Vous êtes sur la page 1sur 4

Révision A A A A A A A A A

T_020 T_020
RESEAU
C
Rég.de N TN 4P4D SJB_3
25 A
300 mA
Tension 400 V
4P
100 A
DISTRIBUTION B

2P1D
Amont TD ZC 02 10 A
B B B B B B
Repère T_020 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A 10 A 10 A

Désignation TN
400 V 10 A 10 A 10 A 10 A 10 A 10 A

I installée 81,19 A
I Totale 107,65 A
Ik3 max 3014 A
Ik1 max 1599 A
L2 L3 L3 L3 L2 L2 L3
Normal Secours
dU max 3,17 %

Repère TD ZC 02 SJB-ECL 03 SJB_3 BD01 LOCAL TGBT ECL-ESC EXT G1 ECL-ESC EXT G2 ECL-ESC EXT F1 ECL-ESC EXT F2 ECL-ESC G1 IH ECL-ESC G2 IH

SJB ECL 03 BOITE DE ECL-ESC EXT ECL-ESC EXT ECL-ESC EXT ECL-ESC EXT ECL-ESC G1 IH ECL-ESC G2 IH
DERIVATION 01 G1 IH G2 IH F1 IH F2 IH
Désignation LOCAL
TECHNIQUE

Nb Consommation 1 45kW 1 1,52kW 0 1 0,2kW 1 0,23kW 1 0,15kW 1 0,23kW 1 0,15kW 1 0,23kW 1 0,15kW

CIRCUIT
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJB_3 SJB_3 SJB_3 SJB_3 SJB_3 SJB_3 SJB_3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 100 m Cu 0m 20 m Cu 90 m Cu 90 m Cu 90 m Cu 90 m Cu 90 m Cu 90 m Cu


L.Max prot. 112 m (CI) 134 m (CC) 134 m (CC) 134 m (CC) 134 m (CC) 134 m (CC) 134 m (CC) 134 m (CC)
dU Circuit dU Totale 2,85 % 3,17 % 0% 3,17 % 0,24 % 3,40 % 1,23 % 4,40 % 0,8 % 3,97 % 1,23 % 4,40 % 0,8 % 3,97 % 1,23 % 4,40 % 0,8 % 3,97 %
Câble 5G25 3G1,5 3G1,5 3G1,5 3G1,5 3G1,5 3G1,5 3G1,5
Neutre
Séparé

LIAISON
PE/PEN
CVS100NA iC60N DT40 DT40 DT40 DT40 DT40 DT40 DT40
Protection
Type AC

Calibre Ir Diff. 100 A 25 A 300 mA 10 A 10 A 10 A 10 A 10 A 10 A 10 A


240 A 50 A 50 A 50 A 50 A 50 A 50 A 50 A

PROT.
Ir Im / Isd
Affectation des phases 123 123 2 3 3 3 2 2 3

NOTE CANECO BT Avis Technique 15L-601


Folio
LOGO A AFFAIRE:
Ind.
34
MODIFICATIONS
Entreprise Unif.Chantier 10 circuits T_020 PLAN: 50
Date : 12/07/2020 Norme : C1510015
Fichier : NOTE CANECO BT PROP_ N°1 BON2.afr ©ALPI Caneco BT 5.71 Authorized user
Révision A A A A A A A A A
T_020 T_020
RESEAU
C
Rég.de N TN SJB_3 4P4D SJB_4
25 A
B B 300 mA B B B B B B
Tension 400 V
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A 10 A 10 A 10 A 10 A
DISTRIBUTION
Amont TD ZC 02 10 A 10 A 10 A 10 A 10 A 10 A 10 A 10 A

Repère T_020

Désignation

I installée 81,19 A
I Totale 107,65 A
Ik3 max 3014 A
Ik1 max 1599 A
L3 L2 L2 L3 L2 L3 L3 L2
Normal Secours
dU max 3,17 %

Repère ECL-ESC F1 IH ECL-ESC F2 IH SJB-ECL 04 SJB_4 ECL-ESC C1 IH ECL-ESC C2 IH ECL- EXT 01 IH ECL-EXT 02 IH ECL-EXT 03 IH ECL-EXT 04 IH

ECL-ESC F1 IH ECL-ESC F2 IH SJB ECL 04 ECL-ESC C1 IH ECL-ESC C2 IH ECL- EXT 01 IH ECL-EXT 02 IH ECL-EXT 03 IH ECL-EXT 04 IH

Désignation

Nb Consommation 1 0,23kW 1 0,15kW 1 1,02kW 0 1 0,16kW 1 0,16kW 1 0,13kW 1 0,13kW 1 0,05kW 1 0,4kW

CIRCUIT
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJB_3 SJB_3 SJB_4 SJB_4 SJB_4 SJB_4 SJB_4 SJB_4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 90 m Cu 90 m Cu 0m 90 m Cu 90 m Cu 90 m Cu 90 m Cu 90 m Cu 90 m Cu
L.Max prot. 134 m (CC) 134 m (CC) 134 m (CC) 134 m (CC) 223 m (CC) 223 m (CC) 223 m (CC) 198 m (DU)
dU Circuit dU Totale 1,23 % 4,40 % 0,8 % 3,97 % 0% 3,17 % 0,85 % 4,02 % 0,85 % 4,02 % 0,42 % 3,58 % 0,42 % 3,58 % 0,16 % 3,33 % 1,28 % 4,45 %
Câble 3G1,5 3G1,5 3G1,5 3G1,5 3G2,5 3G2,5 3G2,5 3G2,5
Neutre
Séparé

LIAISON
PE/PEN
DT40 DT40 iC60N DT40 DT40 DT40 DT40 DT40 DT40
Protection
Type AC

Calibre Ir Diff. 10 A 10 A 25 A 300 mA 10 A 10 A 10 A 10 A 10 A 10 A


50 A 50 A 240 A 50 A 50 A 50 A 50 A 50 A 50 A

PROT.
Ir Im / Isd
Affectation des phases 3 2 123 2 3 2 3 3 2

NOTE CANECO BT Avis Technique 15L-601


Folio
LOGO A AFFAIRE:
Ind.
35
MODIFICATIONS
Entreprise Unif.Chantier 10 circuits T_020 PLAN: 50
Date : 12/07/2020 Norme : C1510015
Fichier : NOTE CANECO BT PROP_ N°1 BON2.afr ©ALPI Caneco BT 5.71 Authorized user
Révision A A A A A A A A A
T_020 T_020
RESEAU
C
Rég.de N TN SJB_4 4P4D
40 A
B B B B 30 mA C B D C
Tension 400 V
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P2D 4P4D
10 A 10 A 10 A 10 A 16 A 16 A 25 A 40 A
DISTRIBUTION 300 mA

Amont TD ZC 02 10 A 10 A 10 A 10 A

Repère T_020

Désignation

I installée 81,19 A
I Totale 107,65 A
Ik3 max 3014 A
Ik1 max 1599 A
L3 L2 L3 L2 L3 L2 L1
Normal Secours
dU max 3,17 %
TAB

Repère ECL-EXT 05 IH ECL-EXT 06 IH ECL-EXT 07 IH RESERVE;:, SJB-PC ZONE COM SJB_10 PC001 RESERVE,;,; ATT - SURP EF CE-AF COMBLE

ECL-EXT 05 IH ECL-EXT 06 IH ECL-EXT 07 IH RESERVE SJB PC 01 PC01 RESERVE ATTENTE COFFRET


ZONE SURPRESSEUR ELECTRIQUE
Désignation COMMUNE EAU FROIDE AILE FILLE
ETAGE
COMBLE
Nb Consommation 1 0,16kW 1 0,16kW 1 0,16kW 1 0,16kW 1 1,4kW 0 1 1,4kW 1 1,4kW 1 4kW 1 7kW

CIRCUIT
Alimentation Normal Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJB_4 SJB_4 SJB_4 SJB_4 SJB_10 SJB_10
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 90 m Cu 90 m Cu 90 m Cu 90 m Cu 0m 30 m Cu 30 m Cu 20 m Cu 54 m Cu
L.Max prot. 223 m (CC) 223 m (CC) 223 m (CC) 223 m (CC) 62 m (CC) 96 m (DU) 86 m (CC) 77 m (CI)
dU Circuit dU Totale 0,51 % 3,68 % 0,51 % 3,68 % 0,51 % 3,68 % 0,51 % 3,68 % 0% 3,17 % 1,5 % 4,67 % 1,5 % 4,67 % 0,73 % 3,90 % 0,57 % 3,74 %
Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G10 5G10
Neutre
Séparé

LIAISON
PE/PEN
DT40 DT40 DT40 DT40 iC60N DT40K DT40 iC60N iC60N
Protection
Type AC Type AC

Calibre Ir Diff. 10 A 10 A 10 A 10 A 40 A 30 mA 16 A 16 A 25 A 300 mA 40 A


50 A 50 A 50 A 50 A 384 A 160 A 80 A 360 A 384 A

PROT.
Ir Im / Isd
Affectation des phases 3 2 3 2 123 3 2 1 123

NOTE CANECO BT Avis Technique 15L-601


Folio
LOGO A AFFAIRE:
Ind.
36
MODIFICATIONS
Entreprise Unif.Chantier 10 circuits T_020 PLAN: 50
Date : 12/07/2020 Norme : C1510015
Fichier : NOTE CANECO BT PROP_ N°1 BON2.afr ©ALPI Caneco BT 5.71 Authorized user
Révision A A A A A A
T_020 T_020
RESEAU
Rég.de N TN
Tension 400 V C C C D D C

4P4D 4P4D 4P4D 4P4D 4P4D 4P4D


40 A 40 A 40 A 32 A 32 A 25 A
DISTRIBUTION
Amont TD ZC 02

Repère T_020

Désignation

I installée 81,19 A
I Totale 107,65 A
Ik3 max 3014 A
Ik1 max 1599 A
Normal Secours
dU max 3,17 %

TAB
TAB
TAB
TAB
TAB
TAB
Repère CE-AG-COMBLE CE-AF-E4 CE-AG-E4 CE-HEBERGEME CE-INFIRMERIE CE-GUERITE

COFFRET COFFRET COFFRET COFFRET COFFRET COFFRET


ELECTRIQUE ELECTRIQUE ELECTRIQUE ELECTRIQUE ELECTRIQUE ELECTRIQUE
Désignation AILE GARCON AILE FILLE AILE GARCON HEBERGEMENT INFIRMERIE GUERITE
ETAGE ETAGE 4 ETAGE 4
COMBLE
Nb Consommation 1 7kW 1 7,5kW 1 7,5kW 1 6kW 1 14kW 1 1kW

CIRCUIT
Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 54 m Cu 48 m Cu 48 m Cu 30 m Cu 40 m Cu 50 m Cu
L.Max prot. 77 m (CI) 77 m (CI) 77 m (CI) 34 m (CI) 57 m (CI) 60 m (CI)
dU Circuit dU Totale 0,57 % 3,74 % 0,55 % 3,71 % 0,55 % 3,71 % 0,45 % 3,62 % 0,85 % 4,02 % 0,19 % 3,35 %
Câble 5G10 5G10 5G10 5G6 5G10 5G4
Neutre
Séparé

LIAISON
PE/PEN
iC60N iC60N iC60N iC60N iC60N iC60N
Protection

Calibre Ir Diff. 40 A 40 A 40 A 32 A 32 A 25 A
384 A 384 A 384 A 460,8 A 460,8 A 240 A

PROT.
Ir Im / Isd
Affectation des phases 123 123 123 123 123 123

NOTE CANECO BT Avis Technique 15L-601


Folio
LOGO A AFFAIRE:
Ind.
37
MODIFICATIONS
Entreprise Unif.Chantier 10 circuits T_020 PLAN: 50
Date : 12/07/2020 Norme : C1510015
Fichier : NOTE CANECO BT PROP_ N°1 BON2.afr ©ALPI Caneco BT 5.71 Authorized user

Vous aimerez peut-être aussi