Académique Documents
Professionnel Documents
Culture Documents
Reserve 1
Calcul du débit d’extraction
S = 506m2
H = 3.2m
V=S×H
V = 506× 3.2
= 1620m3
3
Qext = 1620× 12 = 19440m /h
Caisson
Qext = 19440 × 1.2 = 23328m3/h (Majoration fuites gaines).
Qan= 11664m3/h
Caisson
Qext =11664 × 1.2 = 13997m3/h (Majoration fuites gaines).
Archive 6
S = 234m2
H = 3.2m
V=S×H
V = 234 × 3.2
= 749m3
✶
Qan= 0.6 x Qex
Qan= 5392m3/h
Caisson
Qext = 5392× 1.2 = 6471m3/h (Majoration fuites gaines).
Zone 2
S = 263m2
H = 3.2m
V=S×H
V = 263 × 3.2
= 841.6m3
Qan= 6060m3/h
Caisson
Qext = 6060 × 1.2 = 7272m3/h (Majoration fuites gaines).
Couloir 1
Hypothèse :
Le couloir 1 est donné sur le grillage des geôles, donc on va la considéré comme locale de 306 m2
S = 306m2
H = 3.2m
V=S×H
V = 306× 3.2
= 979m3
3
Qext = 979 × 12 = 11772m3 /h
Caisson
Qext = 11772 × 1.2 = 14127m3/h (Majoration fuites gaines).
Qan= 7064m3/h
✶
Caisson
Qext = 7064 × 1.2 = 8477m3/h (Majoration fuites gaines).
Couloir 5, 7, 12, 13
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 3
Qext = 3UP × 0,5 × 3600
= 5400m3/h
Caisson
Qext = 5400 × 1.2 = 6480 m3/h (Majoration fuites gaines).
Qan= 3240m3/h
Caisson
Qext = 9424 × 1.2 = 3888m3/h (Majoration fuites gaines).
Couloir 2
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 4
Qext = 4UP × 0,5 × 3600
= 7200m3/h
Caisson
Qext = 5400 × 1.2 = 8640 m3/h (Majoration fuites gaines).
Qan= 4320m3/h
Caisson
Qext = 4320 × 1.2 = 5184m3/h (Majoration fuites gaines).
Couloir 3, 4, 8, 11
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
✶
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 6
Qext = 6UP × 0,5 × 3600
= 10800m3/h
Caisson
Qext = 10800 × 1.2 = 12960 m3/h (Majoration fuites gaines).
Qan= 6480m3/h
Caisson
Qext = 6480 × 1.2 = 7776m3/h (Majoration fuites gaines).
Couloir 6&9
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 9
Qext = 9UP × 0,5 × 3600
= 16200m3/h
Caisson
Qext = 16200 × 1.2 = 19440 m3/h (Majoration fuites gaines).
Qan= 9720m3/h
Caisson
Qext = 9720 × 1.2 = 11664m3/h (Majoration fuites gaines).
Reserve 1
Calcul du débit d’extraction
✶
S = 409m2
H = 3.2m
V=S×H
V = 409 × 3.2
= 1309m3
3
Qext = 1309 × 12 = 15706m /h
Caisson
Qext = 15706 × 1.2 = 18848m3/h (Majoration fuites gaines).
Qan= 9424m3/h
Caisson
Qext = 9424 × 1.2 = 11309m3/h (Majoration fuites gaines).
Archive 6
S = 170m2
H = 3.2m
V=S×H
V = 170× 3.2
= 544m3
Caisson
Qext = 6528 × 1.2 = 7834 m3/h (Majoration fuites gaines).
Qan= 3917m3/h
Caisson
Qext = 5392× 1.2 = 6471m3/h (Majoration fuites gaines).
Zone 2
S = 263m2
H = 3.2m
V=S×H
✶
V = 263 × 3.2
= 841.6m3
Qan= 6060m3/h
Caisson
Qext = 6060 × 1.2 = 7272m3/h (Majoration fuites gaines).
Couloir 15
Hypothèse :
Le couloir 1 est donné sur le grillage des geoles, donc on va la considéré comme locale de 306 m2
S = 306m2
H = 3.2m
V=S×H
V = 306× 3.2
= 979m3
3
Qext = 979 × 12 = 11772m3 /h
Caisson
Qext = 11772 × 1.2 = 14127m3/h (Majoration fuites gaines).
Qan= 7064m3/h
Caisson
Qext = 7064 × 1.2 = 8477m3/h (Majoration fuites gaines).
Couloir 7, 12
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 3
Qext = 3UP × 0,5 × 3600
= 5400m3/h
Caisson
✶
Qext = 5400 × 1.2 = 6480 m3/h (Majoration fuites gaines).
Qan= 3240m3/h
Caisson
Qext = 9424 × 1.2 = 3888m3/h (Majoration fuites gaines).
Couloir 2
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 4
Qext = 4UP × 0,5 × 3600
= 7200m3/h
Caisson
Qext = 5400 × 1.2 = 8640 m3/h (Majoration fuites gaines).
Qan= 4320m3/h
Caisson
Qext = 9424 × 1.2 = 5184m3/h (Majoration fuites gaines).
nUP = 6
Qext = 6UP × 0,5 × 3600
= 10800m3/h
Caisson
Qext = 10800 × 1.2 = 12960 m3/h (Majoration fuites gaines).
✶
Qan= 0.6 x Qex
Qan= 6480m3/h
Caisson
Qext = 6480 × 1.2 = 7776m3/h (Majoration fuites gaines).
Couloir 6
Hypothèse :
Extraction // Amené d'air neuf : Mécanique// Mécanique
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 0.5m3/s x 3600
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP = 9
Qext = 9UP × 0,5 × 3600
= 16200m3/h
Caisson
Qext = 16200 × 1.2 = 19440 m3/h (Majoration fuites gaines).
Qan= 9720m3/h
Caisson
Qext = 9720 × 1.2 = 11664m3/h (Majoration fuites gaines).
Couloir 13
Hypothèse :
Extraction // Amené d'air neuf : Naturel// Naturel
Débit d'extraction en désenfumage en m3=h = Nombre des UP x 10 dm²
Débit d'air neuf (Air neuf naturel) = Débit d'extraction
nUP =3
Qext = 3UP × 10
= 30 dm²
✶
Qext = Sporte x Ves
Qext = 2 x 0.5
Qext. = 3600 m3/h
Le débit de fuites de portes fermées 100m3/h par porte
Qan. = 100 x 9
Qan = 900 m3/h
Le débit de soufflage dans le SAS égale au débit pénétré au CHC moins le débit d’escalier
Qan =7200-3600
3600m3/h
Le débit d’extraction de la circulation horizontale comune
=14040m3/h