APPLICATIONS
DONNÉES TECHNIQUES
Type Monobloc
Régulation Dixell
Chauffage - Puissance
Electrique - 50 Kw
calorifique (kw)
WWW.FRIGOP.COM
LES CARACTÉRISTIQUES TECHNIQUES SONT À TITRE D'INFORMATION SEULEMENT. FRIGOP SE RÉSERVE LE DROIT DE LES CHANGER SANS AVIS
PRÉALABLE.
Rapport du projet
climate.emerson.com
Logiciel ver.: 8.15.1.4030
Données: 9,40 / 44938
PERFORMANCES AU POINT DE FONCTIONNEMENT SPÉCIFIÉ
4MK-35X données à 50 Hz
Nombre de cylindres 4
Volume balayé, m³/h 99,4
Alésage/Course, mm 80,6/56,0
Longueur/Largeur, mm 688/501
Hauteur, mm 452
Poids net, kg 202
Aspiration, pouce 2 1/8
Refoulement, pouce 1 3/8
Quantité d'huile, l 3,3
Type d’huile (charge d’origine) POE RL32-3MAF
Type d’huile (huiles approuvées) POE RL32-3MAF, POE MOBIL
EAL Arctic 22 CC
Fixations mm (Ø) 381 x 305 (18)
Pression sonore à 1m (BT), dBA 74
Puissance sonore (BT), dBA 85
Puissance sonore avec coque isophonique (BT), dBA 71
Conditions sonores (BT, Températures: Evap./Cond./Aps. -35 / 40 / 20 °C at 50 Hz
avec fréq./vitesse)
climate.emerson.com
Logiciel ver.: 8.15.1.4030
Données: 9,40 / 44938
DONNÉES ÉLECTRIQUES DU COMPRESSEUR (380-420 V / 3~ / 50 Hz)
ACCESSOIRES INCLUS
Suspensions Ressort
CoreSense Protection (-P) Protection Moteur
Pressostat d'huile (-P) Sonde OPS2
Copeland Compressor Electronic (-N) Protection de pression d'huile, de
température de moteur et
refoulement; fonctions avancées de
diagnostic et de mesure
d'alimentation
ACCESSOIRES OPTIONNELS
climate.emerson.com
Logiciel ver.: 8.15.1.4030
Données: 9,40 / 44938
0 2000 4000 6000 V[C.F.M.] 10000
300 1.20
400V
fa 81 fa
[Pa] [in.WG]
200 0.80
400V Y 81 dB(A)
77
150 0.60
77
82
100 0.40
79
50 0.20
0 0.00
0 2000 4000 6000 8000 10000 12000 14000 16000 V[m3/h] 20000
The necessities of the dynamic world of conditioning find the answer in the IC200CX controllers. This series, allows management and
control of chillers, heat pumps and geothermal heat pump units (with solar integration and sanitary hot water production) with
single or dual circuits “gas and water reversibility” and up to 4 steps. By means of a compact instrument, the possibility of controlling
and managing system like:
air/air - “roof top”
air/water
water/water
motor-condensing
PLUS
s 3INGLE CIRCUITCOMPRESSOR STAND BY THROUGH KEY
s ,!. FOR MASTERSLAVE CONNECTION
s #OMBINEDFORCED DEFROSTING
s !LARM CONTROL EVEN IN STAND BY OR REMOTE OFF
s 0UMP DOWN FUNCTION STOP AND START
s 07-M!6 OUTPUT FOR CONDENSING MANAGEMENT
s 4EMPERATUREPRESSURE UNLOADING FUNCTION
s 3CREW COMPRESSOR MANAGEMENT
s #OMPRESSOR ROTATION CONTROL ALSO FROM STARTHOUR NUMBER
s $IRECT PART WINDING STAR DELTA COMPRESSOR START
s $YNAMIC SET POINT
s 'EOTHERMAL FREE COOLING MANAGEMENT
s #OMPRESSOR MANAGEMENT THROUGH INVERTER
s %%6 MANAGEMENT
s 3TART AND STOP BY TIME BANDS FROM 24#
s %NERGY SAVING BY TIME BANDS FROM 24# OR DIGITAL INPUT
s %ASY PROGRAMMING THROUGH (/4 +%9 OR 0# 02/' 4//, +)4
s 44, CONVERTIBLE IN 23 SERIAL OUTPUT WITH -OD"53 PROTOCOL
22
DISPLAY MEANING
ICON
Celsius degrees
Fahrenheit degrees
Bar
PSI
Compressor 1 COMPLETE
The dual display and the icons display complete information about
Compressor 2
the machine status. With a single touch of one key, all main functions
5NIT ON HEAT PUMP STATUS
of the cooling system are displayed without the need to enter
5NIT ON n CHILLER programming mode.
CONNECTIONS
All the controllers of the ICHILL series, have connection for quick wiring.
ALARM MANAGEMENT
The user interface give complete visual information about the plant status and allow the acknowledgement of the alarm events
signals.
Each alarm has a dedicat label Alarm reset protects by password Internal data logger (up to 100 events)
(eg. C1tr: thermal compressor 1 alarm)
CONTROLLED DEVICES
s CIRCUIT COMPRESSOR UP TO STEPS MANAGEMENT
s CIRCUITS COMPRESSOR WITH CAPACITY STAGES MANAGEMENT
s CIRCUITS COMPRESSOR FOR CIRCUIT MANAGEMENT
s -ANAGEMENT OF UP TO EVAPORATOR SECTION AND CONDENSER SECTION WATER PUMPS
s -ANAGEMENT OF UP TO PROPORTIONAL OR /./&& OUTPUTS 6
s CONlGURABLE 6 !58 OUTPUTS
s REMOTE ,%$ KEYBOARD MANAGEMENT
s REMOTE ,#$ 6)3/'2!0( KEYBOARD MANAGEMENT
23
IC206CX
IC208CX
Analogue input for ratiometric pressure transducer PPR30 Analogue input for pressure transducer PP30 (4÷20mA signal)
(0÷5V signal)
PWM output for condensing single-phase fans 0÷10V output for condensing three-phase fans
Proportional outputs configured for aux relay control Proportional outputs configured for damper control (0÷10V)
25
EXAMPLE OF APPLICATION FOR 2 CIRCUIT UP TO 2 COMPRESSOR AIR/WATER CHILLER