revised
sement des editions revisees et aux amendements peuvent editions and amendments may be obtained from IEC
etre obtenus aupres des Comltes nationaux de la CEI et N ational Committees and from the following IEC
• B u l l e t i n de la CEI • IEC B u l l e t i n
Publie annuellement et mis a jour regulierement Publis h ed y early w ith re g ular updates
Terminologie Terminology
En ce qui concerne la terminologie generale, le lecteur se F or general terminolo g y , readers are referred to I E C 50:
reportera a la CEI 50: Vocabulaire Electrotechnique Inter International Electrotechnical Vocabulary ( I E V ) , w hich is
national (VEI), qui se presents sous forme de chapitres issued in the form of separate chapters each dealing
separes traitant chacun d'un sujet definl. Des details w ith a specific field. F ull details of the IEV will be
complets sur le VEI peuvent etre obtenus sur demande. supplied on request. S ee also the IEC M ultilingual
Les termes et definitions figurant dans la presente publi Th e terms and definitions contained in the present publi
cation ont ete soit tires du VEI, soil specinquement cation h ave either been taken from the IEV or have been
approuves aux fins de cette publication. specifically approved for the purpose of this publication.
Pour les symboles graphiques, les symboles litteraux et les F or graphical symbols, and letter symbols and signs
signes d'usage general approuvss par la CEI, le lecteur approved by the IEC for general use, readers are referred to
consultera: publications:
- la CEI 27: Symboles llttereux a utiliser en I E C 27: Letter symbols to be used in electrical
electro-technique; technology;
la CEI 417: Symboles graphiques utilisables IEC 417: Graphical symbols for use on
sur le materiel. Index, re/eve et compilation des equipment. Index, survey and compilation of the
la CEI 6 1 7 : Symboles graphiques pour schemas; IEC 61 7: Graphical symbols for diagrams;
la CEI 878: Symboles graphiques pour I E C 878: Graphical symbols for electromedical
Les symboles et signes contenus dans la presente publi Th e symbols and signs contained in the present publication
cation ont ete soil tires de la CEI 27, de la CEI 417, de la h ave either been taken from IEC 27, IEC 417, IEC 61 7
CEI 6 1 7 et/ou de la CEI 878, soil specitiquement approuves and/or IEC 878, or have been specifically approved for the
L'attention du lecteur est attlree sur Jes lisles figurant a la fin T he attention of readers is drawn to the end pages of this
de cette publication, qui snurnerent les publications de la publication w hich list the IEC publications issued by the
CEI preparees par le comite d'etudes qui a e tabli la technical committee wh ich has prepared the present
INTERNATIONALE I E C
71-1
INTERNATIONAL
sepneme edition
1993-12
Coordination de l ' i s o l e m e n t
Partie 1 :
D e f i n i t i o n s , principes et reqtes
I n s u l a t i o n co-ordination
Part 1 :
Aucune partie de oette publication ne peut etre reproduite ni No part of this publication may be reproduoed or utilized in
utilis0e sous quelque forme que ce soit et par aucun pre any form or by any means, electronic or mechanical,
cede, Etlectronique ou IT'lecanique, y oompris la photocopie et including photooopying and microfilm, without permission
les microfilms, sans l"accord ecrit de l'editeur. in writing from the publisher.
CONTENTS
Page
FOREWORD.............................................................................................................................. 7
Clause
1 Scope................................................................................................................................. 9
2 Normative references 9
3 Definitions.......................................................................................................................... 11
3.2 External i n s u l a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Non-self-restoring i n s u l a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.7 Insulation c o n f i g u r a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clause Page
4 P r o c e d u r e for i n s u l a t i o n c o - o r d i n a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1 G e n e r a l o u t l i n e of t h e p r o c e d u r e 21
5.1 General r e q u i r e m e n t s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 39
Tables 41
Annex A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
71-1 © IEC:1993 - 7 -
INTERNATIONAL ELECTROTECHNICAL C O M M I S S I O N
INSULATION CO-ORDINATION
Part 1 : D e f i n i t i o n s , p r i n c i p l e s and r u l e s
FOREWORD
comprising all national electrotechnical committees ( I E C National Committees). The object of the IEC is to
promote international cooperation on all questions concerning standardization in the electrical and
electronic fields. To this end and in addition to other activities, the I E C publishes International Standards.
Their preparation is entrusted to technical committees; any IEC National Committee interested in
the subject dealt with may participate in this preparatory work. International, governmental and
non-governmental organizations liaising with the IEC also participate in this preparation. The IEC
collaborates closely with the International Organization for Standardization (ISO) in accordance with
2) The formal decisions or agreements of the I E C on technical matters, prepared by technical committees on
which all the National Committees having a special interest therein are represented, express, as nearly as
3) They have the form of recommendations for international use p u b l i s h e d in the form of standards, technical
reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
International Standard IEC 71-1 has been prepared by IEC technical committee 28:
I n s u l a t i o n co-ordination.
only with insulation co-ordination between phase and earth, and the first part of the
first edition - published in 1982 - of IEC Publication 71-3 which dealt with insulation
co-ordination between p h a s e s .
c o - o r d i n a t i o n of electrical e q u i p m e n t .
28(C0)58 28(C0)60
Full information on the voting for the approval of t h i s standard can be found in the report
A n n e x A is for i n f o r m a t i o n o n l y .
71-1 © IEC:1993 - 9 -
INSULATION CO-ORDINATION
Part 1 : D e f i n i t i o n s , p r i n c i p l e s a n d r u l e s
1 Scope
This part of International Standard IEC 71 applies to three-phase a.c. systems having a
highest voltage for equipment above 1 kV. It specifies the procedure for the selection of
the standard withstand voltages for the phase-to-earth, phase-to-phase and longitudinal
the standardized values from which the standard withstand voltages s h a l l be selected.
This part recommends that the selected withstand voltages s h o u l d be associated with the
highest voltage for equipment. This association is for insulation co-ordination purposes
only. The requirements for h u m a n safety are not covered by this Standard.
Although the principles of t h i s part also apply to transmission line i n s u l a t i o n , the values of
the withstand voltages may be different from the standard withstand voltages.
The apparatus committees are responsible for specifying the withstand voltages and the
test procedures suitable for the relevant equipment taking into consideration the
recommendations of t h i s Standard.
NOTE - In I E C 7 1 - 2 Application G u i d e , ( u n d e r revision), all rules for insulation co-ordination given in this
Standard are justified in detail, in particular the association of the standard withstand voltages with the
highest voltage for equipment. When more than one set of standard withstand voltages is associated with
the same highest voltage for e q u i p m e n t , guidance is provided for the selection of the most suitable set.
2 Normative references
The following normat i ve documents contain provrsions which, through refe re n c e in this
indicated were valid. All normative documents are subject to revision, and p a rt i e s to
I EC 60-1 : 1989, High-voltage test techniques - Part 1: General definitions and test
requirements
71-1 © IEC:1993 - 11 -
3 Definitions
relation to the voltages which can appear on the system for which the equipment is
intended and taking into account the service environment and the characteristics of the
NOTE - By "dielectric strength" of the e q u i p m e n t , is meant here its rated or its standard i n s u l a t i o n level
3.2 external Insulation: The distances in atmospheric air, and the surfaces in contact
with atmospheric air of solid insulation of the equipment which are subject to dielectric
stresses and to the effects of atmospheric and other external c o n d i t i o n s , such as pollution,
3.3 Internal Insulation: The internal solid, liquid, or g a s e o u s parts of the insulation of
equipment which are protected from the effects of atmospheric and other external
c o n d i t i o n s . [ I E V 604-03-03)
NOTE - The definitions of 3.4 and 3.5 apply only when the discharge is caused by the application of a
test voltage during a dielectric test. However, discharges occurring in service may cause a self-restoring
neutral voltage of t h e s y s t e m ;
b) neutral terminal, representing, or connected to, the neutral point of the system
( n e u t r a l t e r m i n a l of t r a n s f o r m e r s , e t c . ) ;
base of d i s c o n n e c t o r s , s t r u c t u r e s of towers, g r o u n d p l a n e , e t c . ) .
and conducting) which influence its die l ectric behaviour. T he following insulation
c o n f i g u r a t i o n s are i d e n t i f i e d :
- three-phase: having three p hase terminals, one neutral terminal and one e a rt h
terminal.
is disregarded. In p a rti cul a r cases. the neutral and the e a rt h terminals are also
disregarded.
- longitudinal, having two phase terminals and one earth terminal. The phase
two independently energized parts (open switching devices). The four te r min als
under normal operating conditions at any time and at any point in the system.
[IEV 601-01-23]
3.10 highest voltage for equi pment (Um): The highest r.m.s. value of phase-to-phase
voltage for which the equipment is designed in respect of its insulation as w e l l as other
[IEV 6 0 4 - 0 3 - 0 1 ]
3.11 isolated neutral system: A system where the neutral point is not intentionally
purposes. [ I E V 6 0 1 - 0 2 - 2 4 ]
3.12 solidly earthed neutral system: A system whose neutral point(s) is(are) earthed
directly. [ I E V 6 0 1 - 0 2 - 2 5 )
3.13 impedance earthed (neutral) system: A system whose neutral point(s) is(are)
3.14 resonant earthed ( n e utral) s y s t e m : A system in which one or more neutral points
capacitive c o m p o n e n t of a s i n g l e - p h a s e - t o - e a rt h f a u l t c u r r e n t . ( I E V 6 0 1 - 0 2 - 2 7 ]
NOTE - With resonant earthing of a system, the residual current in the fault is limited to such an extent
3.15 e a rt h fault factor: At a given location of a three-phase system. and for a given
system configuration, the ratio of the highest r.m.s. phase-to-earth power frequency
voltage on a healthy phase during a fault to e a rt h affecting one or more phases at any
point on the system to the r.m.s. p h a s e - t o - e a r t h power frequency voltage which would be
3.16 overvoltage: Any voltage between one phase conductor and earth or between
voltage for e q u i p m e n t . [ I E V 6 0 4 - 0 3 - 0 9 , m o d i f i e d ]
71-1 © IEC:1993 - 1 5 -
NOTES
1 Unless otherwise clearly indicated, such as for s u r g e arresters, overvoltage values expressed in p.u.
2 For any insulation configuration, an overvoltage is any voltage across its terminals higher than the
peak of the power-frequency voltage existing between them when all phase terminals of the equipment are
According to their shape and duration, voltages and overvoltages are divided in the
insulation configuration.
[ I E V 6 0 4 - 0 3 - 1 2 , modified]
NOTE - The overvoltage may be undamped or weakly damped. In some cases its frequency may be
NOTE - Transient overvoltages may be immediately followed by temporary overvoltages. In such cases
to peak O, 1 µs < T ::; 20 µs, and tail duration T < 300 µs.
1 2
NOTE - More detailed definitions of these standard voltage shapes are given in IEC 60-1 (see also
table 1 ) .
71-1 © IEC:1993 - 1 7 -
peak and half value should not be less than those of the positive impulse. Both
impulses should reach their peak value at the same instant. The peak value of the
to various o r i g i n s . They consist of voltages with t h e standard shape of the c l a s s , and may
NOTE - This definition also applies to the continuous power frequency voltage representing the effect of
3.20 overvoltage limiting device: Device which limits the peak values of the
voltage value on the terminals of a protective device subjected to lightning (or switching)
reduce to an economically and operationally acceptable level the probability that the
resulting voltage stresses imposed on the equipment will cause damage to equipment
etc.) of the i n s u l a t i o n c o n f i g u r a t i o n .
3.23 withstand voltage: The value of the test voltage to be applied under specified
Pw=100%;
is Pw = 90 %.
NOTE - In this Standard, for non-self-restoring insulation are specified conventional assumed withstand
the p e rf o r m a n c e c r i t e r i o n .
71-1 © I E C : 1 9 9 3 - 1 9 -
3.25 co-ordination factor (Kc): The factor by which the value of the representative
voltage.
- temperature t = 20 °C
0
3
- absolute humidity hao = 1 1 g/m
3.27 required withstand voltage (Urw>= The test voltage that the insulation must
withstand in a standard withstand test to ensure that the insulation will meet the
conditions and for the whole service duration. The required withstand voltage has the
shape of the co-ordination withstand voltage, and is specified with reference to all the
withstand voltage to account for the difference between the average atmospheric
external insulation o n l y .
3.29 safety factor (K The overall factor to be applied to the co-ordination withstand
5):
voltage, after the application of the atmospheric correction factor (if required), to obtain
the required withstand voltage, accounting for all other differences between the conditions
3.30 standard withstand voltage (Uw): The standard value of the test voltage applied in
a standard withstand test. It is a rated value of the insulation and proves that the
the case where the standard withstand voltage is selected of different shape, so as to
it.
3.32 rated insulation l e v e l : A set of standard withstand voltages which characterize the
of w h i c h are a s s o c i a t e d to Um as r e c o m m e n d e d in t a b l e s 2 and 3 .
conditions to prove that the insulation complies with a standard withstand voltage. This
standard c o v e r s :
- s h o rt - d u r a t i o n power-frequency t e s t s ;
- c o m b i n e d voltage t e s t s .
71-1 © IEC:1993 -21 -
NOTES
More detailed information on the standard withstand voltage tests are given in IEC 60-1 (see also
2 The very-fast i m p u l s e standard withstand voltage tests should be specified by the relevant apparatus
committees, if required.
The procedure for insulation co-ordination consists of the selection of a set of standard
this standard. This procedure is outlined in figure 1 and its steps are described in 4.2
to 4 . 5 . The optimization of the procedure may require reconsideration of some input data
The standard withstand voltages s h a l l be selected from the lists of 4 . 6 and 4 . 7 . The set of
selected standard voltages constitutes a rated insulation level. If the standard withstand
voltages are also associated with the same Um according to 4.9, this set constitutes a
The voltages and the overvoltages that stress the insulation shall be determined in
amplitude, shape and duration by means of a system a n a l y s i s which includes the selection
For each class of overvoltage, this analysis shall then determine a representative
an assumed maximum, or
NOTE 1 - I n the last case additional characteristics of the overvoltage s h a p e s may have to be considered.
with an r.m.s. value equal to the assumed maximum of the te mporary overvoltages
d i v i d e d by ff.
- for the fast-front o v e r v o l t a g e : a standard lightning impulse with peak value equal
impulse with peak value equal to the peak value of the assumed maximum of the
NOTE 2 - An useful characteristic is the actual ratio, o:, in service of the peak value of the negative
component, u-. to the peak value, U+ + U-, of the assumed maximum phase-to-phase overvoltage:
voltage, each with peak value equal to the two relevant assumed maximum peak
values, and with the instant of impulse peak coinciding with the peak of the
power-frequency of opposite p o l a r i t y .
lowest values of the withstand voltages of the i n s u l a t i o n meeting the performance criterion
The co-ordination withstand voltages of the insulation have the shape of the
representative overvoltages of the relevant class and their values are obtained by
value of the co-ordination factor depends on the accuracy of the evaluation of the
the r e p r e s e n t a t i v e o v e r v o l t a g e s .
compensate for t h e differences between the actual in-service conditions of the insulation
The factors to be a p p l i e d s h a l l c o m p e n s a t e f o r :
- the d i f f e r e n c e s in t h e e q u i p m e n t a s s e m b l y ;
- the d i s p e r s i o n in t h e product q u a l i t y ;
- t h e q u a l i t y of i n s t a l l a t i o n ;
- other unknown i n f l u e n c e s .
71-1 © IEC:1993 -25-
If, however. these factors cannot be evaluated individually. an overall safety factor.
For external insulation only, an additional factor shall be applied to account for the
differences between the standard reference atmospheric conditions and those expected in
service.
The selection of the rated insulation level consists of the selection of the most economical
set of standard withstand voltages ( Uw) of the insulation sufficient to prove that all the
The continuous power-frequency withstand voltage of the insulation, that is its highest
voltage for equipment, is then chosen as the next standard value of Um equal to or higher
Standardization of tests, as well as the selection of the relevant test voltages, to prove the
compliance with Um, are p e rf o r m e d by the relevant apparatus committees (e.g. pollution
The withstand voltages to prove that the required temporary, slow-front and fast-front
insulation, may be selected with the same shape as the required withstand voltage, or
with a different shape, exploiting, for this last selection, the intrinsic characteristics of the
insulation.
The value of the withstand voltage is then selected in the list of the standard withstand
voltages reported in 4.6 and 4.7, as the next value equal to or higher than:
- the required withstand voltage multiplied by the relevant test conversion factor in
NOTE - This may allow the adoption of a single standard withstand voltage to prove compliance with
more than one required withstand voltage, thus giving the possibility of reducing the number of standard
The selection of the standard withstand voltage to prove the compliance with the very-fast
committees.
10 20 28 38 50 70 95 140
The standard highest voltages for equipment are divided in to two ranges:
Range I: Above 1 kV to 245 kV included. This range covers both transmission and
taken into account in the selection of the rated insulation level of the
equipment.
Range I I : Above 245 kV. This range covers mainly transmission systems.
The association of standard withstand voltages with the highest voltage for equipment has
been standardized to benefit from the experience gained from the operation of systems
The standard withstand voltages are associated with the highest voltage for equipment
according to table 2 for range I and table 3 for range I I . The associations obtained by
connecting standard withstand voltages of all columns without crossing horizontal marked
NOTES
In some countries other values of Um and of rated withstand voltages are still in use for range I.
Table A.1 of annex A r e p o rt s these values as well as the relevant associations, which, however, do not
2 If, for the switching impulse withstand voltage test, the apparatus committees specify a positive
component lower than the negative, the required withstand voltage of the external insulation is not proven
longitudinal insulation:
and lightning impulse phase-to-phase withstand voltages are equal to the relevant
phase-to-earth withstand voltages (table 2). The values in brackets, however, may be
insufficient to prove that the required withstand voltages are met and additional
For phase-to-phase insulation, range II, the standard lightning impulse withstand
and lightning impulse withstand voltages are equal to the relevant phase-to-earth
- For longitudinal insulation, range II, the standard switching impulse component of
the combined withstand voltage is given in table 3, while the peak value of the
phase-to-earth withstand voltage (table 3 ) , while the peak value of the power-frequency
More than one preferred association is foreseen for most of the highest voltages for
patterns.
For the preferred associations, only two standard withstand voltages are sufficient to
- For e q u i p m e n t in range I:
recommendations of 4.2 to 4.8 shall be followed in every case. The resulting set of
standard withstand voltages shall be termed, therefore, rated insulation level. Part icu l ar
examples are:
- For external insulation, for the higher values of Um in range I, it may be more
- For internal insulation in range II, high temporary overvoltages may require the
that the actual withstand voltage of the insulation is not lower than the corresponding
specified withstand voltage. The voltages applied in withstand voltage tests are standard
wet tests p e rf o r m e d u n d e r t h e c o n d i t i o n s s p e c i f i e d in I E C 6 0 - 1 .
71-1 © IEC:1993 - 31 -
under voltage.
voltages s h a l l be corrected a c c o r d i n g to I E C 6 0 - 1 .
All impulse withstand voltages shall be verified for both polarities. unless the relevant
When it has been demonstrated that one condition (dry or wet) or one polarity or a
t h e w i t h s t a n d v o l t a g e for this p a r t i c u l a r c o n d i t i o n .
The insulation failures that occur during the test are the basis for the acceptance or
rejection of the test specimen. The relevant apparatus committees or IEC technical
application of the relevant standard withstand voltage to the terminals of the insulation
configuration.
considered to have passed the test if no disruptive discharge occurs. However, if one
disruptive discharge occurs o n the self-restoring i n s u l a t i o n d u r i n g a wet test, the test may
durations shorter than one minute. Unless o t h e rw i s e justified, the test voltages shall be
the s a m e .
the relevant standard withstand voltage to the terminals of the insulation configuration.
- T h r e e - i m p u l s e w i t h s t a n d test i n w h i c h no d i s r u p t i v e d i s c h a r g e is t o l e r a t e d .
s e l f - r e s t o r i n g i n s u l a t i o n are t o l e r a t e d .
71-1 © IEC:1993 -33-
no d i s r u p t i v e d i s c h a r g e is t o l e r a t e d .
- The up-and-down withstand test w i t h seven impulses per level in which disruptive
d i s c h a r g e s on s e l f - r e s t o r i n g i n s u l a t i o n are t o l e r a t e d .
In all the test procedures described above no disruptive discharge is tolerated on the
non-self-restoring i n s u l a t i o n .
applications.
with self-restoring insulation, serious consideration should be given to the fact that in
some test procedures voltages h i g h e r t h a n t h e rated withstand voltage may be applied and
specify the best solution to prove the relevant standard withstand v o l t a g e s . One possibility
An alternative test situation consists of one or more different test conditions (test
demonstrate that the physical conditions for the disruptive discharge development,
NOTE - A typical example is the use of a single voltage source for the tests of longitudinal insulation.
while insulating the base, instead of a combined voltage test. In this case, the de m o ns t rat i on mentioned
above concerning the disruptive discharge development is a very stringent condition for the acceptance of
the alternative.
a) Power-frequency tests
insulation may require a power-frequency withstand voltage higher than the phase-to
earth power-frequency withstand voltage as shown in table 2. In such cases the test
shall preferably be performed with two voltage sources. One terminal shall be energized
with the phase-to-earth power-frequency withstand voltage and the other with the
- with one power-frequency voltage source. The earth terminal may be allowed to
earth t e r m i n a l .
NOTE - If the voltage that the terminal, which is earthed in service, assumes to earth in the test
influences the electrical stresses on the phase terminal (as occurs in compressed gas longitudinal
insulation having Um � 7 2 , 5 kV), means shall be adopted to maintain this voltage as close as possible to
the difference between the test voltage of the phase-to-phase (or longitudinal) insulation and that of the
phase-to-earth i n s u l a t i o n .
in table 2. In such cases, the relevant tests shall be performed immediately after the
phase-to-earth insulation tests increasing the voltage without changing the test
to earth are c o n s i d e r e d as n o n - e v e n t s .
When the number of discharges to earth does not allow the test to be performed, a
lightning impulse withstand voltage and a power-frequency component with the peak
value of opposite polarity equal to the difference between the phase-to-phase (or
for external insulation, the relevant apparatus committees may specify that the phase-to
earth i n s u l a t i o n be i n c r e a s e d .
requirements:
- the test configuration shall suitably duplicate the service configuration, especially
- the e a rt h t e r m i n a l s h a l l be c o n n e c t e d to e a rt h ;
earthed;
- in longitudinal insulation tests the terminals of the o t h e r two phases shall be either
removed or e a rt h e d .
The test shall be repeated for all possible combinations of the phase terminals, unless
proved u n n e c e s s a r y by c o n s i d e r a t i o n s of electrical s y m m e t r y .
The longitudinal insulation lightning impulse withstand test of equipment in range II also
In the evaluation of the test results, any disruptive discharge is counted. More detailed
For special applications, the relevant apparatus committees may extend to longitudinal
to e q u i p m e n t of r a n g e I .
71-1 © IEC:1993 - 3 9 -
I I
l i m i t i n g devices (see 3 . 2 1 )
,,
Insulation characteristics
Representative voltages
Insulation characteristics
Statistical distribution ( +)
factor Kc (see 3 . 2 5 )
Co-ordination withstand
Atmospheric correction
voltages, Ucw (see 3.24)
factor, Ka (see 3 . 2 8 )
Equipment test a s s e m b l y * )
Dispersion in p r o d u c t i o n * ) i
Quality of installation *)
Application of factors to account for the
*) Effects combined in a
(see3.31)
i
Standard withstand voltages
(see 4 . 8 )
NOTE - I n brackets the subclauses reporting the d e f i n i t i o n of the term or the description of the action.
sided b o x e s refer to r e q u i r e d i n p u t .
-c
(I)
ci
(/)
::1.
(/)
::1.
(/)
(I)
·;;; I\ 0
0 ·- ....
(/)
_J ·-
-
0 (/) ...,'."
::1.
e
(I)
0
C\I
>
0
-0
c
cu
(/)
(/)
::!.
(I)
0
O> (/)
C\I
cu (/)
(/)
::1.
..... I\ ::1.
c E 0
0 0 0
I-c.
>
_g 0 l() l()
C\I C\I
/\I ('\J
O> VI
c (/)
II
.fn ::!. 1-
N
1-
N
(/) 0
0
...
(I)
.....
0
l()
(/)
0
(/)
(I)
(/)
0.
N
cu (') N >,
I
s: 0 I C O
(/) >, 0 O C
0 ('\J
0 Cl)
<O -
� �
"O
l() /\I
�
0
c 0 v
VI
-
:::,
o- -
(I) (/)
......... <D
cu a. "'O �
-O -Q) -
(I)
II
E /\I VI .
(/) v
'
(I)
(I)
(/) N .........
N
I-
(/) I .c ;;::,
I 0
(/) 0 (/) 0
co
cu >, 0 <O v
a.
0
(')
c
o (I)
::,
O"
1
(I)
;;::,
.D 0
N N
_J
cu I I
I- (/)
0 0
(/)
<D <O
::,
0
0 �
0
::,
0 <D 0
c N eo N
-� I
/\I
I c
Ill
0 0 0
It) ......... l()
>
0 (I)
II
(I)
-=
>,
.s:::,
"'O
·o
(/) C) a. a.
(/)
(/)
!!! Ill
Ill - .c (I)
0
g (/) .a
0
I-
71-1 © IEC:1993 -43-
Table 2 - S t a n d a r d i n s u l a t i o n l e v e l s for r a n g e I
kV kV kV
3,6 10 20
40
7,2 20 40
60
12 28 60
75
95
17,5 38 75
95
24 50 95
125
145
36 70 145
170
52 95 250
230 550
230 550
275 650
275 650
325 750
(325) (750)
360 850
395 950
460 1 050
withstand
equipment Longitudinal Phase-to-earth Phase-to-phase
voltage
insulation (ratio to the
um
(note 1) phase-to-earth
peak value)
kV kV kV kV
950
1 050
1 050
1 175
1 175
1 300
1 425
1 300
1 425
1 550
1 800
1 950
2 100
NOTES
2 The introduction of Um = 550 kV (instead of 525 kV), 800 kV (instead of 765 kV),
1 200 kV, of a v a l u e between 765 kV and 1 200 kV, and of the associated standard
withstand v o l t a g e s , is under c o n s i d e r a t i o n .
71-1 © IEC:1993 -47-
Annex A
(informative)
kV kV kV
2,75 15 30
45
60
5,5 19 45
60
75
8,25 27 60
75
95
15,5 35 75
85
110
27,0 50 95
125
150
30,0 70 160
38,0 70 125
150
200
40,5 80 190
200
250
185 450
325 750