Vous êtes sur la page 1sur 4

Doc. N.

1SDH000721R0506 - B0530

SACE Tmax XT

1SDH000721R0506

Sganciatori Ekip LSI e Ekip LSIG XT2-XT4


Release Ekip LSI and Ekip LSIG XT2-XT4
Auslser Ekip LSI und Ekip LSIG XT2-XT4
Dclencheur Ekip LSI et Ekip LSIG XT2-XT4
Rel Ekip LSI y Ekip LSIG XT2-XT4
Ekip LSI Ekip LSIG XT2-XT4
XT2-XT4

Istruzioni di montaggio 1SDH000721R505


Assembly instructions 1SDH000721R505
Montageanleitung 1SDH000721R505
Instructions de montage 1SDH000721R505
Instrucciones de montaje 1SDH000721R505

XT2-XT4

XT2

XT4

1
* fold this paper with barcode on the outer side

XT2-XT4

Settaggio di default manuale


Manual default setting
Manuelle Default-Einstellung
Configuration par dfauit manuelle
Ajuste de default manual

(Neutral setting on fig. 9)

LED

Color

CONDITION Run time

Green

LED Fixed = Device active

L
S
G

Red
Red
Red

L|S |I|G

Red

LED Fixed = L pre alarm (0,9 * I1 < I < 1,2 * I1)


LED Blinking = L alarm (I > 1,2 * I1)
LED Blinking = S alarm (I > I2)
LED Blinking = G alarm (I > I4)
_ I.
All LED Blinking = Parameters inconsistency - L = S or S >
All LED Blinking without Parameters inconsistency = generic fault (please contact ABB)

XT2-XT4

Esempio - Example - Beispiel - Exemple - Ejemplo -


In = 100A
I1 = 100x(0,4+0,08+0,32)=80A
t1 = 12s @240A (3I1)

XT2

XT4

IEC-UL
IEC-UL
UL
IEC
IEC-UL
UL
IEC
IEC-UL
UL
IEC
IEC-UL
UL
IEC
UL
IEC-UL

In (A)
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

0,4
4
10
24,0
25,2
40
50
64,0
16,0
24
25,2
40
60
64
90
100

0,42
4,2
10,5
25,2
26,5
42
52,5
67,2
16,8
25,2
26,5
42
63
67,2
94,5
105

I1 (In)
0,44
4,4
11
26,4
27,7
44
55
70,4
17,6
26,4
27,7
44
66
70,4
99
110

0,96
9,6
24
57,6
60,5
96
120
153,6
38,4
57,6
60,5
96
144
153,6
216
240

0,98
1
9,8
10
24,5
25
58,8
60
61,7
63
98
100
122,5 125
156,8 160
39,2
40
58,8
60
61,7
63
98
100
147
150
156,8 160
220,5 225
245 250

XT2-XT4

Esempio - Example - Beispiel - Exemple - Ejemplo -


In = 100A
I2 = 100x(1+2)=300A
2
t2 (I t=ON) = 0,1s @1000A (10In)

XT2

XT4

IEC - UL
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
UL
IEC - UL

In (A)
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

SACE Tmax | ABB

1
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

1,5
15
37,5
90
94,5
150
188
240
60
90
94,5
150
225
240
338
375

2
20
50
120
126
200
250
320
80
120
126
200
300
320
450
500

2,5
25
62,5
150
158
250
313
400
100
150
158
250
375
400
563
625

3
30
75
180
189
300
375
480
120
180
189
300
450
480
675
750

3,5
35
87,5
210
221
350
438
560
140
210
221
350
525
560
788
875

I2 (In)
4,5
5,5
6,5
45
55
65
113
138
163
270 330 390
284 347 410
450
550 650
563 688 813
720 880 1040
180 220 260
270 330 390
284 347 410
450
550 650
675 825 975
720 880 1040
1013 1238 1463
1125 1375 1625

7
7,5
8
8,5
9
10
70
75
80
85
90
100
175
188 200 213 225 250
420 450 480 510
540 600
441 473 504 536
567 630
700
750 800 850 900 1000
875 938 1000 1063 1125 1250
1120 1200 1280 1360 1440 1600
280 300 320 340 360 400
420 450 480 510
540 600
441 473 504 536
567 630
700
750 800 850 900 1000
1050 1125 1200 1275 1350 1500
1120 1200 1280 1360 1440 1600
1575 1688 1800 1913 2025 2250
1750 1875 2000 2125 2250 2500

XT2-XT4

Esempio - Example - Beispiel - Exemple - Ejemplo -


In = 100A
I3 = 100x(1,5+5,5)=700A

XT2

XT4

IEC - UL
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
UL
IEC - UL

In (A)
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

1
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

1,5
15
37,5
90
94,5
150
188
240
60
90
94,5
150
225
240
338
375

2
20
50
120
126
200
250
320
80
120
126
200
300
320
450
500

2,5
25
62,5
150
158
250
313
400
100
150
158
250
375
400
563
625

3
30
75
180
189
300
375
480
120
180
189
300
450
480
675
750

3,5
35
87,5
210
221
350
438
560
140
210
221
350
525
560
788
875

I3 (In)
4,5
5,5
6,5
45
55
65
113
138
163
270 330 390
284 347 410
450
550 650
563 688 813
720 880 1040
180 220 260
270 330 390
284 347 410
450
550 650
675 825 975
720 880 1040
1013 1238 1463
1125 1375 1625

7
7,5
8
8,5
9
10
70
75
80
85
90
100
175
188 200 213 225 250
420 450 480 510
540 600
441 473 504 536
567 630
700
750 800 850 900 1000
875 938 1000 1063 1125 1250
1120 1200 1280 1360 1440 1600
280 300 320 340 360 400
420 450 480 510
540 600
441 473 504 536
567 630
700
750 800 850 900 1000
1050 1125 1200 1275 1350 1500
1120 1200 1280 1360 1440 1600
1575 1688 1800 1913 2025 2250
1750 1875 2000 2125 2250 2500

XT2-XT4

Esempio - Example - Beispiel - Exemple - Ejemplo -


In = 100A
I4 = 100x(0,2+0,25)=45A
t4 = 0,2s @ I>I4

XT2

XT4

IEC - UL
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
IEC - UL
UL
IEC
UL
IEC - UL

In (A)
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

0.2
2
5
12
12.6
20
25
32
8
12
12.6
20
30
32
45
50

0.25
2.5
6.25
15
15.8
25
31.3
40
10
15
15.8
25
37.5
40
56.3
62.5

I4 (In)
0.45 0.55
4.5
5.5
11.3 13.8
27
33
28.4 34.7
45
55
56.3 68.8
72
88
18
22
27
33
28.4 34.7
45
55
67.5 82.5
72
88
101 124
113
138

0.75
7.5
18.8
45
47.3
75
93.8
120
30
45
47.3
75
113
120
169
188

0.8
8
20
48
50.4
80
100
128
32
48
50.4
80
120
128
180
200

1
10
25
60
63
100
125
160
40
60
63
100
150
160
225
250

XT2-XT4

Settaggio elettronico
Electronic setting
elektronische Einstellung
Configuration lectronique
Ajuste electrnico

Ekip LSI
Ekip LSIG
L

I
G*

I1

D EF A U LT

R A N GE
See Syst em Int er f ace
1SD H0 0 1115R 0 0 0 1

1 In

0.4 1 In step 0.01 In

t1

60 s

3 60 s step 3 s

Curve type

t = k / I2

t = k / I2 | t = k

I2

OFF

1 10 In step 0.1 In

t2

0.4 s

0.5 0.4 s step 0.01 s

I3

4.5 In

1 10 In step 0.1 In

I4

OFF

0.2 1 In step 0.02 In

t4

0.8 s

0.1 0.8 s step 0.05 s

* Ekip LSIG only

Rem = Enalbed
Modifica settaggi elettronici e invio comandi sa System Bus
Changing settings and sending electronic commands from
System Bus
ndern von Einstellungen und Senden elektronischer Befehle
vom System-Bus

Loc Disabled
Modification des paramtres et lenvoi de commandes
lectroniques au Bus Systme

Rem Enabled

Cambio de la configuracin y el envio de comandos


electronicos de System Bus
(Neutral setting on fig. 9)

SACE Tmax | ABB

NEUTRAL SETTING XT2-XT4/III-IV

CB Poles

Neutral setting

III + Ext Ne

Always only by means of Ekip T&P or System Bus

ON; 100%

IV

Always only by means of dip switches

ON; 100%

Default setting

Esempio - Example - Beispiel - Exemple - Ejemplo -

Dip switches setting example


with IV:
Ne=ON; 50%

10

TRIP TEST

1
PROCEDURA DI CONTROLLO

DIAGNOSTIC PROCEED
- Connect and switch on
Ekip TT
UNIT CHECK LED:
- CONTROLLO LED:
all the leds in the relay
tutti i led del rel si
must come on
devono accendere
- ULTIMA INDICAZIONE DI TRIP: - LAST TRIP INDICATION:
if present in the relay's
se presente nella memoria
data store
del rel
- LED:
remains on for
- LED:
as long as the TT is
resta acceso finch lunit TT
connected to the relay
e connessa al rel
- READY TO TRIP
- PRONTO PER TRIP

- Collegare e accendere
Ekip TT

DIAGISTIKABLAUF
- Verbinden en inschakelen
Ekip TT
- EINEITHSPRUF-LED:
Alle LEDs des Relais mssen
aufleuchten
- ANGABE DER LETZTEN AUSLOSUNG:
Wenn im Speicher des Relais
vorhanden.
- LED: Bleibt angeschaltet,
bis die Einheit TT an die Relais
angeschlossen ist.
- AUSLOSEBEREIT

PROCDURE DE DIAGNOSTIC
- Brancher et allumer
Ekip TT
- UNIT CHECK LED : toutes les
diodes du relais doivent
s'allumer
- LAST TRIP INDICATION :
si prsente dans la mmoire
du relais
- DIODE: reste
allume tant que l'unit TT
est connecte au relais
- PRT DCLENCHER

PROCEDIMIENTO DIAGNOSTICO
- Conectar y encender
- Ekip TT
Ekip TT
- LED CONTROL UNIDAD: todos los - :
led del rel se deben

encender
- INDICACION ULTIMA ACTUACION: -
si est presente en la memoria

del rel
- LED: queda encendido
- LED:
TT
mientras la unidad TT

permanezca conectada con el rel


- LISTO PARA LA ACTUACION
-

LED Ekip TT

Rosso
Verde
Red
Green
Rot
Grn
Rouge
Vert
Rojo
Verde

Dispositivo acceso
Sostituire batterie
Device ON
Change battery
Einrichtung eingeschaltet Batterie ersetzen
Dispositif allum
Remplacer batteries
Dispositivo encendido
Sustituir bateras

PRESS

Copyright

2010-2016 ABB. All rights reserved


www.abb.com

4
CLACK

Vous aimerez peut-être aussi