Architecte
Jamel fraj
C 0.40 0.40 IMMEUBLE FAFOU RUE AMOR BEN SLIMENE GAFSA
IPE180 dalle mixte IPE180 Tél :76200126 / Fax: 76202559 Port: 97939466
B3 104.65 m Email:jamelarch22@yahoo.fr
0.60 104.27 m
IPE180
IPE140
IPE140
IPE140
IPE140
IPE140
IPE180
IPE180 Architecte
(32*180)
(32*180)
TLILI NOURHENE
B3
B3
7 P14 (32*60) Port : 21174475
6 B01
IPE180 P14 (32*60) B01
B2 11
1
B01 1.61 4.70 1.61 11 Architecte
CHIBANI MARWEN
B01
Tél: 71 340 110 / Port: 96628853
IPE140
IPE140
IPE140
IPE140
IPE140
IPE180
IPE180
0.14
IPE140
IPE140
IPE140
IPE140
IPE140
IPE180
IPE180
dalle mixte Tôle Toitesco Ref Fc83.732 PH 1ér étage Bureau de controle
104.65 m IPE140
ep=0.7 mm
IPE180 105.68 m 0.10 Carthage Controle
3 Rue Med Marzouki El manzah 8 ariana
Tél : 70866812
A1 IPE180 Fax: 70866813
B1 bis e-mail: contact@carthage-control.com
(22*140) Détail Dalle Mixte
13 1 : 15 Entreprise
B1 (22*80)
A Vue 3d (Jarret ) Détail 3 Société Nouvelle de Bâtiment
Av. Salah Ben Youssef. Bureau N° 6. Midoun djerba
5 12 1 : 10 C3 D E Tél.: 00216 75.730.641Fax: +216 75.733.036:
5'A 5'B e-mail: snb.cherni@gmail.com
4.88 1.41 0.85 0.85 0.85 0.85 0.85 0.85 1.41 1.45 10
e-mail: b.technique.snb@gmail.com
B2 B01
0.37 m
104.65 m
Platine e=1cm IPE180
0.85 0.85 0.85 0.85 (0.37*0.09)
0.38
dalle mixte dalle mixte
104.65 m +8 Bls ∅16 104.65 m
0.13 m
IPE180
0.09 m
B2 (22*70)
IPE180
0.77 N° Description Date
4.93 0.09 m
Nota:
A A1 B B1 B2 B3 C C1 C2 C3 D E
- Qualité d'acier E24-2 selon NFE 35.501 ou équivalent
- Dimensions du cordon de soudure a=0.7xe avec
e=sup(e1,e2).
PH 2éme étage - Toutes les boulonneries qualité 8.8 min
109.23 m Selon NFE 27005 sauf indication.
1.50 2.00 0.39 2.00 2.00 0.27 1.73 2.00 0.55 0.560.24
04/03/2024 11:28:21
Plan d'exécution structure Métallique
Plancher Mixte
Coupe 2 {3D}
2 1 : 30
3 Echelle Comme indiqué
NOTE DE CALCUL
I. Vue 3d
2. Données - Barres
3. Données - Sections
4. Données - Matériaux
Matéria E G N LX [1/°C] RO Re
u [MPa] [MPa] U [kN/m3] [MPa]
5. Données - Appuis
Nom de l'appui Liste de noeuds Liste de bords Liste d'objets Conditions d'appui
III. Chargements
1. Cas des charges
- Cas: 245
Cas Type de charge Liste Valeurs de la charge
Cas 2 EXPL1
Somme totale -0,00 0,00 83,69 -0,35 -7,41 0,34
Somme -0,00 0,00 83,69 213,41 -457,79 -0,00
réactions
Somme efforts 0,0 0,0 -83,69 -213,41 457,79 0,0
Vérification -0,00 0,00 -0,00 -0,00 -0,00 -0,00
Précision 2,01265e-01 8,17421e-01
4 5
Cas 5 PERM1
Somme totale -0,00 0,00 122,75 -0,51 -10,87 0,51
Somme -0,00 0,00 122,75 313,00 -671,42 -0,00
réactions
Somme efforts 0,0 0,0 -122,75 -313,00 671,42 0,0
Vérification -0,00 0,00 0,0 -0,00 -0,00 -0,00
Précision 1,49701e-01 8,17421e-01
4 5
V. Déplacements - Valeurs
Noeud/Cas UX [cm] UY [cm] UZ [cm] RX [Rad] RY [Rad] RZ [Rad]
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -9.26 + 1.00*-72.30 + -1.53 = | -83.09 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.04| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-13.41| = |-20.64| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.45 + 1.00*-105.29 + -1.95 = | -118.69 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.05| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-19.52| = |-30.05| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.05 + 1.00*-109.59 + -0.79 = | -121.43 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.02 = 0.03 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-20.31| = |-31.28| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.48 + 1.00*-98.06 + -0.29 = | -109.82 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.01 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-18.17| = |-27.98| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -6.04 + 1.00*-60.68 + -1.58 = | -68.30 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.03 = 0.05 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-11.23| = |-17.29| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -2.08 + 1.00*-37.96 + -1.82 = | -41.86 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.04 = 0.06 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-7.00| = |-10.78| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -8.84 + 1.00*-73.90 + -1.14 = | -83.88 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.02 = 0.03 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-13.70| = |-21.10| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.41 + 1.00*-103.57 + -3.13 = | -118.11 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.06| = |-0.09| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-19.19| = |-29.56| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.46 + 1.00*-108.95 + -0.97 = | -121.38 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.02| = |-0.03| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-20.19| = |-31.09| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -11.00 + 1.00*-98.63 + -2.78 = | -112.41 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.05| = |-0.08| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-18.28| = |-28.15| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -6.47 + 1.00*-58.45 + -2.62 = | -67.53 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.05| = |-0.08| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-10.81| = |-16.65| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.24 Sig D=103.02 MPa
lD_inf=1.53 m C=1.88 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -1.95 + 1.00*-39.00 + -1.61 = | -42.57 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.05| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-7.19| = |-11.07| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_inf=2.00 m C=2.86 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=219991.41 Lz=2.00 m Muz=16846.47
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=26.97 kFy=1.00 Lambda z=97.46 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.01 + 1.00*1.00*3.48 + 1.00*0.09 = 3.58 < 235.00
MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.51| = |-0.79| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
----------------------------------------------------------------------------------------------------------------------------------
Profil correct
Date : 20/03/24 Page : 30
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_sup=2.00 m C=2.41 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.02 + 1.00*-2.49 + -0.10 = | -2.61 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.25| = |-0.39| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_inf=2.00 m C=2.76 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=46532.39 Lz=2.00 m Muz=3563.35
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=26.97 kFy=1.00 Lambda z=97.46 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.06 + 1.00*1.00*0.70 + 1.00*0.16 = 0.92 < 235.00
MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.08 = 0.13 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
Profil correct !!!
Date : 20/03/24 Page : 32
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_sup=2.00 m C=1.48 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=12204.83 Lz=2.00 m Muz=934.62
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=26.97 kFy=1.00 Lambda z=97.46 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.23 + 1.00*1.00*0.56 + 1.00*0.38 = 1.17 < 235.00
MPa (3.731)
1.54*Tauy = 1.54*0.01 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.03 = 0.04 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 33
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.03 Sig D=113.61 MPa
lD_sup=0.55 m C=1.01 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=128338.45 Lz=0.55 m Muz=9827.89
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=7.42 kFy=1.00 Lambda z=26.80 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.29 + 1.00*1.00*0.23 + 1.00*1.59 = 2.11 < 235.00
MPa (3.731)
1.54*Tauy = 1.54*0.08 = 0.13 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 34
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_sup=2.00 m C=2.08 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.07 + 1.00*-3.03 + -0.08 = | -3.19 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.26 = 0.40 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_inf=2.00 m C=2.90 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.01 + 1.00*-3.92 + -0.11 = | -4.04 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.50 = 0.77 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_sup=2.00 m C=2.91 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=117852.28 Lz=2.00 m Muz=9024.88
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=26.97 kFy=1.00 Lambda z=97.46 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.02 + 1.00*1.00*3.40 + 1.00*0.19 = 3.61 < 235.00
MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.44 = 0.67 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 37
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.39 Sig D=96.68 MPa
lD_inf=2.00 m C=2.82 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=10554.26 Lz=2.00 m Muz=808.22
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=26.97 kFy=1.00 Lambda z=97.46 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.27 + 1.00*1.00*3.66 + 1.00*0.25 = 4.19 < 235.00
MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.55 = 0.85 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 38
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.03 Sig D=113.61 MPa
lD_inf=0.55 m C=2.05 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=108784.19 Lz=0.55 m Muz=8330.46
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=7.42 kFy=1.00 Lambda z=26.80 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.35 + 1.00*1.00*2.60 + 1.00*1.19 = 4.13 < 235.00
MPa (3.731)
1.54*Tauy = |1.54*-0.07| = |-0.11| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.80 = 1.24 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.53 Sig D=91.44 MPa
lD_inf=2.39 m C=1.61 kD=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.39 m Muy=3038.78 Lz=2.39 m Muz=232.70
Lfy=2.39 m k1y=1.00 Lfz=2.39 m k1z=1.00
Lambda y=32.23 kFy=1.00 Lambda z=116.46 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.66 + 1.00*1.00*0.77 + 1.01*0.08 = 1.51 < 235.00
MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.04| = |-0.06| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 40
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=1.53 Sig D=91.44 MPa
lD_inf=2.39 m C=1.22 kD=1.02
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.39 m Muy=2700.38 Lz=2.39 m Muz=206.79
Lfy=2.39 m k1y=1.00 Lfz=2.39 m k1z=1.00
Lambda y=32.23 kFy=1.00 Lambda z=116.46 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kD*kFy*SigFy + kFz*SigFz = 1.00*0.74 + 1.02*1.00*0.46 + 1.01*0.04 = 1.25 < 235.00
MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.01| = |-0.02| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 41
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=2.43 Sig D=55.18 MPa
lD_sup=5.10 m C=1.00 kD=2.56
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.38 + 2.56*33.46 + 0.10 = 85.49 < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.24 = 1.90 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 3.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=2.43 Sig D=55.18 MPa
lD_sup=5.10 m C=1.03 kD=2.49
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.46 + 2.49*33.89 + 0.10 = 84.18 < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-1.30| = |-2.00| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 3.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=2.43 Sig D=55.18 MPa
lD_sup=5.10 m C=1.02 kD=2.53
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.40 + 2.53*30.59 + 0.04 = 76.90 < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.03 = 1.58 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 3.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=2.43 Sig D=55.18 MPa
lD_sup=5.10 m C=1.03 kD=2.49
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.54 + 2.49*22.16 + 0.00 = 54.71 < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.03 = 1.59 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 3.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
z=0.00 B=1.00 D=2.43 Sig D=55.18 MPa
lD_sup=5.10 m C=1.01 kD=2.53
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + kD*SigFy + SigFz = -0.65 + 2.53*19.55 + 0.16 = 49.08 < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.85| = |-1.30| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Déplacements
vx = 0.0 cm < vx max = L/150.00 = 3.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -1.38 + -18.75 + -1.11 = | -21.24 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.02 = 0.03 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.30 = 3.54 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.2 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1876.30 Lz=2.00 m Muz=155.72
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.91 + 1.00*14.86 + 1.01*0.58 = 16.36 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.02 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-2.72| = |-4.19| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 48
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=3144.27 Lz=2.00 m Muz=260.95
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.54 + 1.00*13.77 + 1.01*0.40 = 14.72 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.02 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-2.82| = |-4.34| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 49
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=4214.85 Lz=2.00 m Muz=283.34
Lfy=1.80 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=31.36 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.50 + 1.00*13.71 + 1.01*0.08 = 14.29 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.82 = 4.34 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1160.94 Lz=2.00 m Muz=96.35
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*1.47 + 1.00*13.93 + 1.01*0.17 = 15.59 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-1.96| = |-3.01| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 51
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=339615.53 Lz=0.55 m Muz=28185.71
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=9.58 kFy=1.00 Lambda z=33.26 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.07 + 1.00*1.12 + 1.00*0.18 = 1.37 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.30 = 0.45 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 0.3 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 52
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -3.42 + -28.07 + -0.96 = | -32.45 | < 235.00 MPa (3.731)
1.54*Tauy = 1.54*0.02 = 0.03 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*3.04 = 4.69 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.2 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1112.78 Lz=2.00 m Muz=92.35
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*1.53 + 1.00*6.37 + 1.01*0.22 = 8.14 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.13 = 0.20 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 54
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=2222.78 Lz=2.00 m Muz=184.48
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.77 + 1.00*2.64 + 1.01*0.05 = 3.46 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.02 = 0.04 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 55
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=2432.59 Lz=2.00 m Muz=201.89
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.70 + 1.00*3.05 + 1.01*0.04 = 3.79 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.16| = |-0.24| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 56
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1776.22 Lz=2.00 m Muz=147.41
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.96 + 1.00*5.62 + 1.01*0.06 = 6.65 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.47 = 0.73 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 57
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=91818.65 Lz=0.55 m Muz=7620.30
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=9.58 kFy=1.00 Lambda z=33.26 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.25 + 1.00*2.50 + 1.00*0.03 = 2.78 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.76| = |-1.17| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 0.3 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 58
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -4.74 + -30.13 + -0.29 = | -35.16 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.98 = 4.60 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.2 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=917.73 Lz=2.00 m Muz=76.17
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.02
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*1.86 + 1.00*7.75 + 1.02*0.18 = 9.80 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.08 = 0.13 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 60
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1667.91 Lz=2.00 m Muz=138.42
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*1.02 + 1.00*5.20 + 1.01*0.03 = 6.27 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.41 = 0.64 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 61
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=3092.51 Lz=2.00 m Muz=256.66
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.55 + 1.00*3.63 + 1.01*0.02 = 4.20 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.45 = 0.69 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 62
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1775.07 Lz=2.00 m Muz=147.32
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.96 + 1.00*7.65 + 1.01*0.14 = 8.77 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.97| = |-1.49| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 63
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -0.05 + -1.20 + -0.01 = | -1.26 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.28| = |-0.43| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 0.3 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -1.65 + -19.83 + -0.41 = | -21.89 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.00| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.43 = 2.20 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.2 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -0.10 + -9.22 + -0.43 = | -9.74 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.41| = |-0.63| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=25312.15 Lz=2.00 m Muz=2100.73
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.07 + 1.00*2.39 + 1.00*0.07 = 2.52 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.16 = 0.25 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 67
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1718.80 Lz=2.00 m Muz=142.65
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.99 + 1.00*3.76 + 1.01*0.12 = 4.88 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*0.03 = 0.05 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 68
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=2516.26 Lz=2.00 m Muz=208.83
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.68 + 1.00*2.95 + 1.01*0.02 = 3.65 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.00| = |-0.00| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.04| = |-0.06| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 69
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=80267.11 Lz=0.55 m Muz=6661.61
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=9.58 kFy=1.00 Lambda z=33.26 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.28 + 1.00*2.45 + 1.00*0.13 = 2.86 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.75| = |-1.16| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 0.3 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 70
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
SigN + SigFy + SigFz = -2.56 + -15.33 + -1.52 = | -19.42 | < 235.00 MPa (3.731)
1.54*Tauy = |1.54*-0.03| = |-0.05| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.52 = 2.35 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.2 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.6 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=882.65 Lz=2.00 m Muz=73.25
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.02
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*1.93 + 1.00*16.37 + 1.02*0.36 = 18.70 < 235.00 MPa
(3.731)
1.54*Tauy = |1.54*-0.01| = |-0.01| < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.33 = 3.58 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 72
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=5501.48 Lz=2.00 m Muz=456.58
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.31 + 1.00*8.94 + 1.00*0.11 = 9.36 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*1.88 = 2.89 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 73
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=1725.46 Lz=2.00 m Muz=143.20
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.01
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.99 + 1.00*14.37 + 1.01*0.06 = 15.43 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.00 = 0.00 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.52 = 3.88 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 74
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=2.00 m Muy=3309.56 Lz=2.00 m Muz=274.67
Lfy=2.00 m k1y=1.00 Lfz=2.00 m k1z=1.00
Lambda y=34.84 kFy=1.00 Lambda z=120.94 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.52 + 1.00*10.29 + 1.00*0.22 = 11.03 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = 1.54*2.00 = 3.08 < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 1.0 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 1.3 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 75
Société Nouvelle de bâtiment (SNB)
PARAMETRES DE DEVERSEMENT :
-----------------------------------------------------------------------------------------------------------------------------------
-----
PARAMETRES DE FLAMBEMENT :
en y : en z :
Ly=0.55 m Muy=63489.97 Lz=0.55 m Muz=5269.22
Lfy=0.55 m k1y=1.00 Lfz=0.55 m k1z=1.00
Lambda y=9.58 kFy=1.00 Lambda z=33.26 kFz=1.00
-----------------------------------------------------------------------------------------------------------------------------------
-----
FORMULES DE VERIFICATION :
k1*SigN + kFy*SigFy + kFz*SigFz = 1.00*0.36 + 1.00*1.37 + 1.00*0.14 = 1.86 < 235.00 MPa
(3.731)
1.54*Tauy = 1.54*0.01 = 0.01 < 235.00 MPa (1.313)
1.54*Tauz = |1.54*-0.27| = |-0.42| < 235.00 MPa (1.313)
-----------------------------------------------------------------------------------------------------------------------------------
-----
DEPLACEMENTS LIMITES
Flèches
uz = 0.0 cm < uz max = L/200.00 = 0.3 cm Vérifié
Cas de charge décisif : 5 PERM1
Déplacements
vy = 0.0 cm < vy max = L/150.00 = 0.4 cm Vérifié
Cas de charge décisif : 5 PERM1
-----------------------------------------------------------------------------------------------------------------------------------
-----
Profil correct !!!
Date : 20/03/24 Page : 76
Société Nouvelle de bâtiment (SNB)
1. Géométrie
Poteau
Profilé : IPE 180
Barre N° : 5
= -90,0 [Deg] Angle d'inclinaison
hc = 180 [mm] Hauteur de la section du poteau
bfc = 91 [mm] Largeur de la section du poteau
twc = 5 [mm] Epaisseur de l'âme de la section du poteau
tfc = 8 [mm] Epaisseur de l'aile de la section du poteau
rc = 9 [mm] Rayon de congé de la section du poteau
Ac = 23,95 [cm2] Aire de la section du poteau
Ixc = 1316,96 [cm4] Moment d'inertie de la section du poteau
Matériau : ACIER
ec = 235,00 [MPa] Résistance
Poutre
Profilé : IPE 180
Barre N° : 53
= 0,0 [Deg] Angle d'inclinaison
hb = 180 [mm] Hauteur de la section de la poutre
bf = 91 [mm] Largeur de la section de la poutre
twb = 5 [mm] Epaisseur de l'âme de la section de la poutre
tfb = 8 [mm] Epaisseur de l'aile de la section de la poutre
rb = 9 [mm] Rayon de congé de la section de la poutre
rb = 9 [mm] Rayon de congé de la section de la poutre
Ab = 23,95 [cm2] Aire de la section de la poutre
Date : 20/03/24 Page : 77
Société Nouvelle de bâtiment (SNB)
= 0,0 [Deg] Angle d'inclinaison
Ixb = 1316,96 [cm4] Moment d'inertie de la poutre
Matériau : ACIER
eb = 235,00 [MPa] Résistance
Boulons
d= 16 [mm] Diamètre du boulon
Classe = 8.8 Classe du boulon
Fb = 69,08 [kN] Résistance du boulon à la rupture
nh = 2 Nombre de colonnes des boulons
nv = 4 Nombre de rangéss des boulons
h1 = 50 [mm] Pince premier boulon-extrémité supérieure de la platine d'about
Ecartement ei = 60 [mm]
Entraxe pi = 80;90;80 [mm]
Platine
hp = 380 [mm] Hauteur de la platine
bp = 90 [mm] Largeur de la platine
tp = 10 [mm] Epaisseur de la platine
Matériau : ACIER
ep = 235,00 [MPa] Résistance
Jarret inférieur
wd = 90 [mm] Largeur de la platine
tfd = 8 [mm] Epaisseur de l'aile
hd = 180 [mm] Hauteur de la platine
twd = 8 [mm] Epaisseur de l'âme
ld = 750 [mm] Longueur de la platine
= 13,5 [Deg] Angle d'inclinaison
Matériau : ACIER
ebu = 235,00 [MPa] Résistance
Raidisseur poteau
Supérieur
hsu = 164 [mm] Hauteur du raidisseur
bsu = 43 [mm] Largeur du raidisseur
thu = 8 [mm] Epaisseur du raidisseur
Matériau : ACIER
esu = 235,00 [MPa] Résistance
Inférieur
hsd = 164 [mm] Hauteur du raidisseur
bsd = 43 [mm] Largeur du raidisseur
thd = 8 [mm] Epaisseur du raidisseur
Matériau : ACIER
esu = 235,00 [MPa] Résistance
Soudures d'angle
aw = 4 [mm] Soudure âme
af = 6 [mm] Soudure semelle
as = 4 [mm] Soudure du raidisseur
afd = 5 [mm] Soudure horizontale
2. Efforts
Cas : 8: COMB1 2*1.50+5*1.33
My = 8,26 [kN*m] Moment fléchissant
Fz = -11,60 [kN] Effort tranchant
Fx = 1,31 [kN] Effort axial
3. Résultats
Distances de calcul
Boulon N° Type a1 a2 a3 a4 a5 a6 a'1 a'2 a'3 a'4 a'5 a'6 s s1 s2
1 Intérieurs 22 27 24 32 18 27 26 32
2 Centraux 22 27 18 27 85
3 Centraux 22 27 18 27 85
4 Centraux 22 27 18 27 80
x= 27 [mm] Zone comprimée x = es*(b/ea)
Vérification de la poutre
Fres = 34,00 [kN] Effort de compression Fres = 2*Fi - 2*N
Compression réduite de la semelle [9.2.2.2.2]
Nc adm = 220,16 [kN] Résistance de la section de la poutre Ncadm = Abc*e + N*Abc/Ab
Fres Nc adm 34,00 < 220,16 vérifié (0,15)
Vérification du poteau
Compression de l'âme du poteau [9.2.2.2.2]
Fres Fpot 34,00 < 309,94 vérifié (0,11)
Cisaillement de l'âme du poteau - (recommandation C.T.I.C.M)
VR = 124,27 [kN] Effort tranchant dans l'âme VR = 0.47*Av*e
|Fres| VR |34,00| < 124,27 vérifié (0,27)
4. Remarques
Pince du boulon trop faible. 15 [mm] < 27 [mm]