Académique Documents
Professionnel Documents
Culture Documents
Ma 2015
Ma 2015
2, SPRING 2015
77
Manuscript received April 22, 2014; revised August 17, 2014; accepted
October 15, 2014. Date of current version April 29, 2015. This work was
supported in part by the National Basic Research Program (973 Program)
of China under Grant 2012CB215200, in part by the National Natural
Science Foundation of China under Grant 51277193, in part by the Chinese
University Scientific Fund Project under Grant 2014ZZD02, in part by the
Scientific Research Foundation for the Returned Overseas Chinese Scholars,
Ministry of State Education of 2011, under Grant 1139, in part by the
Natural Science Foundation of Hebei Province under Grant E2012502034,
in part by the Beijing Metropolis Beijing Nova Program under Grant
Z141101001814012, in part by the Excellent Talents in Beijing City under
Grant 2013B009005000001, and in part by the Fok Ying Tung Education
Foundation under Grant 141057.
J. Ma is with the State Key Laboratory of Alternate Electrical Power System
with Renewable Energy Sources, North China Electric Power University,
Beijing 102200, China, and also with the Bradley Department of Electrical
and Computer Engineering, Virginia Polytechnic Institute and State University,
Blacksburg, VA 24061 USA (e-mail: hdmajing@aliyun.com).
W. Ma, X. Yan, and Z. Wang are with the State Key Laboratory of Alternate
Electrical Power System with Renewable Energy Sources, North China
Electric Power University, Beijing 102200, China (e-mail: jnyzmawei@
163.com; yanxinsdu@163.co; wangzp1103@aliyun.com).
Associate Editor managing this papers review: S. Ali Khajehoddin.
Color versions of one or more of the figures in this paper are available
online at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/CJECE.2014.2364256
I. I NTRODUCTION
0840-8688 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
78
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Fig. 1.
Fig. 2.
where Imn is the short-circuit current on the fault line MN, and
Ij m is the short-circuit current on line JM where the upstream
protection is located.
Define the protection range of distance protection zone-II as
II Z
Z jm
Z set.1
jm
I
II
II
= K rel
K rel
1 K rel
. (3)
K b Z mn
K b Z mn
The protection range Pr represents the line length on the
downstream line MN covered by the zone-II of the protection
at IED1.
According to (3), the branch coefficient K b has the followII :
ing relationship with the reliability coefficient of zone- II K rel
79
Z mn
Pr K b .
Z jm
(6)
Pr =
II
K rel
Z jm
Z mn
Z jm
I
K b K rel + Z mn
K b Pr +
(4)
80
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
(3)
where IJ(3)
B and I J C are the fault current of phase B and C
measured at IED1.
Equation (9) can be rewritten as
(3)
U U (3)
JB
JC
(10)
(3)
= 31 .
I Z j m
JB
ks | IJ B Z j m |
|U J B U M B |
=
|U J B U J C |
|U J B |
(14)
between
following relationship:
(3)
(3)
U
(3) (3)
(3)
(3)
M B U MC + U J B U J C U M B U MC
(3)
(3) (3)
(3)
(3)
+ U
= 3 2 I Z mn + I Z j m
= U
U
M BC
J BC
M BC
MB
JB
(15)
(3)
U M B
(3)
U MC
where
and
are the fault voltages of phase B and C
(3)
(3)
(3)
(3)
measured at IED3. U M
BC = U M B U MC and U J BC =
(3)
(3)
(3)
(3)
are the fault current of phase B
U U . I and I
JB
JC
JB
MB
(2) (2)
(2)
(2)
M B U MC + U J B U J C U M B U MC
(2) (2)
(2)
(2)
(2)
= U M
BC + U J BC U M BC = 2 2 I M B Z mn + I J B Z j m
(17)
where U J(2)B and U J(2)
C are the fault voltages of phase B and C
(2)
(2)
(2)
= U M
measured at IED3. U M
BC
B U MC and
(2)
(2)
(2)
(2)
(2)
U J BC = U J B U J C . IJ B and IM B are the fault current of
phase B measured at IED1 and IED3, respectively.
Equation (17) can be rewritten as
(2)
(2) (2)
U
(2)
M BC + U J BC U M BC 2 I J B Z j m
= 22 . (18)
(2)
I Z mn
MB
Combining (16) and (18), the adaptive action factor A f 2 is
defined
kd kr | IM1 Z mn |
A f2 =
(19)
|U M1 2 | + |U J 1 2 U M1 2 | kd | IJ 1 Z j m |
where U M1 2 = U M1 U M2 , and U M1 , U M2 are the
voltages of the fault phases 1 , 2 . IM1 is the current
of the fault phase 1 . U M1 , U M2 , and IM1 are all
measured at IED3 and transmitted to IED1. Similarly,
U J 1 2 = U J 1 U J 2 , and U J 1 , U J 2 are the voltages of the
fault phases 1 , 2 . IJ 1 is the current of the fault phase 1 .
U J 1 , U J 2 , and IJ 1 are all measured at IED1. kd is the fault
type coefficient. kr is the reliability coefficient, and in this
paper kr = 0.5 (see Appendix).
Phase B and C are taken as an example to analyze the
operation characteristic of the adaptive action factor A f 2 .
When the system operates in normal state, the adaptive action
factor A f 2 is
kr | IM B Z mn |
|U M BC | + |U J BC U M BC | | IJ B Z j n |
0.5 |U M B U N B |
=
(20)
3|U M B | + ( 3 1)| IJ B Z j n |
M B |. Therefore, in
where |U M B U N B | ( 6 2)/2|
U
normal operation state A f 2 < (3 2 6)/12 0.1494.
Besides, comparison between (16), (18), and (19) shows that,
for any type of interphase fault on the neighboring line,
Af2 =
81
Fig. 4.
Fig. 3.
82
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
TABLE II
L INE PARAMETERS OF IEEE N EW E NGLAND
10-M ACHINE 39-B US S YSTEM
Fig. 6. Fault occurs at 90% of line 3-18. (a) Adaptive action factor of R18
for three-phase fault. (b) Adaptive action factor of R2 for phase-to-phase fault.
TABLE III
A DAPTIVE A CTION FACTOR OF R18 W HEN FAULT O CCURS ON L INE 18-3
Fig. 5.
after fault occurs on line 18-3, the adaptive action factor of R18 A f 118 increases rapidly. When A f 118 > 1,
R18 operates immediately.
When fault occurs at different locations on line 18-3, the
adaptive action factor of R18 is shown in Table III. It can be
seen that, R18 is able to respond accurately to interphase fault
at any location on line 18-3. Moreover, when an interphase
fault occurs at the end of line 18-3, the adaptive action factor
of R18 has enough sensitivity, which can ensure the selectivity
of protection.
B. Fault on the Neighboring Line 3-4
When fault occurs at 30% of line 3-4, and if R3 as the
primary protection does not operate, then R2 and R18 will
provide backup protection. Figs. 7 and 8 are the adaptive action
factor characteristic of R2 and R18. It can be seen that, for any
type of interphase fault, after the fault occurs both A f 22 > 1
and A f 218 > 1, i.e., both R2 and R18 are effective as the
adaptive backup protection.
When fault occurs at different locations on line 3-4,
the adaptive action factors of R2 and R18 are shown in
Tables IV and V, respectively. It can be seen that, the adaptive
83
TABLE IV
A DAPTIVE A CTION FACTOR OF R2 W HEN FAULT O CCURS ON L INE 3-4
Fig. 7. Three-phase fault occurs at 30% of line 3-4. (a) Adaptive action
factor characteristic of R2. (b) Adaptive action factor characteristic of R18.
TABLE V
A DAPTIVE A CTION FACTOR OF R18 W HEN FAULT O CCURS ON L INE 3-4
Fig. 8. Phase-to-phase fault occurs at 30% of line 3-4. (a) Adaptive action
factor characteristic of R2. (b) Adaptive action factor characteristic of R18.
84
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
TABLE VI
A DAPTIVE A CTION FACTOR OF R18 W HEN FAULT O CCURS
VIA
TABLE IX
A DAPTIVE A CTION FACTOR OF R2 AND R18
W HEN FAULT O CCURS ON L INE 3-4
TABLE VII
A DAPTIVE A CTION FACTOR OF R2 W HEN FAULT O CCURS
VIA
TABLE X
T IME TAKEN BY THE A DAPTIVE I NTERPHASE BACKUP P ROTECTION
TO I SSUE THE
T RIPPING C OMMAND
TABLE VIII
A DAPTIVE A CTION FACTOR OF R18 W HEN FAULT O CCURS ON L INE 18-3
85
Fig. 9. Phase-to-phase fault occurs at 30% of line 3-4. (a) Adaptive action
factor characteristic of R2. (b) Adaptive action factor characteristic of R18.
Fig. 10. Simulation result of traditional distance protection when fault occurs
on line 3-4 at different location. (a) Measured impedance trajectory of R2.
(b) Measured impedance trajectory of R18.
(21)
86
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015
Fig. 13.
Positive sequence current angle absolute differences for lines
connected to Bus3 when a phase-to-phase fault occurs at 30% of line 3-4.
Fig. 14. Waveforms of voltage and current during power swing. (a) Voltage
waveform. (b) Current waveform.
Fig. 15.
87
that
A f 1 = ( 6 2)/(2 3)ks 1, i.e., ks (3 2 + 6)/2.
When fault occurs at the end of the line, it requires that
A f 1 = ks 1.
Therefore, the value range of ks is 1
ks (3 2 + 6)/2. If ks applies a relatively small value,
for example ks = 1, then the protection might refuse to
operate when fault occurs at the end of the line. On the
other hand,
ifks applies a relatively big value, for example,
ks = (3 2 + 6)/2, then the protection might maloperate
when the system is in normal operation state.In view of these
factors, the margin coefficient ks is set to be 3 in this paper.
The value range of the reliability coefficient kr is kr 0.5.
When the system is in normal operation state, if the voltage
phase angle difference between thetwo line
endsreaches 30,
the adaptive action factor A f 2 ( 6 2)/(2 3)kr . When
phase-to-phase fault occurs at the midpoint of the downstream
line, the adaptive action factor A f 2 = 2kr . Since the setting
value of A f 2 is 1, when the system
is in normal
operation
state, it requires
that
A
(
6
2)/(2
3)kr 1,
f
2
VI. C ONCLUSION
ACKNOWLEDGMENT
A PPENDIX
The value
range
of the margin coefficient ks is 1
ks (3 2 + 6)/2. When the system is in normal
operation state, if the voltage phase angle difference
R EFERENCES
[1] S. Eric, S. S. Venkata, and J. Mitra, Microgrid protection using
communication-assisted digital relays, IEEE Trans. Power Del., vol. 25,
no. 4, pp. 27892796, Oct. 2010.
[2] J. Ma, X. Wang, Y. G. Zhang, and Z. P. Wang, A novel adaptive current
protection scheme for distribution systems with distributed generation,
Int. J. Elect. Power Energy Syst., vol. 43, no. 1, pp. 14601466,
Dec. 2012.
[3] J. Li, J. He, H. Zhang, F. Xie, Z. Bo, and T. Yip, Research on adaptive
protection based on integrated protection, in Proc. Int. Conf. Adv. Power
Syst. Automat. Protection, vol. 2. Oct. 2011, pp. 848852.
[4] J. Ma, W. Ma, X. Wang, and Z. Wang, A new adaptive voltage
protection scheme for distribution network with distributed generations,
Can. J. Elect. Comput. Eng., vol. 36, no. 4, pp. 142151, 2013.
[5] A. K. Pradhan and G. Jos, Adaptive distance relay setting for lines
connecting wind farms, IEEE Trans. Energy Convers., vol. 22, no. 1,
pp. 206213, Mar. 2007.
[6] H. Sadeghi, A novel method for adaptive distance protection of transmission line connected to wind farms, Int. J. Elect. Power Energy Syst.,
vol. 43, no. 1, pp. 13761382, Dec. 2012.
[7] T. Hayder, U. Schaerli, K. Feser, and L. Schiel, Universal adaptive
differential protection for regulating transformers, IEEE Trans. Power
Del., vol. 23, no. 2, pp. 568572, Apr. 2008.
88
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 38, NO. 2, SPRING 2015