Révision 1 1 1 1 1 1 1

T1.1.HJN T1.1.HJN
RESEAU
C
Rég.de N TN 4P3D
25 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


25 A 25 A 25 A 25 A 25 A 25 A
DISTRIBUTION
Normal TG.N-3HJ_T5
Amont
Secours

Repère T1.1.HJN
Désignation
TAB.ELEC T1.1.HJN

Normal Secours

I Totale 149,75 A

I installée 126,79 A

Ik3 max 17294 A


L2 L3 L3 L2 L3 L2
Ik1 max 10461 A

DU max 3,17 %

Repère SJDB8 T1.1.HJN_A10 T1.1.HJN_A11 T1.1.HJN_A12 T1.1.HJN_A13 T1.1.HJN_A14 T1.1.HJN_A15 T1.1.HJN_J009


ALIM. CEN-INS ALIM. CEN-INS ALIM. CEN-INS ALIM. CEN-INS ALIM. CEN-INS ALIM. CEN-INS JDB ALIM OSMOS
LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE
Désignation SUPPORT SUPPORT SUPPORT SUPPORT SUPPORT SUPPORT
CIRCUIT

Nb Consommation 0 1 3850W 1 3850W 1 3850W 1 3850W 1 3850W 1 3850W 1 1,6kVA


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB8 SJDB8 SJDB8 SJDB8 SJDB8 SJDB8
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 24 m Cu 36 m Cu 38 m Cu 28 m Cu 22 m Cu 20 m Cu
L.Max prot. 55 m (DU) 55 m (DU) 55 m (DU) 55 m (DU) 55 m (DU) 55 m (DU)

DU Circuit DU Totale 2,08 % 5,25 % 3,12 % 6,29 % 3,3 % 6,47 % 2,43 % 5,60 % 1,9 % 5,08 % 1,73 % 4,90 % 0% 3,17 %
LIAISON

Câble 3G4 3G4 3G4 3G4 3G4 3G4


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40 DT40 DT40 DT40 DT40 DT40 DT40N Type AC
Protection
PROT.

Calibre IDn 25 A 25 A 25 A 25 A 25 A 25 A 25 A 30 mA
Ir Im / Isd 250 A 250 A 250 A 250 A 250 A 250 A 250 A
Affectation des phases 2 3 3 2 3 2 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.1.HJN 150
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.1.HJN T1.1.HJN
RESEAU
C
Rég.de N TN 2P1D
16 A
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T5
Amont
Secours

Repère T1.1.HJN
Désignation
TAB.ELEC T1.1.HJN

Normal Secours

I Totale 149,75 A

I installée 126,79 A

Ik3 max 17294 A


L1 L3 L2 L1 L3 L2 L2
Ik1 max 10461 A

DU max 3,17 %

Repère SJDB9 T1.1.HJN_A04 T1.1.HJN_A05 T1.1.HJN_A06 T1.1.HJN_A07 T1.1.HJN_A08 T1.1.HJN_A09 T1.1.HJN_A01


ALIM OSMOS ALIM OSMOS ALIM OSMOS ALIM OSMOS ALIM OSMOS ALIM OSMOS ALIM. CAPTEUR
LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE LOCAUX DE TEMP QUALITE AIR
Désignation SUPPORT SUPPORT SUPPORT SUPPORT SUPPORT SUPPORT
CIRCUIT

Nb Consommation 0 1 40W 1 40W 1 40W 1 40W 1 40W 1 40W 2 30W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB9 SJDB9 SJDB9 SJDB9 SJDB9 SJDB9
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 24 m Cu 36 m Cu 39 m Cu 27 m Cu 21 m Cu 20 m Cu 70 m Cu
L.Max prot. 74 m (CC) 74 m (CC) 74 m (CC) 74 m (CC) 74 m (CC) 74 m (CC) 74 m (CI)

DU Circuit DU Totale 0,03 % 3,21 % 0,05 % 3,22 % 0,06 % 3,23 % 0,04 % 3,21 % 0,03 % 3,20 % 0,03 % 3,20 % 0,11 % 3,29 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 1 3 2 1 3 2 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.1.HJN 151
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.1.HJN T1.1.HJN
RESEAU
C C C C C C C C
Rég.de N TN 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T5
Amont
Secours

Repère T1.1.HJN
Désignation
TAB.ELEC T1.1.HJN

Normal Secours

I Totale 149,75 A

I installée 126,79 A

Ik3 max 17294 A


L1 L2 L3 L3 L2 L2 L3 L1
Ik1 max 10461 A

DU max 3,17 %

Repère T1.1.HJN_A02 T1.1.HJN_A03 T1.1.HJN_A16 T1.1.HJN_A17 T1.1.HJN_A18 T1.1.HJN_A19 T1.1.HJN_A20 T1.1.HJN_A21


ALIM. CAPTEUR ALIM. CAPTEUR ALIM. VRV ALIM. VRV PETITE ALIM. VR LAB CIAM. ALIM. VR LAB CIAM. ALIM. VR LAB CIAM. ALIM. VR LAB CIAM.
TEMP QUALITE AIR TEMP QUALITE AIR EPIDEMIOLOGY SALLE DE REUNION
Désignation COMPUTER LAB
CIRCUIT

Nb Consommation 4 30W 2 30W 1 280W 1 220W 4 300W 3 300W 3 300W 2 300W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 70 m Cu 70 m Cu 30 m Cu 21 m Cu 30 m Cu 31 m Cu 38 m Cu 46 m Cu
L.Max prot. 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI)

DU Circuit DU Totale 0,23 % 3,40 % 0,11 % 3,29 % 0,3 % 3,47 % 0,17 % 3,34 % 1,22 % 4,40 % 0,98 % 4,16 % 1,21 % 4,38 % 0,99 % 4,16 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 1 2 3 3 2 2 3 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.1.HJN 152
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1
T1.1.HJN T1.1.HJN
RESEAU
C C C C
Rég.de N TN 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T5
Amont
Secours

Repère T1.1.HJN
Désignation
TAB.ELEC T1.1.HJN

Normal Secours

I Totale 149,75 A

I installée 126,79 A

Ik3 max 17294 A


L1 L1 L3 L2
Ik1 max 10461 A

DU max 3,17 %

Repère T1.1.HJN_A22 T1.1.HJN_A23 T1.1.HJN_A24 T1.1.HJN_A25


ALIM. VR LAB CIAM. ALIM. VR LAB CIAM. ALIM. VR ALIM. VR
EPIDEMIOLOGY LAB EPIDEMIOLOGY LAB
Désignation
CIRCUIT

Nb Consommation 3 300W 2 300W 3 300W 3 300W


Alimentation Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 29 m Cu 26 m Cu 33 m Cu 38 m Cu
L.Max prot. 74 m (CI) 74 m (CI) 74 m (CI) 74 m (CI)

DU Circuit DU Totale 0,92 % 4,09 % 0,56 % 3,73 % 1,05 % 4,22 % 1,21 % 4,38 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40T iDT40T iDT40T iDT40T
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 1 1 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.1.HJN 153
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN 3P 4P3D SJDB1
160 A 25 A
30 mA
Tension 400 V C C C C

2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont L
Secours P.T.

Repère T1.2.HJN TN
Désignation 400 V
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L1 L1 L3 L3
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_BS001 TG.N-3HJ_T6 T1.2.HJN_J001 SJDB1 T1.2.HJN_PN25 T1.2.HJN_PN26 T1.2.HJN_PN27 T1.2.HJN_PN28


Voyant présence TAB.ELEC T1.2.HJN JDB PC PC. N HVAC PC. N SALLE DE REU PC. N SALLE DE PC. N S DE REUN ET
tension ET CONFER REUN ET CONFER DE CONFER
Désignation
CIRCUIT

Nb Consommation 1 1 76kW 1 7kVA 0 5 250W 8 250W 8 250W 7 250W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 34 m Cu 0m 25 m Cu 32 m Cu 28 m Cu 37 m Cu
L.Max prot. 62 m (DU) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 0,66 % 3,45 % 0% 3,45 % 0,92 % 4,37 % 1,9 % 5,35 % 1,83 % 5,28 % 2,07 % 5,52 %
LIAISON

Câble 2x1,5 3X(1x70) 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN 1x70
Taux d'Harmonique TH <= 15% TH <= 15%
NSXm160NA DT40N Type AC DT40K DT40K DT40K DT40K
Protection
PROT.

Calibre IDn 160 A 25 A 30 mA 16 A 16 A 16 A 16 A


Ir Im / Isd 250 A 160 A 160 A 160 A 160 A
Affectation des phases 123 123 1 1 3 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 154
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 2 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB1 4P3D SJDB2
32 A
30 mA
Tension 400 V C C C C C C
-D5 -D6 -D7 -D8 -D9 -D10
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L3 L2 L2 L3 L1 L3
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PN29 T1.2.HJN_PN30 T1.2.HJN_PN31 T1.2.HJN_J002 SJDB2 T1.2.HJN_PN32 T1.2.HJN_PN33 T1.2.HJN_PN34


PC. N S DE REU ET PC. N S DE REU ET PC.N S DE REU ET JDB PC PC.N S DE REU ET DE PC.N SPECTRO PC.N WORK R
CONFER DE CONFER DE CONFER CONFER LAB+WORK R COPIER+SAMPLE
Désignation COPIER PREP
CIRCUIT

Nb Consommation 8 250W 8 250W 6 250W 1 7kVA 0 8 250W 8 250W 9 250W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 32 m Cu 39 m Cu 35 m Cu 0m 42 m Cu 44 m Cu 28 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 2,11 % 5,56 % 2,58 % 6,03 % 1,61 % 5,06 % 0% 3,45 % 2,8 % 6,25 % 2,87 % 6,32 % 2,02 % 5,46 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40N Type AC DT40K DT40K DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 32 A 30 mA 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 320 A 160 A 160 A 160 A
Affectation des phases 3 2 2 123 3 1 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 155
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB2 4P3D SJDB3
25 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L2 L2 L1 L1 L1 L3
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PN35 T1.2.HJN_PN36 T1.2.HJN_PN37 T1.2.HJN_PN38 T1.2.HJN_J003 SJDB3 T1.2.HJN_PN39 T1.2.HJN_PN40


PC.N SAMPLE PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO LAB JDB PC PC.N SPECTRO LAB PC.N SPECTRO LAB
RECEIPT+HYDRO
Désignation LAB
CIRCUIT

Nb Consommation 8 250W 7 250W 6 250W 7 250W 1 7kVA 0 7 250W 7 250W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB2 SJDB2 SJDB2 SJDB2 SJDB3 SJDB3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 24 m Cu 42 m Cu 47 m Cu 49 m Cu 0m 47 m Cu 47 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 0% 3,45 % 2,83 % 6,27 % 2,83 % 6,27 %


LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40K DT40N Type AC DT40K DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 25 A 30 mA 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 160 A 250 A 160 A 160 A
Affectation des phases 2 2 1 1 123 1 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 156
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB3 4P3D SJDB4
25 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 32 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L1 L2 L2 L1 L2 L1
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PN41 T1.2.HJN_PN42 T1.2.HJN_PN43 T1.2.HJN_PN44 T1.2.HJN_PN45 T1.2.HJN_J004 SJDB4 T1.2.HJN_PN46


PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO JDB PC PC.N HYDRO LAB
LAB+SAMPLE PREP
Désignation
CIRCUIT

Nb Consommation 6 250W 7 250W 7 250W 8 93,8W 8 250W 1 7kVA 0 6 250W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB3 SJDB3 SJDB3 SJDB3 SJDB3 SJDB4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 52 m Cu 50 m Cu 50 m Cu 62 m Cu 43 m Cu 0m 52 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 82 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 2,69 % 6,14 % 3,01 % 6,46 % 3,01 % 6,46 % 0,8 % 4,25 % 2,91 % 6,36 % 0% 3,45 % 2,72 % 6,17 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G6 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40K DT40K DT40N Type AC DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 32 A 16 A 25 A 30 mA 16 A
Ir Im / Isd 160 A 160 A 160 A 320 A 160 A 250 A 160 A
Affectation des phases 1 2 2 1 2 123 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 157
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB4 4P3D
25 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L3 L3 L2 L2 L1 L1
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PN52 T1.2.HJN_PN51 T1.2.HJN_PN49 T1.2.HJN_PN48 T1.2.HJN_PN50 T1.2.HJN_PN47 T1.2.HJN_J005 SJDB5


PC.N LABO INFORM PC.N HYDRO PC.N HYDRO LAB PC.N HYDRO LAB PC.N HYDRO PC.N HYDRO LAB JDB PC
LAB+LABO INFORM LAB+LABO INFORMA
Désignation
CIRCUIT

Nb Consommation 6 250W 8 250W 8 250W 5 250W 8 250W 8 250W 1 7kVA 0


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB4 SJDB4 SJDB4 SJDB4 SJDB4 SJDB4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 37 m Cu 32 m Cu 37 m Cu 32 m Cu 33 m Cu 40 m Cu 0m
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 1,75 % 5,20 % 2,01 % 5,46 % 2,51 % 5,96 % 1,39 % 4,84 % 2,08 % 5,53 % 2,65 % 6,10 % 0% 3,45 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40K DT40K DT40K DT40N Type AC
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 25 A 30 mA
Ir Im / Isd 160 A 160 A 160 A 160 A 160 A 160 A 250 A
Affectation des phases 3 3 2 2 1 1 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 158
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB5 4P3D SJDB6
32 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 4P3D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L3 L2 L2 L3 L3
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PN57 T1.2.HJN_PN56 T1.2.HJN_PN53 T1.2.HJN_PN55 T1.2.HJN_PN54 T1.2.HJN_J006 SJDB6 T1.2.HJN_PS01


PC.N SANIATAIRES PC.N S DE REUN ET PC.N LABO INFOR PC.N S DE REU ET PC.N HYDRO JDB PC PC.N SAMPLE
CONFER CONFER LAB+LAB INFO+S PREPAR
Désignation LIBRARY
CIRCUIT

Nb Consommation 4 250W 5 250W 8 250W 5 250W 7 250W 1 12kVA 0 1 1500W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB5 SJDB5 SJDB5 SJDB5 SJDB5 SJDB6
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 9m Cu 28 m Cu 35 m Cu 28 m Cu 25 m Cu 0m 23 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 73 m (CC)

DU Circuit DU Totale 0,25 % 3,70 % 1,19 % 4,64 % 2,19 % 5,63 % 1,19 % 4,64 % 1,32 % 4,76 % 0% 3,45 % 0,21 % 3,66 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 5G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
DT40K DT40K DT40K DT40K DT40K DT40N Type AC iDT40N
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 32 A 30 mA 16 A
Ir Im / Isd 160 A 160 A 160 A 160 A 160 A 320 A 153,6 A
Affectation des phases 3 2 2 3 3 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 159
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB6 4P3D SJDB7
32 A
30 mA
Tension 400 V C C C C C C

4P3D 4P3D 4P3D 4P3D 4P3D 4P3D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A

Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PS02 T1.2.HJN_PS03 T1.2.HJN_PS04 T1.2.HJN_PS05 T1.2.HJN_PS06 T1.2.HJN_J007 SJDB7 T1.2.HJN_PS07


PC.N HYDRO LAB PC.N HYDRO LAB PC.N HYDRO LAB PC.N HYDRO LAB PC.N SPECTRO LAB JDB PC PC.N SPECTRO LAB

Désignation
CIRCUIT

Nb Consommation 1 1500W 1 1500W 1 1500W 1 1500W 1 1500W 1 12kVA 0 1 1500W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB6 SJDB6 SJDB6 SJDB6 SJDB6 SJDB7
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 36 m Cu 28 m Cu 33 m Cu 50 m Cu 48 m Cu 0m 37 m Cu
L.Max prot. 73 m (CC) 73 m (CC) 73 m (CC) 73 m (CC) 73 m (CC) 73 m (CC)

DU Circuit DU Totale 0,32 % 3,77 % 0,25 % 3,70 % 0,3 % 3,74 % 0,45 % 3,90 % 0,43 % 3,88 % 0% 3,45 % 0,33 % 3,78 %
LIAISON

Câble 5G2,5 5G2,5 5G2,5 5G2,5 5G2,5 5G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
iDT40N iDT40N iDT40N iDT40N iDT40N DT40N Type AC iDT40N
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 32 A 30 mA 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 320 A 153,6 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 160
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C
Rég.de N TN SJDB7 4P3D SJDB8
32 A
30 mA
Tension 400 V C C C C C C
-D56
4P3D 4P3D 4P3D 4P3D 2P1D 2P1D
16 A 16 A 16 A 16 A 25 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L1 L2
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_PS08 T1.2.HJN_PS09 T1.2.HJN_PS10 T1.2.HJN_PS11 T1.2.HJN_J008 SJDB8 T1.2.HJN_A05 T1.2.HJN_A06


PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO LAB PC.N SPECTRO LAB JDB ALIM CEN-INS ALIM. CEN-INS ALIM. OSMOS
SAMPLE SAMPLE RECEIPT
Désignation PREPARATION
CIRCUIT

Nb Consommation 1 1500W 1 1500W 1 1500W 1 1500W 1 10kVA 0 1 3850W 1 40W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB7 SJDB7 SJDB7 SJDB7 SJDB8 SJDB8
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 46 m Cu 48 m Cu 48 m Cu 43 m Cu 0m 26 m Cu 22 m Cu
L.Max prot. 73 m (CC) 73 m (CC) 73 m (CC) 73 m (CC) 52 m (DU) 70 m (CC)

DU Circuit DU Totale 0,41 % 3,86 % 0,43 % 3,88 % 0,43 % 3,88 % 0,38 % 3,83 % 0% 3,45 % 2,25 % 5,70 % 0,03 % 3,48 %
LIAISON

Câble 5G2,5 5G2,5 5G2,5 5G2,5 3G4 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
iDT40N iDT40N iDT40N iDT40N DT40N Type AC DT40 DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 32 A 30 mA 25 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 320 A 250 A 160 A
Affectation des phases 123 123 123 123 123 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 161
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 2 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C C C C C C
Rég.de N TN -D61 -D62 -D63 -D64
SJDB8 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
30 mA 30 mA
Tension 400 V C C
-D60 -D59
2P1D 2P1D
16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L2 L2 L2 L1 L3 L1 L1 L2
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_A08 T1.2.HJN_A07 T1.2.HJN_A09 T1.2.HJN_A10 T1.2.HJN_A11 T1.2.HJN_A12 T1.2.HJN_A13 T1.2.HJN_A14


ALIM. OSMOS ALIM. OSMOS ALIM. VRV ALIM. VRV ALIM. VRV ALIM. CE.ACC ALIM. SM SANITAIRES ALIM. VR
SAMPLE SAMPLE S.REUNION ET S.REUNION ET S.REUNION ET SANITAIRES SPECTROSCOPY LAB
Désignation PREPARATION PREPARATION CONFERENCE CONFERENCE CONFERENCE
CIRCUIT

Nb Consommation 1 40W 1 40W 1 280W 1 110W 1 100W 1 2200W 1 2000W 2 300W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB8 SJDB8
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 21 m Cu 26 m Cu 27 m Cu 20 m Cu 23 m Cu 9m Cu 8m Cu 44 m Cu
L.Max prot. 113 m (CC) 70 m (CC) 73 m (CI) 73 m (CI) 73 m (CI) 91 m (DU) 63 m (DU) 73 m (CI)

DU Circuit DU Totale 0,02 % 3,47 % 0,04 % 3,49 % 0,27 % 3,72 % 0,08 % 3,53 % 0,08 % 3,53 % 0,44 % 3,89 % 0,57 % 4,02 % 0,95 % 4,39 %
LIAISON

Câble 3G4 3G2,5 3G2,5 3G2,5 3G2,5 3G4 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
DT40K DT40K iDT40T iDT40T iDT40T DT40 Type AC DT40 Type AC iDT40T
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 30 mA 16 A 30 mA 16 A
Ir Im / Isd 160 A 160 A 153,6 A 153,6 A 153,6 A 160 A 160 A 153,6 A
Affectation des phases 2 2 2 1 3 1 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 162
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C C C C C C C C
Rég.de N TN -D73 -D74
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A 16 A 40 A
30 mA
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L2 L3 L1 L3 L3 L1 L2 L2
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_A15 T1.2.HJN_A16 T1.2.HJN_A17 T1.2.HJN_A18 T1.2.HJN_A19 T1.2.HJN_A20 T1.2.HJN_A21 T1.2.HJN_A22


ALIM. VR ALIM. VR ALIM. VR HYDRO LAB ALIM. VR ALIM. VR ALIM. VR S.REUNION ALIM. VR S.REUNION ALIM. OVN SAMPLES
SPECTROSCOPY LAB SPECTROSCOPY LAB LABORATOIR LABORATOIR ET CONFERENCE ET CONFERENCE PREPARATION
Désignation INFORMATIQUE INFORMATIQUE
CIRCUIT

Nb Consommation 4 300W 3 300W 3 300W 2 300W 4 300W 3 300W 3 300W 1 7000W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 32 m Cu 40 m Cu 30 m Cu 25 m Cu 28 m Cu 35 m Cu 34 m Cu 29 m Cu
L.Max prot. 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 71 m (DU)

DU Circuit DU Totale 1,33 % 4,78 % 1,27 % 4,72 % 0,95 % 4,40 % 0,53 % 3,98 % 1,14 % 4,59 % 1,1 % 4,54 % 1,08 % 4,53 % 1,85 % 5,30 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G10


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T DT40 Type AC
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 16 A 40 A 30 mA
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 400 A
Affectation des phases 2 3 1 3 3 1 2 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 163
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.2.HJN T1.2.HJN
RESEAU
C C C C C C C C
Rég.de N TN -D75 -D76 -D77 -D78 -D79 -D80 -D81 -D82
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
40 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T6
Amont
Secours

Repère T1.2.HJN
Désignation
TAB.ELEC T1.2.HJN

Normal Secours

I Totale 137,12 A

I installée 132,95 A

Ik3 max 13569 A


L3 L3 L1 L1 L3 L2 L1 L3
Ik1 max 7772 A

DU max 3,45 %

Repère T1.2.HJN_A23 T1.2.HJN_A25 T1.2.HJN_A26 T1.2.HJN_A27 T1.2.HJN_F1 T1.2.HJN_F2 T1.2.HJN_F3 T1.2.HJN_F4


ALIM. OVN SAMPLES ALIM. CAPTEUR ALIM. CAPTEUR ALIM. CAPTEUR ALIM. VAV ALIM. VAV SAMPLE ALIM. VAV SAMPLE ALIM. VAV SAMPLE
PREPARATION TEMP QUALITE AIR TEMP QUALITE AIR TEMP QUALITE AIR SPECTROSCOPY LAB PRAPARATION RECEIPT LIBRARY
Désignation
CIRCUIT

Nb Consommation 1 7000W 3 30W 3 30W 3 30W 8 44W 8 41,3W 8 39,9W 4 38,5W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 27 m Cu 70 m Cu 70 m Cu 70 m Cu 42 m Cu 30 m Cu 23 m Cu 18 m Cu
L.Max prot. 71 m (DU) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI) 73 m (CI)

DU Circuit DU Totale 1,72 % 5,17 % 0,17 % 3,62 % 0,17 % 3,62 % 0,17 % 3,62 % 0,5 % 3,95 % 0,34 % 3,79 % 0,25 % 3,69 % 0,09 % 3,54 %
LIAISON

Câble 3G10 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T iDT40T
Protection
PROT.

Calibre IDn 40 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 384 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 3 3 1 1 3 2 1 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.2.HJN 164
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
T1.3.HJN T1.3.HJN
RESEAU
C
Rég.de N TN 3P 4P3D SJDB1
32 A 25 A
30 mA
Tension 400 V C C C C
-PRO|263 -PRO|331
2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T7
Amont L
Secours P.T.

Repère T1.3.HJN TN
Désignation 400 V
TAB.ELEC T1.3.HJN

Normal Secours

I Totale 25,26 A

I installée 41,72 A

Ik3 max 3686 A


L2 L1 L1 L3
Ik1 max 1879 A

DU max 3,52 %

Repère T1.3.HJN_BS001 TG.N-3HJ_T7 T1.3.HJN_J001 SJDB1 T1.3.HJN_PO13 T1.3.HJN_PN21 T1.3.HJN_PN22 T1.3.HJN_PN23


Voyant présence TAB.ELEC T1.3.HJN JDB PC PC.O PC.N BUR VISISTEUR PC.N BUR VISISTEUR PC.O BUR VISISTEUR
tension CIRCULAT+DEPOT,AR
Désignation CHIVES
CIRCUIT

Nb Consommation 1 1 14kW 1 7kVA 0 8 250W 6 250W 8 250W 8 250W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 54 m Cu 0m 22 m Cu 40 m Cu 59 m Cu 41 m Cu
L.Max prot. 89 m (DU) 66 m (CC) 66 m (CC) 66 m (CC) 66 m (CC)

DU Circuit DU Totale 0,73 % 3,52 % 0% 3,52 % 1,07 % 4,60 % 1,93 % 5,46 % 3,77 % 7,29 % 2,69 % 6,21 %
LIAISON

Câble 2x1,5 4G16 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
INFC 32 10x38 DT40N Type AC iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 32 A 25 A 30 mA 16 A 16 A 16 A 16 A
Ir Im / Isd 250 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 123 123 2 1 1 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.3.HJN 165
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.3.HJN T1.3.HJN
RESEAU
C
Rég.de N TN SJDB1 4P3D SJDB2
25 A
30 mA
Tension 400 V C C C C C C
-PRO|334 -PRO|337
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T7
Amont
Secours

Repère T1.3.HJN
Désignation
TAB.ELEC T1.3.HJN

Normal Secours

I Totale 25,26 A

I installée 41,72 A

Ik3 max 3686 A


L1 L3 L3 L2 L3 L2
Ik1 max 1879 A

DU max 3,52 %

Repère T1.3.HJN_PN24 T1.3.HJN_PN25 T1.3.HJN_PN26 T1.3.HJN_PN27 T1.3.HJN_J002 SJDB2 T1.3.HJN_PN28 T1.3.HJN_PN29


PC.N BUR VISISTEUR PC.N BUR VISISTEUR PC.N BUR VISISTEUR PC.N BUR DE JDB PC PC.N BUR DE DIRECT PC.N BUR DE DIRECT
DIRECT+CIRCUL
Désignation
CIRCUIT

Nb Consommation 8 250W 8 250W 5 250W 7 250W 1 7kVA 0 8 250W 8 250W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 44 m Cu 44 m Cu 41 m Cu 44 m Cu 0m 46 m Cu 47 m Cu
L.Max prot. 66 m (CC) 66 m (CC) 66 m (CC) 66 m (CC) 66 m (CC) 66 m (CC)

DU Circuit DU Totale 2,91 % 6,43 % 2,91 % 6,43 % 1,68 % 5,20 % 2,51 % 6,03 % 0% 3,52 % 3,01 % 6,54 % 2,94 % 6,46 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K iDT40K iDT40K iDT40K DT40N Type AC iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 25 A 30 mA 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 250 A 153,6 A 153,6 A
Affectation des phases 1 3 3 2 123 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.3.HJN 166
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.3.HJN T1.3.HJN
RESEAU
C C
Rég.de N TN SJDB2 2P1D 2P1D
16 A 16 A
Tension 400 V C C C C C C
-PRO|346 -PRO|350
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T7
Amont
Secours

Repère T1.3.HJN
Désignation
TAB.ELEC T1.3.HJN

Normal Secours

I Totale 25,26 A

I installée 41,72 A

Ik3 max 3686 A


L1 L2 L3 L1 L2 L1 L2 L2
Ik1 max 1879 A

DU max 3,52 %

Repère T1.3.HJN_PN30 T1.3.HJN_PN31 T1.3.HJN_PN32 T1.3.HJN_PN33 T1.3.HJN_PN34 T1.3.HJN_PN35 T1.3.HJN_A01 T1.3.HJN_A02


PC.N BUR DE DIRECT PC.N BUR PC.N BUR PROFESS PC.N TERASSE PC.N PC.N CIRCULAT ALIM. VRV BUREAUX ALIM. VRV BUREAUX
CHERCHEU CIRCULAT+DEPOT,AR VISITEURS VISITEURS
Désignation CHIVES
CIRCUIT

Nb Consommation 8 250W 8 250W 8 250W 6 250W 5 250W 6 200W 1 280W 1 280W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 41 m Cu 38 m Cu 35 m Cu 76 m Cu 22 m Cu 22 m Cu 29 m Cu 34 m Cu
L.Max prot. 66 m (CC) 66 m (CC) 66 m (CC) 106 m (CC) 66 m (CC) 66 m (CC) 66 m (CI) 66 m (CI)

DU Circuit DU Totale 2,62 % 6,14 % 2,44 % 5,96 % 2,08 % 5,60 % 2,02 % 5,54 % 0,8 % 4,33 % 0,77 % 4,30 % 0,29 % 3,81 % 0,34 % 3,86 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G4 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 1 2 3 1 2 1 2 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.3.HJN 167
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.3.HJN T1.3.HJN
RESEAU
C C C C C C C C
Rég.de N TN 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T7
Amont
Secours

Repère T1.3.HJN
Désignation
TAB.ELEC T1.3.HJN

Normal Secours

I Totale 25,26 A

I installée 41,72 A

Ik3 max 3686 A


L2 L1 L1 L1 L1 L2 L3 L3
Ik1 max 1879 A

DU max 3,52 %

Repère T1.3.HJN_A03 T1.3.HJN_A04 T1.3.HJN_A05 T1.3.HJN_A06 T1.3.HJN_A07 T1.3.HJN_A08 T1.3.HJN_A09 T1.3.HJN_A10


ALIM. VRV BUREAUX ALIM. VRV BUREAUX ALIM. VRV BUREAUX ALIM. VRV BUREAU ALIM. VRV BUREAU ALIM. VRV DEPOTS ALIM. VR BUREAU ALIM. VR BUREAU
DE DIRECTION DE DIRECTION DE DIRECTION RECEPTION RECEPTION ARCHIVES VISITEUR VISITEUR
Désignation
CIRCUIT

Nb Consommation 1 100W 1 110W 1 100W 1 110W 1 110W 1 40W 3 300W 3 300W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 32 m Cu 37 m Cu 29 m Cu 26 m Cu 19 m Cu 17 m Cu 41 m Cu 42 m Cu
L.Max prot. 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI)

DU Circuit DU Totale 0,11 % 3,64 % 0,15 % 3,67 % 0,1 % 3,63 % 0,1 % 3,62 % 0,07 % 3,60 % 0,02 % 3,55 % 1,29 % 4,81 % 1,34 % 4,86 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 2 1 1 1 1 2 3 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.3.HJN 168
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1
T1.3.HJN T1.3.HJN
RESEAU
C C C C
Rég.de N TN 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T7
Amont
Secours

Repère T1.3.HJN
Désignation
TAB.ELEC T1.3.HJN

Normal Secours

I Totale 25,26 A

I installée 41,72 A

Ik3 max 3686 A


L2 L1 L1 L2
Ik1 max 1879 A

DU max 3,52 %

Repère T1.3.HJN_A11 T1.3.HJN_A12 T1.3.HJN_A13 T1.3.HJN_A14


ALIM. VR BUREAUX ALIM. VR BUREAU ALIM. CAPTEUR ALIM. CAPTEUR
DE DIRECTION PROFESSEURS TEMP QUALITE AIR TEMP QUALITE AIR
Désignation
CIRCUIT

Nb Consommation 4 300W 1 300W 2 30W 3 30W


Alimentation Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 41 m Cu 21 m Cu 66 m Cu 66 m Cu
L.Max prot. 66 m (CI) 66 m (CI) 66 m (CI) 66 m (CI)

DU Circuit DU Totale 1,72 % 5,24 % 0,23 % 3,75 % 0,11 % 3,63 % 0,16 % 3,69 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 2 1 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.3.HJN 169
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
T1.4.HJN T1.4.HJN
RESEAU
C
Rég.de N TN 3P 4P3D SJDB1
32 A 25 A
30 mA
Tension 400 V C C C C
-PRO|355 -PRO|357 -PRO|359 -PRO|361
2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T8
Amont L
Secours P.T.

Repère T1.4.HJN TN
Désignation 400 V
TAB.ELEC T1.4.HJN

Normal Secours

I Totale 23,45 A

I installée 27,82 A

Ik3 max 4096 A


L3 L2 L1 L1
Ik1 max 2093 A

DU max 3,40 %

Repère T1.4.HJN_BS001 TG.N-3HJ_T8 T1.4.HJN_J001 SJDB1 T1.4.HJN_PN15 T1.4.HJN_PN16 T1.4.HJN_PN17 T1.4.HJN_PN18


Voyant présence TAB.ELEC T1.4.HJN JDB PC PC.N CFA+LOCAL PC.N LOCAL PC.N BUR PARTAG PC.O BUR
tension TECHNIQUE TECHNIQUE PARTAG+CIRCUL
Désignation
CIRCUIT

Nb Consommation 1 1 13kW 1 7kVA 0 9 250W 8 250W 8 250W 7 250W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 48 m Cu 0m 13 m Cu 31 m Cu 24 m Cu 31 m Cu
L.Max prot. 96 m (DU) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,6 % 3,40 % 0% 3,40 % 0,68 % 4,08 % 1,97 % 5,37 % 1,32 % 4,72 % 1,66 % 5,06 %
LIAISON

Câble 2x1,5 4G16 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
INFC 32 10x38 DT40N Type AC iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 32 A 25 A 30 mA 16 A 16 A 16 A 16 A
Ir Im / Isd 250 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 123 123 3 2 1 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.4.HJN 170
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T1.4.HJN T1.4.HJN
RESEAU
C C
Rég.de N TN SJDB1 4P3D 2P1D
25 A 16 A
30 mA
Tension 400 V C C C C C
-PRO|362
2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T8
Amont
Secours

Repère T1.4.HJN
Désignation
TAB.ELEC T1.4.HJN

Normal Secours

I Totale 23,45 A

I installée 27,82 A

Ik3 max 4096 A


L2 L2 L3 L3 L3 L2
Ik1 max 2093 A

DU max 3,40 %

Repère T1.4.HJN_PN19 T1.4.HJN_J002 SJDB2 T1.4.HJN_PN20 T1.4.HJN_PN23 T1.4.HJN_PN21 T1.4.HJN_PN22 T1.4.HJN_A01


PC.N BUR PARTAG JDB PC PC.N BUR PARTAG PC.N SANITAIRES PC.N TERASSE PC.N BUR PARTAG ALIM. VR ESPACES
COLLABORATIFS
Désignation
CIRCUIT

Nb Consommation 6 250W 1 7kVA 0 8 250W 4 250W 6 250W 7 250W 3 300W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB2 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 35 m Cu 0m 28 m Cu 9m Cu 66 m Cu 42 m Cu 28 m Cu
L.Max prot. 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CI)

DU Circuit DU Totale 1,61 % 5,01 % 0% 3,40 % 1,79 % 5,19 % 0,21 % 3,61 % 2,66 % 6,05 % 2,23 % 5,62 % 0,89 % 4,28 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K DT40N Type AC iDT40K iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 25 A 30 mA 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 250 A 153,6 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 2 123 2 3 3 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.4.HJN 171
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T1.4.HJN T1.4.HJN
RESEAU
C C C C C C C C
Rég.de N TN 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
30 mA 30 mA
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T8
Amont
Secours

Repère T1.4.HJN
Désignation
TAB.ELEC T1.4.HJN

Normal Secours

I Totale 23,45 A

I installée 27,82 A

Ik3 max 4096 A


L2 L1 L1 L1 L1 L3 L3 L3
Ik1 max 2093 A

DU max 3,40 %

Repère T1.4.HJN_A02 T1.4.HJN_A03 T1.4.HJN_A04 T1.4.HJN_A05 T1.4.HJN_A06 T1.4.HJN_A07 T1.4.HJN_A08 T1.4.HJN_A09


ALIM. VR ESPACES ALIM. VRV BUREAUX ALIM. CE.ACC ALIM. SM ALIM. VR BUREAUX ALIM. VR BUREAUX ALIM. VRV BUREAUX ALIM. VRV BUREAUX
COLLABORATIFS PARTAGES SANITAIRES SANITAIRES PARTAGES PARTAGES PARTAGES PARTAGES
Désignation
CIRCUIT

Nb Consommation 3 300W 1 220W 1 2200W 1 2000W 3 300W 1 300W 1 220W 1 220W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 29 m Cu 12 m Cu 8m Cu 5m Cu 28 m Cu 22 m Cu 15 m Cu 19 m Cu
L.Max prot. 67 m (CI) 67 m (CI) 92 m (DU) 64 m (DU) 67 m (CI) 67 m (CI) 67 m (CI) 67 m (CI)

DU Circuit DU Totale 0,9 % 4,30 % 0,09 % 3,49 % 0,39 % 3,79 % 0,36 % 3,75 % 0,87 % 4,26 % 0,24 % 3,63 % 0,12 % 3,51 % 0,15 % 3,54 %
LIAISON

Câble 3G2,5 3G2,5 3G4 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K DT40 Type AC DT40 Type AC iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 30 mA 16 A 30 mA 16 A 16 A 16 A 16 A
Ir Im / Isd 153,6 A 153,6 A 160 A 160 A 153,6 A 153,6 A 153,6 A 153,6 A
Affectation des phases 2 1 1 1 1 3 3 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.4.HJN 172
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1
T1.4.HJN
RESEAU
C
Rég.de N TN 2P1D
16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T8
Amont
Secours

Repère T1.4.HJN
Désignation
TAB.ELEC T1.4.HJN

Normal Secours

I Totale 23,45 A

I installée 27,82 A

Ik3 max 4096 A


L3
Ik1 max 2093 A

DU max 3,40 %

Repère T1.4.HJN_A10
ALIM. CAPTEUR
TEMP QUALITE AIR
Désignation
CIRCUIT

Nb Consommation 2 30W
Alimentation Normal
JdB Amont
Type U1000R2V (90°C)

Longueur Ame 65 m Cu
L.Max prot. 67 m (CI)

DU Circuit DU Totale 0,12 % 3,52 %


LIAISON

Câble 3G2,5
Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K
Protection
PROT.

Calibre IDn 16 A
Ir Im / Isd 153,6 A
Affectation des phases 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T1.4.HJN 173
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T2.1.HJN T2.1.HJN
RESEAU
C C C C C
Rég.de N TN -PRO|488 -PRO|489 -PRO|490 -PRO|491 -PRO|492 -PRO|493
3P 4P3D 4P4D 4P4D 4P3D 4P3D 4P3D
250 A 125 A 40 A 80 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T9
Amont L
Secours P.T.

Repère T2.1.HJN TN
Désignation 400 V
TAB.ELEC T2.1.HJN

Normal Secours

I Totale 234,55 A

I installée 173,37 A

Ik3 max 14277 A

Ik1 max 8376 A

DU max 3,71 %

Repère T2.1.HJN_BS001 TG.N-3HJ_T9 T2.1-HJ_A01 T2.1-HJ_A02 T2.1-HJ_A03 T2.1-HJ_A04 T2.1-HJ_A05 T2.1-HJ_A06


Voyant présence TAB.ELEC T2.1.HJN ALIM PAC AIR/EAU ALIM PAC AIR/EAU ALIM PAC AIR/EAU ALIM CTA LAB ALIM CTA LAB ALIM CTA LAB
tension
Désignation
CIRCUIT

Nb Consommation 1 1 130kW 1 58740W 1 18610W 1 38500W 1 2420W 1 1270W 1 2850W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 50 m Cu 15 m Cu 22 m Cu 15 m Cu 15 m Cu 15 m Cu 12 m Cu
L.Max prot. 65 m (DU) 82 m (CI) 114 m (CI) 127 m (CI) 113 m (CI) 113 m (CI) 113 m (CI)

DU Circuit DU Totale 0,92 % 3,71 % 0,41 % 4,12 % 0,62 % 4,33 % 0,36 % 4,07 % 0,14 % 3,84 % 0,07 % 3,78 % 0,13 % 3,84 %
LIAISON

Câble 2x1,5 3X(1x150) 5G35 5G10 5G25 5G4 5G4 5G4


Neutre
Séparé
PE/PEN 1x150
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NSX250NA NSX160B iC60L C120N DT40N DT40N DT40N
Protection
TM125D
PROT.

Calibre IDn 250 A 125 A 40 A 80 A 16 A 16 A 16 A


Ir Im / Isd 112,5 A 1250 A 384 A 800 A 160 A 160 A 160 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.1.HJN 174
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
T2.1.HJN T2.1.HJN
RESEAU
C C C C C C
Rég.de N TN -PRO|494 -PRO|495 -PRO|496 -PRO|497 -PRO|498 -PRO|499
4P3D 4P3D 2P1D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T9
Amont
Secours

Repère T2.1.HJN
Désignation
TAB.ELEC T2.1.HJN

Normal Secours

I Totale 234,55 A

I installée 173,37 A

Ik3 max 14277 A


L3 L1 L3 L2
Ik1 max 8376 A

DU max 3,71 %

Repère T2.1-HJ_A07 T2.1-HJ_A08 T2.1-HJ_A09 T2.1-HJ_A10 T2.1-HJ_A11 T2.1-HJ_A12


ALIM CAISSON LAB ALIM CAISSON LAB ALIM SPLIT SYSYTEM ALIM SPLIT SYSYTEM ALIM SPLIT SYSYTEM ALIM SPLIT SYSYTEM
EXT EXT EXT EXT
Désignation
CIRCUIT

Nb Consommation 1 2420W 1 2420W 1 2510W 1 2510W 1 2510W 1 2510W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 10 m Cu 9m Cu 10 m Cu 7m Cu 7m Cu 9m Cu
L.Max prot. 113 m (CI) 113 m (CI) 47 m (DU) 47 m (DU) 47 m (DU) 47 m (DU)

DU Circuit DU Totale 0,09 % 3,80 % 0,08 % 3,79 % 0,9 % 4,61 % 0,63 % 4,34 % 0,63 % 4,34 % 0,81 % 4,52 %
LIAISON

Câble 5G4 5G4 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
DT40N DT40N DT40 DT40 DT40 DT40
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 160 A 160 A 160 A
Affectation des phases 123 123 3 1 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.1.HJN 175
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T2.2.HJN T2.2.HJN
RESEAU
C C C C C C
Rég.de N TN -PRO|500 -PRO|501 -PRO|502 -PRO|503 -PRO|504 -PRO|505
3P 4P4D 4P4D 4P4D 4P3D 4P3D 4P4D
250 A 80 A 80 A 80 A 16 A 16 A 80 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T10
Amont L
Secours P.T.

Repère T2.2.HJN TN
Désignation 400 V
TAB.ELEC T2.2.HJN

Normal Secours

I Totale 234,55 A

I installée 170,97 A

Ik3 max 12881 A

Ik1 max 7447 A

DU max 3,91 %

Repère T2.2.HJN_BS001 TG.N-3HJ_T10 T2.2-HJ_A01 T2.2-HJ_A02 T2.2-HJ_A03 T2.2-HJ_A04 T2.2-HJ_A05 T2.2-HJ_A06


Voyant présence TAB.ELEC T2.2.HJN ALIM POMPE A ALIM POMPE A ALIM POMPE A ALIM CTA LAB ALIM CTA LAB ALIM VRV
tension CHALEUR AIR/AIR CHALEUR AIR/EAU CHALEUR AIR/EAU
Désignation
CIRCUIT

Nb Consommation 1 1 130kW 1 35200W 1 43780W 1 43780W 1 2420W 1 2420W 1 32590W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 70 m Cu 4m Cu 18 m Cu 17 m Cu 13 m Cu 13 m Cu 11 m Cu
L.Max prot. 75 m (DU) 126 m (CI) 126 m (CI) 126 m (CI) 113 m (CI) 113 m (CI) 126 m (CI)

DU Circuit DU Totale 1,11 % 3,91 % 0,09 % 3,99 % 0,5 % 4,40 % 0,47 % 4,37 % 0,12 % 4,02 % 0,12 % 4,02 % 0,23 % 4,13 %
LIAISON

Câble 2x1,5 3X(1x185) 5G25 5G25 5G25 5G4 5G4 5G25


Neutre
Séparé
PE/PEN 1x185
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NSX250NA C120N C120N C120N DT40N DT40N C120N
Protection
PROT.

Calibre IDn 250 A 80 A 80 A 80 A 16 A 16 A 80 A


Ir Im / Isd 800 A 800 A 800 A 160 A 160 A 800 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.2.HJN 176
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
T2.2.HJN T2.2.HJN
RESEAU
C C C C C
Rég.de N TN -PRO|506 -PRO|507 -PRO|508 -PRO|509 -PRO|510
4P3D 4P3D 2P1D 2P1D 2P1D
16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T10
Amont
Secours

Repère T2.2.HJN
Désignation
TAB.ELEC T2.2.HJN

Normal Secours

I Totale 234,55 A

I installée 170,97 A

Ik3 max 12881 A


L2 L3 L1
Ik1 max 7447 A

DU max 3,91 %

Repère T2.2-HJ_A07 T2.2-HJ_A08 T2.2-HJ_A09 T2.2-HJ_A10 T2.2-HJ_A11


ALIM C.EXT LAB ALIM C.EXT LAB ALIM CAISSON ALIM ARMOIRES DE ALIM ARMOIRES DE
D'EXTRACTION VMC CLIMATISATION CLIMATISATION
Désignation
CIRCUIT

Nb Consommation 1 2420W 1 2420W 1 610W 1 400W 1 400W


Alimentation Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 10 m Cu 11 m Cu 13 m Cu 10 m Cu 9m Cu
L.Max prot. 113 m (CI) 113 m (CI) 70 m (CI) 70 m (CI) 70 m (CI)

DU Circuit DU Totale 0,09 % 4,00 % 0,1 % 4,01 % 0,28 % 4,19 % 0,14 % 4,05 % 0,13 % 4,03 %
LIAISON

Câble 5G4 5G4 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
DT40N DT40N DT40 DT40 DT40
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 160 A 160 A
Affectation des phases 123 123 2 3 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.2.HJN 177
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
T2.3.HJN T2.3.HJN
RESEAU
C C C C C C
Rég.de N TN -PRO|511 -PRO|512 -PRO|513 -PRO|514 -PRO|515 -PRO|516
3P 4P4D 4P3D 4P3D 4P4D 4P4D 4P4D
250 A 80 A 20 A 16 A 63 A 80 A 80 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T11
Amont L
Secours P.T.

Repère T2.3.HJN TN
Désignation 400 V
TAB.ELEC T2.3.HJN

Normal Secours

I Totale 247,18 A

I installée 203,82 A

Ik3 max 13329 A

Ik1 max 7750 A

DU max 3,88 %

Repère T2.3.HJN_BS001 TG.N-3HJ_T11 T2.3-HJ_A01 T2.3-HJ_A02 T2.3-HJ_A03 T2.3-HJ_A04 T2.3-HJ_A05 T2.3-HJ_A06


Voyant présence TAB.ELEC T2.3.HJN ALIM POMPE A ALIM POMPE A ALIM CAT A/N ALIM UNITE ALIM UNITE ALIM UNITE
tension CHALEUR AIR/AIR CHALEUR AIR/EAU EXTERIEUR VRV EXTERIEUR VRV EXTERIEUR VRV
Désignation
CIRCUIT

Nb Consommation 1 1 137kW 1 35200W 1 7220W 1 750W 1 22810W 1 38040W 1 35040W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 65 m Cu 13 m Cu 13 m Cu 9m Cu 11 m Cu 8m Cu 9m Cu
L.Max prot. 72 m (DU) 126 m (CI) 135 m (CI) 113 m (CI) 106 m (CI) 126 m (CI) 126 m (CI)

DU Circuit DU Totale 1,09 % 3,88 % 0,29 % 4,17 % 0,24 % 4,12 % 0,03 % 3,91 % 0,24 % 4,12 % 0,19 % 4,07 % 0,2 % 4,08 %
LIAISON

Câble 2x1,5 3X(1x185) 5G25 5G6 5G4 5G16 5G25 5G25


Neutre
Séparé
PE/PEN 1x185
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NSX250NA C120N DT40N DT40N DT60N C120N C120N
Protection
PROT.

Calibre IDn 250 A 80 A 20 A 16 A 63 A 80 A 80 A


Ir Im / Isd 800 A 200 A 160 A 630 A 800 A 800 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.3.HJN 178
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1 1
T2.3.HJN T2.3.HJN
RESEAU
C C C C C C C C
Rég.de N TN -PRO|517 -PRO|518 -PRO|519 -PRO|520 -PRO|521 -PRO|522 -PRO|523 -PRO|524
4P4D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
80 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Tension 400 V

DISTRIBUTION
Normal TG.N-3HJ_T11
Amont
Secours

Repère T2.3.HJN
Désignation
TAB.ELEC T2.3.HJN

Normal Secours

I Totale 247,18 A

I installée 203,82 A

Ik3 max 13329 A


L3 L2 L1 L1 L2 L3 L3
Ik1 max 7750 A

DU max 3,88 %

Repère T2.3-HJ_A07 T2.3-HJ_A08 T2.3-HJ_A09 T2.3-HJ_A10 T2.3-HJ_A11 T2.3-HJ_A12 T2.3-HJ_A13 T2.3-HJ_A14


ALIM UNITE ALIM SPLIT SYSTEM ALIM SPLIT SYSTEM ALIM SPLIT SYSTEM ALIM SPLIT SYSTEM ALIM SPLIT SYSTEM ALIM CDAISSON ALIM ADOUCISSEUR
EXTERIEUR VRV EXT EXT EXT EXT EXT D'EXTRACTION VMC
Désignation
CIRCUIT

Nb Consommation 1 38040W 1 2510W 1 2510W 1 2510W 1 2510W 1 2510W 1 610W 1 390W


Alimentation Normal Normal Normal Normal Normal Normal Normal Normal
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 10 m Cu 16 m Cu 13 m Cu 14 m Cu 15 m Cu 15 m Cu 6m Cu 13 m Cu
L.Max prot. 126 m (CI) 45 m (DU) 45 m (DU) 45 m (DU) 45 m (DU) 45 m (DU) 71 m (CI) 71 m (CI)

DU Circuit DU Totale 0,24 % 4,12 % 1,44 % 5,32 % 1,17 % 5,05 % 1,26 % 5,14 % 1,35 % 5,23 % 1,35 % 5,23 % 0,13 % 4,01 % 0,18 % 4,06 %
LIAISON

Câble 5G25 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
C120N DT40 DT40 DT40 DT40 DT40 DT40 DT40
Protection
PROT.

Calibre IDn 80 A 16 A 16 A 16 A 16 A 16 A 16 A 16 A
Ir Im / Isd 800 A 160 A 160 A 160 A 160 A 160 A 160 A 160 A
Affectation des phases 123 3 2 1 1 2 3 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits T2.3.HJN 179
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
TS1.HJN TS1.HJN
RESEAU
C
Rég.de N TN 3P 4P3D SJDB1
50 A 32 A
30 mA
Tension 400 V B B C C

2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T12
Amont L
Secours P.T.

Repère TS1.HJN TN
Désignation 400 V
TAB.ELEC TS1.HJN

Normal Secours

I Totale 45,11 A

I installée 8,04 A

Ik3 max 15197 A


L3 L1 L3 L2
Ik1 max 8806 A

DU max 2,97 %

Repère TS1.HJN_BS001 TG.N-3HJ_T12 TS1.HJN_J001 SJDB1 TS.1_3HJ_N_PC21 TS.1_3HJ_N_PC22 TS.1_3HJ_N_PC23 TS.1_3HJ_N_PC24


Voyant présence TAB.ELEC TS1.HJN JDB PC TBD PARKING ESPACE ET TBD PC PUMP ROOM PC FOSSE RELEVAGE
tension PARKING
Désignation
CIRCUIT

Nb Consommation 1 1 25kW 1 7,5kVA 0 8 250W 8 250W 8 250W 8 250W


Alimentation Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 15 m Cu 0m 107 m Cu 81 m Cu 58 m Cu 48 m Cu


L.Max prot. 17 m (DU) 149 m (CC) 149 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 0,17 % 2,97 % 0% 2,97 % 1,5 % 4,46 % 1,19 % 4,16 % 0,83 % 3,80 % 0,69 % 3,66 %
LIAISON

Câble 2x1,5 4G35 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
NSXm50NA DT40N Type AC iDT40T iDT40T DT40K DT40K
Protection
PROT.

Calibre IDn 50 A 32 A 30 mA 16 A 16 A 16 A 16 A
Ir Im / Isd 320 A 76,8 A 76,8 A 160 A 160 A
Affectation des phases 123 123 3 1 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TS1.HJN 180
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
TS1.HJN TS1.HJN
RESEAU
C
Rég.de N TN SJDB1 4P3D SJDB2
32 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T12
Amont
Secours

Repère L3
TS1.HJN
Réserve
Désignation Equipée
TAB.ELEC TS1.HJN

Normal Secours

I Totale 45,11 A

I installée 8,04 A

Ik3 max 15197 A


L1 L2 L1 L1 L2
Ik1 max 8806 A

DU max 2,97 %

Repère TS.1_3HJ_N_PC25 TS.1_3HJ_N_PC26 TS1.HJN_R1 TS1.HJN_J002 SJDB2 TS.1_3HJ_N_PC27 TS.1_3HJ_N_PC28 TS.1_3HJ_N_PC29


PC LOCAL PC L.T & HALL Réserve équipée JDB PC PC L.T PC LOCAL PC LOCAL VELO
ENTRETIEN ASCENSEUR TECHNIQUE
Désignation
CIRCUIT

Nb Consommation 8 250W 3 250W 1 0,00001W 1 8,9kVA 0 4 250W 7 250W 5 250W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 41 m Cu 29 m Cu 0m 0m 19 m Cu 45 m Cu 55 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 0,57 % 3,53 % 0,37 % 3,34 % 0% 2,97 % 0% 2,97 % 0,15 % 3,12 % 0,63 % 3,59 % 0,66 % 3,63 %
LIAISON

Câble 3G2,5 3G2,5 3G2,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40N Type AC DT40K DT40K DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 32 A 30 mA 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 320 A 160 A 160 A 160 A
Affectation des phases 1 2 3 123 1 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TS1.HJN 181
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
TS1.HJN TS1.HJN
RESEAU
C
Rég.de N TN SJDB2 4P3D SJDB3
32 A
30 mA
Tension 400 V C C C C C C

2P1D 2P1D 2P1D 2P1D 2P1D 2P1D


16 A 16 A 16 A 16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T12
Amont
Secours

Repère L3 L3
TS1.HJN
Réserve Réserve
Désignation Equipée Equipée
TAB.ELEC TS1.HJN

Normal Secours

I Totale 45,11 A

I installée 8,04 A

Ik3 max 15197 A


L3 L3 L2 L1
Ik1 max 8806 A

DU max 2,97 %

Repère TS.1_3HJ_N_PC30 TS1.HJN_R2 TS1.HJN_R3 TS1.HJN_J003 SJDB3 TS.1_3HJ_N_AL31 TS.1_3HJ_N_AL32 TS.1_3HJ_N_AL40


PC TBD Réserve équipée Réserve équipée JDB ALIM ALIM SM SANITAIRE ALIM BECS ALIM VENTILATEUR
SANITAIRE SANITAIRE
Désignation
CIRCUIT

Nb Consommation 8 250W 1 0,00001W 1 0,00001W 1 5kVA 0 1 1500W 1 2000W 1 1500W


Alimentation Normal Normal Normal Normal Normal Normal Normal
JdB Amont SJDB2 SJDB2 SJDB2 SJDB3 SJDB3 SJDB3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 63 m Cu 0m 0m 0m 52 m Cu 52 m Cu 10 m Cu
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC) 70 m (CC) 113 m (DU) 113 m (CC)

DU Circuit DU Totale 0,93 % 3,90 % 0% 2,97 % 0% 2,97 % 0% 2,97 % 2,8 % 5,77 % 2,31 % 5,28 % 0,34 % 3,30 %
LIAISON

Câble 3G2,5 3G2,5 3G4 3G4


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40K DT40K DT40K DT40N Type AC DT40K DT40K DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A 32 A 30 mA 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A 320 A 160 A 160 A 160 A
Affectation des phases 3 3 3 123 3 2 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TS1.HJN 182
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1
TS1.HJN
RESEAU
Rég.de N TN SJDB3

Tension 400 V C C C

2P1D 2P1D 2P1D


16 A 16 A 16 A
DISTRIBUTION
Normal TG.N-3HJ_T12
Amont
Secours

Repère L3 L3 L3
TS1.HJN
Réserve Réserve Réserve
Désignation Equipée Equipée Equipée
TAB.ELEC TS1.HJN

Normal Secours

I Totale 45,11 A

I installée 8,04 A

Ik3 max 15197 A

Ik1 max 8806 A

DU max 2,97 %

Repère TS1.HJN_R4 TS1.HJN_R5 TS1.HJN_R6


Réserve équipée Réserve équipée Réserve équipée

Désignation
CIRCUIT

Nb Consommation 1 0,00001W 1 0,00001W 1 0,00001W


Alimentation Normal Normal Normal
JdB Amont SJDB3 SJDB3 SJDB3
Type
Longueur Ame 0m 0m 0m
L.Max prot. 70 m (CC) 70 m (CC) 70 m (CC)

DU Circuit DU Totale 0% 2,97 % 0% 2,97 % 0% 2,97 %


LIAISON

Câble
Neutre
Séparé
PE/PEN
Taux d'Harmonique
DT40K DT40K DT40K
Protection
PROT.

Calibre IDn 16 A 16 A 16 A
Ir Im / Isd 160 A 160 A 160 A
Affectation des phases 3 3 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TS1.HJN 183
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 0 1 1 1 1 1
TGBT.NS TGBT.NS
RESEAU
Rég.de N TN 3P3D 3P3D 4P3D 3P3D 3P3D 4P3D 3P3D
1000 A 1000 A 25 A 400 A 400 A 40 A 63 A
Tension 400 V

DISTRIBUTION
Normal W W W W W Réserve
TGBT.N_T3
Equipée
Amont L
Secours SECOURS P.T.

Repère TGBT.NS TN TN
Désignation 400 V 400 V
TAB.ELEC TGBT.NS

Normal Secours

I Totale 909,33 A 909,35 A

I installée 649,52 A 649,52 A

Ik3 max 37052 A 9770 A

Ik1 max 31833 A 10932 A

TAB

TAB

TAB
DU max 1,17 % 0,37 %

Repère TGBT.NS_BS001 TGBT.N_T3 SECOURS TGBT.NS_F001 TGBT.NS_T1 TGBT.NS_T2 TGBT.NS_T3 TGBT.NS_R1


Voyant présence TAB.ELEC TGBT.NS TAB.ELEC TGBT.NS Parafoudre TYPE 2 TAB.ELEC TG.NS-3A TAB.ELEC TG.NS-3HJ TAB.ELEC TPS.EXT- Réserve équipée
tension 3HJ
Désignation
CIRCUIT

Nb Consommation 1 1 630kVA 1 630KVA 1 0,00001W 1 185kW 1 165kW 1 10kW 1 0,00001W


Alimentation Normal Secours Normal N et S N et S N et S Normal
JdB Amont
Type CR1-C1 (90°C) U1000R2V (90°C) U1000R2V (90°C) CR1-C1 (90°C) CR1-C1 (90°C) U1000R2V (90°C)

Longueur Ame 0m 18 m Cu 15 m Cu 2m Cu 103 m Cu 55 m Cu 10 m Cu 0m


L.Max prot. 65 m (DU) 127 m (CC) 117 m (DU) 77 m (DU) 21 m (DU) 121 m (CI)

DU Circuit DU Totale 0,31 % 1,17 % 0% 0,37 % 0% 1,17 % 1,16 % 2,33 % 0,94 % 2,11 % 0,15 % 1,32 % 0% 1,17 %
LIAISON

Câble 2x1,5 3X3X(1x240) 2X3X(1x240) 4x10 2X3X(1x185) 3X(1x240) 5G10


Neutre
Séparé
PE/PEN 3X(1x240) 2X(1x240) 2X(1x185) 1x240
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NS1000N NS1000N NSX100F NSX400F NSX400F NSX100F NSX100F
Protection
Micrologic 2.0 Micrologic 2.0 TM25D Micrologic 2.3 Micrologic 2.3 TM40D TM63D
PROT.

Calibre IDn 1000 A 1000 A 25 A 400 A 400 A 40 A 63 A


Ir Im / Isd 950 A 9500 A 950 A 1900 A 25 A 300 A 334,8 A 1339,2 A 300,8 A 1804,8 A 28 A 500 A 63 A 500 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TGBT.NS 184
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1
TGBT.NS
RESEAU
Rég.de N TN 3P3D 3P3D
40 A 25 A
Tension 400 V

DISTRIBUTION
Réserve Réserve
Normal TGBT.N_T3
Equipée Equipée
Amont
Secours SECOURS

Repère TGBT.NS
Désignation
TAB.ELEC TGBT.NS

Normal Secours

I Totale 909,33 A 909,35 A

I installée 649,52 A 649,52 A

Ik3 max 37052 A 9770 A

Ik1 max 31833 A 10932 A

DU max 1,17 % 0,37 %

Repère TGBT.NS_R2 TGBT.NS_R3


Réserve équipée Réserve équipée

Désignation
CIRCUIT

Nb Consommation 1 0,00001W 1 0,00001W


Alimentation Normal Normal
JdB Amont
Type
Longueur Ame 0m 0m
L.Max prot. 75 m (CI) 127 m (CI)

DU Circuit DU Totale 0% 1,17 % 0% 1,17 %


LIAISON

Câble
Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
NSX100F NSX100F
Protection
TM40D TM25D
PROT.

Calibre IDn 40 A 25 A
Ir Im / Isd 40 A 500 A 25 A 300 A
Affectation des phases 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TGBT.NS 185
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1 1
TG.NS-3A TG.NS-3A
RESEAU
C C C C C
Rég.de N TN -PRO|835 -PRO|836 -PRO|841 -PRO|838 -PRO|854
3P 4P4D 4P4D 4P4D 4P4D 4P4D 4P3D
400 A 25 A 40 A 40 A 40 A 40 A 250 A
Tension 400 V

DISTRIBUTION
Normal W W W W W
TGBT.NS_T1
Amont L
Secours TGBT.NS_T1 P.T.

Repère TG.NS-3A TN
Désignation 400 V
TAB.ELEC TG.NS-3A

Normal Secours

I Totale 333,78 A 333,78 A

I installée 471,60 A 471,60 A

Ik3 max 18905 A 8152 A

Ik1 max 11832 A 7375 A

TAB

TAB

TAB

TAB
DU max 2,33 % 1,54 % A.S.I

Repère TG.NS-3A_BS003 TGBT.NS_T1 TG.NS-3A_F001 TG.NS-3A_T1 TG.NS-3A_T2 TG.NS-3A_T3 TG.NS-3A_T4 TG.NS-3A_T5


Voyant présence TAB.ELEC TG.NS-3A Parafoudre TYPE 2 TAB.ELEC TR1.AS TAB.ELEC TR2.AS TAB.ELEC TR3.AS TAB.ELEC TR4.AS TAB.ELEC ONDULE
tension TGO-3A
Désignation
CIRCUIT

Nb Consommation 1 1 185kW 1 0,00001W 1 7kW 1 7kW 1 6kW 1 4kW 1 160kVA


Alimentation N et S Normal N et S N et S N et S N et S N et S
JdB Amont
Type CR1-C1 (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 103 m Cu 2m Cu 19 m Cu 29 m Cu 89 m Cu 71 m Cu 20 m Cu


L.Max prot. 117 m (DU) 188 m (CC) 62 m (DU) 62 m (DU) 116 m (CI) 109 m (DU) 56 m (DU)

DU Circuit DU Totale 1,16 % 2,33 % 0% 2,33 % 0,2 % 2,53 % 0,31 % 2,64 % 0,81 % 3,14 % 0,43 % 2,76 % 0,41 % 2,74 %
LIAISON

Câble 2x1,5 2X3X(1x185) 4x10 5G10 5G10 5G10 5G10 4x120


Neutre
Séparé
PE/PEN 2X(1x185) 1x70
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NSX400NA iC60L iC60L iC60L iC60L iC60L NSX250F
Protection
TM250D
PROT.

Calibre IDn 400 A 25 A 40 A 40 A 40 A 40 A 250 A


Ir Im / Isd 240 A 384 A 384 A 384 A 384 A 250 A 1250 A
Affectation des phases 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TG.NS-3A 186
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
TG.NS-3A TG.NS-3A
RESEAU
C C C C
Rég.de N TN 4P3D 4P4D 4P4D 4P4D 4P4D 3P3D
250 A 40 A 40 A 40 A 40 A 125 A
Tension 400 V

DISTRIBUTION
Normal W W W W W
TGBT.NS_T1
Amont
Secours TGBT.NS_T1

Repère TG.NS-3A
Désignation
TAB.ELEC TG.NS-3A

Normal Secours

I Totale 333,78 A 333,78 A

I installée 471,60 A 471,60 A

Ik3 max 18905 A 8152 A

Ik1 max 11832 A 7375 A

TAB

TAB

TAB

TAB

TAB
DU max 2,33 % 1,54 %

Repère TG.NS-3A_BS001 TG.NS-3A_BS002 TG.NS-3A_T6 TG.NS-3A_T7 TG.NS-3A_T8 TG.NS-3A_T9 TG.NS-3A_T10 TG.NS-3A_T11


TAB.ELEC ONDULE TAB.ELEC T1.1.AS TAB.ELEC T1.2.AS TAB.ELEC T1.3.AS TAB.ELEC T1.4.AS TAB.ELEC S.SOL
TGO-3A (BY PASS) TS2.AS
Désignation
CIRCUIT

Nb Consommation 0 0 1 160kVA 1 7kW 1 10kW 1 6kW 1 5kW 1 56kW


Alimentation N et S N et S N et S N et S N et S N et S
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 0m 20 m Cu 25 m Cu 34 m Cu 54 m Cu 48 m Cu 15 m Cu
L.Max prot. 55 m (DU) 62 m (DU) 43 m (DU) 73 m (DU) 87 m (DU) 25 m (DU)

DU Circuit DU Totale 0,42 % 2,76 % 0,27 % 2,60 % 0,52 % 2,85 % 0,49 % 2,82 % 0,36 % 2,70 % 0,39 % 2,72 %
LIAISON

Câble 3X(1x120) 5G10 5G10 5G10 5G10 4G35


Neutre 1x120
Séparé
PE/PEN 1x70
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
NSX250F iC60L iC60L iC60L iC60L NSX160B
Protection
TM250D TM125D
PROT.

Calibre IDn 250 A 40 A 40 A 40 A 40 A 125 A


Ir Im / Isd 250 A 1250 A 384 A 384 A 384 A 384 A 112,5 A 1250 A
Affectation des phases 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TG.NS-3A 187
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 2 2 1 1 1 1 1 1
TG.NS-3A TG.NS-3A
RESEAU
C C C C C C C
Rég.de N TN 4P4D 4P4D 4P4D 4P4D 4P4D 4P3D 4P4D 4P4D
40 A 40 A 25 A 25 A 25 A 63 A 40 A 25 A
Tension 400 V

DISTRIBUTION
Normal W W W W W Réserve Réserve Réserve
TGBT.NS_T1
Equipée Equipée Equipée
Amont
Secours TGBT.NS_T1

Repère TG.NS-3A
Désignation
TAB.ELEC TG.NS-3A

Normal Secours

I Totale 333,78 A 333,78 A

I installée 471,60 A 471,60 A

Ik3 max 18905 A 8152 A

Ik1 max 11832 A 7375 A


TAB

TAB

DU max 2,33 % 1,54 %

Repère TG.NS-3A_T12 TG.NS-3A_T13 TG.NS-3A/ASC1 TG.NS-3A/ASC2 TG.NS-3A/ASC3 TG.NS-3A_R1 TG.NS-3A_R2 TG.NS-3A_R3


TAB.ELEC TP.EXT.AS TAB.ELEC TLT.EXT.AS ALIM. ASCENSEUR ALIM. ASCENSEUR ALIM. ASCENSEUR Réserve équipée Réserve équipée Réserve équipée
Asc1 Asc2 Asc3
Désignation
CIRCUIT

Nb Consommation 1 5kVA 1 5kVA 1 10kW 1 10kW 1 10kW 1 0,00001W 1 0,00001W 1 0,00001W


Alimentation N et S N et S N et S N et S N et S N et S N et S N et S
JdB Amont
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 15 m Cu 15 m Cu 38 m Cu 25 m Cu 54 m Cu 0m 0m 0m
L.Max prot. 96 m (DU) 109 m (DU) 188 m (CI) 188 m (CI) 188 m (CI) 114 m (CI) 69 m (CI) 47 m (CI)

DU Circuit DU Totale 0,1 % 2,44 % 0,09 % 2,42 % 0,58 % 2,91 % 0,38 % 2,71 % 0,82 % 3,15 % 0% 2,33 % 0% 2,33 % 0% 2,33 %
LIAISON

Câble 5G10 5G10 5G10 5G10 5G10


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15% TH <= 15%
iC60L iC60L iC60L iC60L iC60L NSX100B iC60L iC60L
Protection
TM63D
PROT.

Calibre IDn 40 A 40 A 25 A 25 A 25 A 63 A 40 A 25 A
Ir Im / Isd 384 A 384 A 240 A 240 A 240 A 63 A 500 A 384 A 240 A
Affectation des phases 123 123 123 123 123 123 123 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TG.NS-3A 188
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR1.AS TR1.AS
RESEAU
C C
Rég.de N TN 4P 2P1D 4P3D SJDB1
40 A 10 A 25 A
300 mA
Tension 400 V C C
-PRO|294
2P1D 2P1D
10 A 10 A
DISTRIBUTION L1

Normal TG.NS-3A_T1 T.B.S


Amont L
Secours TG.NS-3A_T1 P.T.

Repère TR1.AS TN
Désignation 400 V
TAB.ELEC TR1.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 5,47 A 0,06 A

Ik3 max 5684 A 4883 A


L2 L3
Ik1 max 2941 A 2849 A

DU max 2,53 % 1,74 %

Repère TR1.AS_BS002 TG.NS-3A_T1 TR1.AS_F001 TR1.AS_J1 SJDB1 TR1.AS/BS1 TR1.AS/E1 TR1.AS/E2


Voyant présence TAB.ELEC TR1.AS Télécommande bloc de JDB ECL BAES ECL L.TGBT ECL SALLE DE
tension sécurité CONFERENCE
Désignation
CIRCUIT

Nb Consommation 1 1 7kW 1 50W 1 3kVA 0 1 3 72W 12 40W


Alimentation N et S N et S N et S Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 19 m Cu 0m 0m 14 m Cu 14 m Cu 59 m Cu
L.Max prot. 62 m (DU) 66 m (CC) 69 m (CC) 69 m (CC)

DU Circuit DU Totale 0,2 % 2,53 % 0% 2,53 % 0% 2,53 % 0,13 % 2,67 % 1,24 % 3,77 %
LIAISON

Câble 2x1,5 5G10 4x1.5 3G1,5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
iSW-NA DT40 DT40 Type AC iDT40K iDT40K
Protection
PROT.

Calibre IDn 40 A 10 A 25 A 300 mA 10 A 10 A


Ir Im / Isd 100 A 250 A 96 A 96 A
Affectation des phases 123 1 123 2 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR1.AS 189
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR1.AS TR1.AS
RESEAU
C
Rég.de N TN SJDB1 4P3D
25 A
300 mA
Tension 400 V C C C C
-PRO|293 -PRO|281 -PRO|284
2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T1
Amont
Secours TG.NS-3A_T1

Repère TR1.AS
Désignation
TAB.ELEC TR1.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 5,47 A 0,06 A

Ik3 max 5684 A 4883 A


L1 L3 L1 L3
Ik1 max 2941 A 2849 A

DU max 2,53 % 1,74 %

Repère TR1.AS/BS3 TR1.AS/E3 TR1.AS/BS4 TR1.AS/E4 TR1.AS/BS5 TR1.AS/E5 TR1.AS/E6 TR1.AS_J002


BAES ECL SALLE DE BAES ECL SALLE DE BAES ECL LAB ECL JDB ECL
CONFERENCE CONFERENCE
Désignation
CIRCUIT

Nb Consommation 1 8 40W 1 8 40W 1 11 40W 8 40W 1 3kVA


Alimentation Normal Normal Normal Normal N et S
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 21 m Cu 44 m Cu 66 m Cu 42 m Cu 29 m Cu 49 m Cu 48 m Cu
L.Max prot. 69 m (CC) 69 m (CC) 69 m (CC) 69 m (CC)

DU Circuit DU Totale 0,67 % 3,21 % 0,63 % 3,16 % 1,03 % 3,56 % 0,77 % 3,30 % 0% 2,53 %
LIAISON

Câble 4x1.5 3G1,5 4x1.5 3G1,5 4x1.5 3G1,5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K iDT40K iDT40K iDT40K DT40 Type AC
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A 25 A 300 mA


Ir Im / Isd 96 A 96 A 96 A 96 A 250 A
Affectation des phases 1 3 1 3 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR1.AS 190
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1
TR1.AS TR1.AS
RESEAU
Rég.de N TN SJDB2

Tension 400 V C C C C
-PRO|288 -PRO|285 -PRO|291
2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T1
Amont
Secours TG.NS-3A_T1

Repère TR1.AS
Désignation
TAB.ELEC TR1.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 5,47 A 0,06 A

Ik3 max 5684 A 4883 A


L2 L1 L1 L3
Ik1 max 2941 A 2849 A

DU max 2,53 % 1,74 %

Repère SJDB2 TR1.AS/BS7 TR1.AS/E7 TR1.AS/E8 TR1.AS/E9 TR1.AS/BS10 TR1.AS/E10 TR1.AS_BS001


BAES ECL LAB ECL LAB ECL LAB BAES ECL CORE SHACK BAES

Désignation
CIRCUIT

Nb Consommation 0 1 7 40W 6 40W 6 40W 1 5 15W 0


Alimentation Normal Normal Normal Normal
JdB Amont SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 35 m Cu 46 m Cu 30 m Cu 31 m Cu 32 m Cu 29 m Cu 0m
L.Max prot. 69 m (CC) 69 m (CC) 69 m (CC) 69 m (CC)

DU Circuit DU Totale 0,65 % 3,18 % 0,36 % 2,89 % 0,38 % 2,91 % 0,11 % 2,65 %
LIAISON

Câble 4x1.5 3G1,5 3G1,5 3G1,5 4x1.5 3G1,5 5G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A
Ir Im / Isd 96 A 96 A 96 A 96 A
Affectation des phases 2 1 1 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR1.AS 191
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR1.AS TR1.AS
RESEAU
C
Rég.de N TN SJDB2 4P3D SJDB3
25 A
300 mA
Tension 400 V C C C C
-PRO|295 -PRO|290 -PRO|289
2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T1
Amont
Secours TG.NS-3A_T1

Repère TR1.AS
Désignation
TAB.ELEC TR1.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 5,47 A 0,06 A

Ik3 max 5684 A 4883 A


L3 L2 L2 L2
Ik1 max 2941 A 2849 A

DU max 2,53 % 1,74 %

Repère TR1.AS/E11 TR1.AS/E12 TR1.AS_J003 SJDB3 TR1.AS/BS13 TR1.AS/E13 TR1.AS/BS14 TR1.AS/E14


ECL CORE SHACK ECL CORE SHACK JDB ECL BAES ECL PROCESSING BAES ECL PROCESSING

Désignation
CIRCUIT

Nb Consommation 8 40W 4 40W 1 3kVA 0 1 10 40W 1 8 40W


Alimentation Normal Normal N et S Normal Normal
JdB Amont SJDB2 SJDB2 SJDB3 SJDB3 SJDB3 SJDB3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 54 m Cu 43 m Cu 0m 18 m Cu 43 m Cu 36 m Cu 31 m Cu
L.Max prot. 69 m (CC) 69 m (CC) 69 m (CC) 69 m (CC)

DU Circuit DU Totale 0,88 % 3,42 % 0,38 % 2,91 % 0% 2,53 % 0,7 % 3,23 % 0,4 % 2,93 %
LIAISON

Câble 3G1,5 3G1,5 4x1.5 3G1,5 4x1.5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K iDT40K DT40 Type AC iDT40K iDT40K
Protection
PROT.

Calibre IDn 10 A 10 A 25 A 300 mA 10 A 10 A


Ir Im / Isd 96 A 96 A 250 A 96 A 96 A
Affectation des phases 3 2 123 2 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR1.AS 192
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR1.AS TR1.AS
RESEAU
C C
Rég.de N TN SJDB3 2P1D 2P1D
16 A 16 A
30 mA 30 mA
Tension 400 V C C C
-PRO|282 -PRO|283 -PRO|292
2P1D 2P1D 2P1D
10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T1
Amont
Secours TG.NS-3A_T1

Repère TR1.AS
Désignation
TAB.ELEC TR1.AS
1P
10 A
Normal Secours

I Totale 12,63 A 12,63 A

I installée 5,47 A 0,06 A

Ik3 max 5684 A 4883 A


L1 L L3 L3 L1 L2
Ik1 max 2941 A 2849 A

DU max 2,53 % 1,74 %

Repère TR1.AS/E15 TR1.AS/BS16 TR1.AS/DM16 TR1.AS/E16 TR1.AS/BS17 TR1.AS/E17 TR1.AS/PE39 TR1.AS/PE38


ECL BAES BP commande ECL CIRCULATION BAES ECL ESCALIERS PC SEDIMENTOLOGY PC
télérupteur LAB + HYDROGEOPHYSICS
Désignation ENVIRONMENTAL LAB-
LAB GEOMECHANICS LAB
CIRCUIT

Nb Consommation 4 40W 1 1 8 15W 1 4 45W 5 250W 6 250W


Alimentation Normal Normal Normal Normal Normal
JdB Amont SJDB3 SJDB3 SJDB3 SJDB3 SJDB3 SJDB3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 34 m Cu 37 m Cu 27 m Cu 32 m Cu 28 m Cu 65 m Cu 38 m Cu 63 m Cu
L.Max prot. 69 m (CC) 69 m (CC) 69 m (CC) 66 m (CC) 66 m (CC)

DU Circuit DU Totale 0,29 % 2,83 % 0,17 % 2,71 % 0,47 % 3,01 % 0,28 % 2,81 % 0,7 % 3,24 %
LIAISON

Câble 3G1,5 4x1.5 4X1,5 3G1,5 4x1.5 3G1,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K DT40 Type AC DT40 Type AC
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 16 A 30 mA 16 A 30 mA
Ir Im / Isd 96 A 96 A 96 A 160 A 160 A
Affectation des phases 1 3 3 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR1.AS 193
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR2.AS TR2.AS
RESEAU
C C
Rég.de N TN 4P 2P1D 4P3D SJDB1
40 A 10 A 25 A
300 mA
Tension 400 V C C
-PRO|262 -PRO|255
2P1D 2P1D
10 A 10 A
DISTRIBUTION L1

Normal TG.NS-3A_T2 T.B.S


Amont L
Secours TG.NS-3A_T2 P.T.

Repère TR2.AS TN
Désignation 400 V
TAB.ELEC TR2.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L3 L2
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS_BS001 TG.NS-3A_T2 TR2.AS_F002 TR2.AS_J001 SJDB1 TR2.AS/BS4 TR2.AS/E4 TR2.AS/E6


Voyant présence TAB.ELEC TR2.AS Télécommande bloc de JDB ECL BAES ECL BUREAUX ECL THIN &
tension sécurité PARTAGES POLISHED
Désignation
CIRCUIT

Nb Consommation 1 1 7kW 1 50W 1 3kVA 0 1 8 40W 12 40W


Alimentation N et S N et S N et S Normal Normal
JdB Amont SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 29 m Cu 0m 0m 77 m Cu 52 m Cu 60 m Cu
L.Max prot. 62 m (DU) 64 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,31 % 2,64 % 0% 2,64 % 0% 2,64 % 0,81 % 3,46 % 1,34 % 3,98 %
LIAISON

Câble 2x1,5 5G10 4x1.5 3G1,5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15% TH <= 15%
iSW-NA DT40 DT40 Type AC iDT40K iDT40K
Protection
PROT.

Calibre IDn 40 A 10 A 25 A 300 mA 10 A 10 A


Ir Im / Isd 100 A 250 A 96 A 96 A
Affectation des phases 123 1 123 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 194
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR2.AS TR2.AS
RESEAU
C
Rég.de N TN SJDB1 4P3D
25 A
300 mA
Tension 400 V C C C C
-PRO|274 -PRO|268 -PRO|254 -PRO|270
2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L3 L2 L1 L1
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS/E5 TR2.AS/BS3 TR2.AS/E3 TR2.AS/E2 TR2.AS/BS1 TR2.AS/E1 TR2.AS_J002 SJDB2


ECL BAES ECL BUREAUX ECL BUREAUX BAES ECL LT JDB ECL
PARTAGES PARTAGES
Désignation
CIRCUIT

Nb Consommation 5 40W 1 8 40W 12 40W 1 2 72W 1 3kVA 0


Alimentation Normal Normal Normal Normal N et S
JdB Amont SJDB1 SJDB1 SJDB1 SJDB1 SJDB1 SJDB1
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 34 m Cu 42 m Cu 50 m Cu 59 m Cu 25 m Cu 22 m Cu 0m
L.Max prot. 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,36 % 3,00 % 0,79 % 3,43 % 1,26 % 3,91 % 0,15 % 2,79 % 0% 2,64 %
LIAISON

Câble 3G1,5 4x1.5 3G1,5 3G1,5 4x1.5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K iDT40K iDT40K iDT40K DT40 Type AC
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A 25 A 300 mA


Ir Im / Isd 96 A 96 A 96 A 96 A 250 A
Affectation des phases 3 2 1 1 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 195
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1 1
TR2.AS TR2.AS
RESEAU
Rég.de N TN SJDB2 SJDB2

Tension 400 V C C C C C C
-PRO|267 -PRO|260 -PRO|273 -PRO|256 -PRO|275 -PRO|257
2P1D 2P1D 2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L3 L1 L2 L3 L2 L1
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS/E8 TR2.AS/BS7 TR2.AS/E7 TR2.AS/E12 TR2.AS/E9 TR2.AS/BS10 TR2.AS/E10 TR2.AS/E11


ECL BAES ECL THIN & ECL SIEVING ROOM ECL BAES ECL SIEVING ROOM ECL SIEVING ROOM
POLISHED
Désignation
CIRCUIT

Nb Consommation 8 40W 1 9 37,2W 6 40W 4 40W 1 5 15W 6 40W


Alimentation Normal Normal Normal Normal Normal N et S
JdB Amont SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2 SJDB2
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 31 m Cu 69 m Cu 53 m Cu 48 m Cu 28 m Cu 35 m Cu 32 m Cu 41 m Cu
L.Max prot. 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,47 % 3,11 % 0,84 % 3,48 % 0,6 % 3,24 % 0,25 % 2,89 % 0,12 % 2,77 % 0,5 % 3,14 %
LIAISON

Câble 3G1,5 4x1.5 3G1,5 3G1,5 3G1,5 4x1.5 3G1,5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A 10 A 10 A
Ir Im / Isd 96 A 96 A 96 A 96 A 96 A 96 A
Affectation des phases 3 1 2 3 2 1

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 196
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1
TR2.AS TR2.AS
RESEAU
C
Rég.de N TN 4P3D SJDB3
25 A
300 mA
Tension 400 V C C
-PRO|266 -PRO|264
2P1D 2P1D
10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L1 L2 L
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS_J003 SJDB3 TR2.AS/BS13 TR2.AS/E13 TR2.AS/BS16 TR2.AS/E16 TR2.AS/BS18 TR2.AS/E18_1


JDB ECL BAES ECL ROCK LIBRARY BAES ECL SAMPLE BAES BP commande
RECEPTION télérupteur
Désignation
CIRCUIT

Nb Consommation 1 3kVA 0 1 8 40W 1 6 40W 1 1


Alimentation N et S Normal Normal
JdB Amont SJDB3 SJDB3 SJDB3 SJDB3 SJDB3 SJDB3
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 0m 32 m Cu 47 m Cu 12 m Cu 37 m Cu 33 m Cu 29 m Cu
L.Max prot. 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0% 2,64 % 0,75 % 3,39 % 0,45 % 3,09 %


LIAISON

Câble 4x1.5 3G1,5 4x1.5 3G1,5 4x1.5 4X1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
DT40 Type AC iDT40K iDT40K
Protection
PROT.

Calibre IDn 25 A 300 mA 10 A 10 A


Ir Im / Isd 250 A 96 A 96 A
Affectation des phases 123 1 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 197
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR2.AS TR2.AS
RESEAU
C
Rég.de N TN SJDB3 4P3D SJDB4
25 A
300 mA
Tension 400 V C C C C
-PRO|261 -PRO|272 -PRO|271 -PRO|259
2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS
1P
10 A
Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L1 L1 L3 L3
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS/E18 TR2.AS/E15 TR2.AS/BS17 TR2.AS/E17 TR2.AS/E14 TR2.AS_J004 SJDB4 TR2.AS/BS21


ECL CIRCULATION ECL SAMPLE BAES ECL SANITAIRES ECL ROCK LIBRARY JDB ECL BAES
RECEPTION
Désignation
CIRCUIT

Nb Consommation 8 15W 6 40W 1 11 8W 8 40W 1 3kVA 0 1


Alimentation Normal Normal Normal Normal N et S
JdB Amont SJDB3 SJDB3 SJDB3 SJDB3 SJDB3 SJDB4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 32 m Cu 36 m Cu 27 m Cu 33 m Cu 49 m Cu 0m 20 m Cu
L.Max prot. 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,18 % 2,82 % 0,43 % 3,07 % 0,15 % 2,79 % 0,79 % 3,43 % 0% 2,64 %
LIAISON

Câble 3G1,5 3G1,5 4x1.5 3G1,5 3G1,5 4x1.5


Neutre
Séparé
PE/PEN
Taux d'Harmonique TH <= 15%
iDT40K iDT40K iDT40K iDT40K DT40 Type AC
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A 25 A 300 mA


Ir Im / Isd 96 A 96 A 96 A 96 A 250 A
Affectation des phases 1 1 3 3 123

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 198
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1 1 1
TR2.AS TR2.AS
RESEAU
Rég.de N TN SJDB4 SJDB4

Tension 400 V C C C C C
-PRO|265 -PRO|269 -PRO|276 -PRO|258 -PRO|263
2P1D 2P1D 2P1D 2P1D 2P1D
10 A 10 A 10 A 10 A 10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS
1P 2P
10 A 16 A
Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L2 L1 L L3 L2 L3
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS/E21 TR2.AS/E23 TR2.AS/BS20 TR2.AS/DM20 TR2.AS/E20 TR2.AS/BS19 TR2.AS/E19 TR2.AS/E22


ECL RECEPTION ECL SPACE BAES ECL CIRCULATIONS ECL CIRCULATION ECL CIRCULATIONS ECL CIRCULATION ECL HALL

Désignation
CIRCUIT

Nb Consommation 6 15W 4 20W 1 1 8 15W 1 7 15W 4 15W


Alimentation Normal Normal Normal Normal Normal
JdB Amont SJDB4 SJDB4 SJDB4 SJDB4 SJDB4 SJDB4 SJDB4 SJDB4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 27 m Cu 63 m Cu 13 m Cu 26 m Cu 28 m Cu 21 m Cu 26 m Cu 35 m Cu
L.Max prot. 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC) 67 m (CC)

DU Circuit DU Totale 0,1 % 2,74 % 0,19 % 2,83 % 0,14 % 2,78 % 0,13 % 2,77 % 0,07 % 2,71 %
LIAISON

Câble 3G1,5 3G1,5 4x1.5 4x1.5 3G1,5 4x1.5 3G1,5 3G1,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K iDT40K iDT40K iDT40K iDT40K
Protection
PROT.

Calibre IDn 10 A 10 A 10 A 10 A 10 A
Ir Im / Isd 96 A 96 A 96 A 96 A 96 A
Affectation des phases 2 1 3 2 3

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 199
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126
Révision 1 1 1
TR2.AS
RESEAU
C C
Rég.de N TN SJDB4 2P1D 2P1D
16 A 16 A
30 mA 30 mA
Tension 400 V C

2P1D
10 A
DISTRIBUTION
Normal TG.NS-3A_T2
Amont
Secours TG.NS-3A_T2

Repère TR2.AS
Désignation
TAB.ELEC TR2.AS

Normal Secours

I Totale 12,63 A 12,63 A

I installée 6,12 A 0,30 A

Ik3 max 4042 A 3739 A


L2 L3 L2
Ik1 max 2066 A 2041 A

DU max 2,64 % 1,85 %

Repère TR2.AS/E24 TR2.AS/PE44 TR2.AS/PE45


ECL RECEPTION PC PELLETS & PC SAMPLE,
FUSION BEADS RECEPTION,
Désignation WORKSHOP STORAGE
CIRCUIT

Nb Consommation 9 15W 5 250W 4 250W


Alimentation Normal Normal Normal
JdB Amont SJDB4
Type U1000R2V (90°C) U1000R2V (90°C) U1000R2V (90°C)

Longueur Ame 25 m Cu 63 m Cu 45 m Cu
L.Max prot. 67 m (CC) 64 m (CC) 64 m (CC)

DU Circuit DU Totale 0,16 % 2,80 % 0,74 % 3,38 % 0,35 % 2,99 %


LIAISON

Câble 3G1,5 3G2,5 3G2,5


Neutre
Séparé
PE/PEN
Taux d'Harmonique
iDT40K DT40 Type AC DT40 Type AC
Protection
PROT.

Calibre IDn 10 A 16 A 30 mA 16 A 30 mA
Ir Im / Isd 96 A 160 A 160 A
Affectation des phases 2 3 2

UM6P PST TRANCHE 2C 2 MAJ GENERALE 2 : Recolement Avis Technique ELIE


1 MAJ GENERALE : Recolement
Folio
0 PREMIERE EMISSION: Recolement AFFAIRE: Q5486
Unif.Chantier 8 circuits TR2.AS 200
Ind. MODIFICATIONS
PLAN: 09-SH-3A-3HJ-++-0015 384
Date : 23/10/2022 Norme : C1510018
Fichier : PST-PEO-BYM-09-SH-3A-3HJ-++-0015-2_NC BT 3A3HJ.afr ©ALPI Caneco BT 5.90 Cracked by gta126