238-4-DSE-003
Zishan Engineers (Pvt.) Ltd.
An ISO 9001-2015 certified company, Revision 0
47/F, Block 6, PECHS, Karachi-Pakistan
Tel: (92-21) 34393045-48 & 34310151-54 Date 08-11-2022
Fax: (92-21) 34533430 & 34310156
E-mail : contact@zishanengineers.com, Total Pages
Web : www.zishanengineers.com 18
(inc front cover)
COVERING NOTES
1 The ratings mentioned for components (combination fuse switch, contactor) are preliminary. Supplier to verify and provide the same
as per applicable IEC Standards
2 The protections mentioned in the SLDs shall be provided by the suppler in the form of Microprocessor based electronic protection
relay for incoming and buscoupler breaker/feeder protection.
3 Short circuit ratings, trip ratings and tripping time mentioned in datasheets and drawings are preliminary and shall be verified by
Contractor/Supplier through relevant system interlock studies (complete software based Power System Studies. Short Circuit ,
Load Flow,arc flash,protection cordination,harmonic filteration, that are supposed to be part of RFQ) specified in BOQ and Scope of
work.
4 EPR/soft starter of each motor circuit to be connected in a redundant Modbus RS-485 loop (perferably through daisy-chaining). All
internal modbus connection and wiring shall be provided as pre-installed by the supplier who shall bring out all such Rs-485
connections to a dedicated common terminal block, from where the tie in a PC along with all licensed software provided by bidder.
5 EPR shall also incorporate all metering functions, as required in relevant specifications, drawings and datasheet
6 As an alternate option to provide separate electronic EPR, supplier may incorporate the protection functions in soft starter module.
In this regards, supplier is encouraged to select a soft starter with builtin motor protection functions and metering functions.
8 The CTs quatities shown is minimum. Any other CTs requires shall be estimated by Vendor and same shall be deemed to be
included in the quoted price.
9 This datasheet shall be read in conjunction with SLD # 238-4-ELS-002.Document shall be read in conjunction with Specs
10 The main bus bar of MV switchgear shall be extendable both ways such that it shall remain suitable for tie-in with new MV panel
assembly .
11 Vendor shall seek client/consultant' approval on fabrication /wiring GA drawings complete in all respects prior to proceeding with
actual fabrication / Manufacturing. Also CT/VT sizing calculations to be submitted for client review & approval.
13 All energy analyzer shall be capable of Measurement of voltage, current, active & reactive power, frequency, active & reactive
energy, power factor, symmetry factor, voltage and current harmonics up to the 21st, total harmonic distortion.Communications:
PROFIBUS-DP, MODBUS RTU / ASCII or IEC communication protocol simple parameterization via front key or RS485
communication port Graphic display with background illumination with up to 20 programmable screens Real-time clock: Measured
values and states will be recorded with time stamps Recording and display of limit value violations and log entries Battery:
Recordings like limit value violations or energy counter values stay safely in the memory up to 1 months in case of a blackout.
14 Motor Protection function shall include Alarm and Trip for following (Overcurrent,Undercurrent,Current imbalance,
overload,Reset,Start-per-hour & etc).Phase Reversal, Thermal & etc
15 Metering Functions includes (Motor load,Current data,Thermal data,Start data,RTD data,Metering & etc)
16 HMI function Display includes (LCD display,Keypad,Status indications include,Fault display,Lockout display & etc)
17 Programmable Outputs includes (Rating,Run, speed,Acceleration,Deceleration & etc) & all necessary required SS feature suitable
reciprocroting compressor application.
18 Installation of Local manufactured CT/PT is not allowed.ALL Panel shall be type tested
19 Bidder to note that all upstream & downstream VCB earth switches are interlocked to avoid hot swtiching.Bidder is also
responsiable for providing all ATS which are mentioned in SLD,Specfication or required for completion of satisfactory operation.
20 Details of required motors data for sizing of Soft Starter will be provided at time of detailed engineering
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
2 Service Conditions
Max.
3 Ambient Temperature 47.2ºC
Min.
4 Min. 36 deg F 0ºC
Max./Min
5 Relative Humidity 90% 45%
Less than
6 Altitude 50 meters
7 Installation Indoor
12 Rated Short-time withstand current (25 kA HOLD), rms 3 sec (See Note 3)
29 Partition class PM
32 Serial No.
35 Shipping Dimensions
Remarks:
2 Service Conditions
Max.
3 Ambient Temperature 47.2ºC
Min.
4 Min. 36 deg F 0ºC
Max./Min
5 Relative Humidity 90% 45%
Less than
6 Altitude 50 meters
7 Installation Indoor
12 Rated Short-time withstand current (31.5 kA HOLD), rms 3 sec (See Note 3)
29 Partition class PM
32 Serial No.
35 Shipping Dimensions
Remarks:
15 VA Class 0.2 (AS PER IEC 60044-2) 0.2 (AS PER IEC 60044-2) 0.2 (AS PER IEC 60044-2)
16 VOLTAGE TRANSFORMERS FOR PROTECTION
Secondary
17 110/√3 110/√3 110/√3
18 VA Rating BY VENDOR AS PER ACTUAL VT BY VENDOR AS PER ACTUAL VT SIZING BY VENDOR AS PER ACTUAL VT SI
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE CALCULATION IN ACCORDANCE WITH
ACCORDANCE WITH THE INSTALLED INSTALLED BURDEN INSTALLED BURDEN
BURDEN
19 VA Class 3P 3P 3P
20 CURRENT TRANSFORMERS FOR METERING
Secondary
21 800/1 (VTC) 800/1 (VTC) 800/1 (VTC)
22 A Rating BY VENDOR AS PER ACTUAL VT BY VENDOR AS PER ACTUAL VT SIZING BY VENDOR AS PER ACTUAL VT SI
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE CALCULATION IN ACCORDANCE WITH
ACCORDANCE WITH THE INSTALLED INSTALLED BURDEN INSTALLED BURDEN
BURDEN
27 VA Class 5P 5P 5P
28 RELAYS (see note 2)
29 Overcurrent YES YES YES
30 Earth fault YES YES YES
31 Overvoltage YES YES YES
32 Undervoltage YES YES YES
33 Motor winding temp. alarm and trip relay
34 Motor protection relay
35 Tripcircuit monitoring relay
36 Under and over frequency relay YES YES YES
37 Lock-out relay YES YES YES
38 Automatic Transfer Scheme
39 Phase sequence relay YES YES YES
40 Synchro-check relay
41 Bucholz relay
42 Voltmeter
MEASURING AC AND INDICATING (see Note 5 &12)
5 OF 18
OUTGOING
2
VCB
800A
110/√3
BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN
110/√3
BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN
3P
800/1 (VTC)
BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN
0.5
800/1 (VTC)
BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN
5P
YES
YES
YES
YES
YES
YES
YES
YES
238-4-DSE-003
6 OF 18
YES
YES
YES
YES
YES
YES
YES
TBA
VTS
VTS
VTS
16 VA Class 0.2 (AS PER IEC 60044-2) 0.2 (AS PER IEC 60044-2)
17 VOLTAGE TRANSFORMERS FOR PROTECTION
Secondary
18 110/√3 110/√3
19 VA Rating BY VENDOR AS PER ACTUAL VT SIZING BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN INSTALLED BURDEN
20 VA Class 3P 3P
21 CURRENT TRANSFORMERS FOR METERING
Secondary
22 400/1 (VTC) 400/1 (VTC)
23 A Rating BY VENDOR AS PER ACTUAL VT SIZING BY VENDOR AS PER ACTUAL VT SIZING
CALCULATION IN ACCORDANCE WITH THE CALCULATION IN ACCORDANCE WITH THE
INSTALLED BURDEN INSTALLED BURDEN
28 VA Class 5P 5P
29 RELAYS (see note 2)
30 Overcurrent YES YES
31 Earth fault YES YES
32 Overvoltage YES YES
33 Undervoltage YES YES
34 Phase balance current protection YES YES
35 Incomplete sequence
36 Tripcircuit monitoring relay
37 Under and over frequency relay YES YES
38 Overload
39 Phase sequence relay YES YES
40 Lock-out relay YES YES
41 Automatic Transfer Scheme
42 Synchro-check relay
43 Bucholz relay
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
44 MEASURING
Voltmeter AC AND INDICATING (see Note 5 &12)
45 Energy Analyser (see Note 13) YES YES
46 YES YES
47 Ammeter AC YES YES
48 Frequency meter YES YES
49 Power-factor meter YES YES
50 Ammeter DC
51 Wattmeter
52 Reactive volt-ampere meter
53 Watt-hour meter
54 Maximum-demand indicator
55 INDICATION LAMPS
56 Open YES YES
57 Close YES YES
58 Fault YES YES
59 Others Motor Charging, Earth Switch, Test etc YES YES
60 MAIN TERMINALS
61 Incoming / Outgoing Cable Entry TBA TBA
62 Cable data VTS VTS
63 Size VTS VTS
64 Specification VTS VTS
65 CONTROL AND CT CABLE TERMINALS
66 Control Cable : Size and quantity (see note 4) To PMS By Supplier To PMS By Supplier
67 CT Cable: Size VTS VTS
REMARKS:
Vendor shall complete DATA SHEET
TBC=To Be Confirmed, NA=Not Applicable, TBA=To Be Advised, VTS=Vendor To Specify
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
2 Quantity 2 nos
3 Panel identification number
4 Type of switching device VCB
Rated current switching device
5 630A
A Rated current MV fuses fuses (see Note 1)
6
7 Rated voltage 7.2 kV
8 Operating voltage 6.6 kV
9 Rated frequency 50 Hz
10 Rated short-duration power-freq. withstand voltage 20 kV
11 Rated lightning impulse withstand voltage 60 kV
12 Busbar insulation VTS
13 VOLTAGE TRANSFORMERS FOR METERING
Secondary
14 110/√3
15 VA Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
20 VA Class 3P
21 CURRENT TRANSFORMERS FOR METERING
Secondary
22 400/1 (VTC)
23 A Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
24 VA Class 0.5
25 CURRENT TRANSFORMERS FOR PROTECTION
Ratio
26 400/1 (VTC)
27 Amp Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
28 VA Class 5P
29
30 RELAYS (see note 2)
31 Overcurrent YES
32 Earth fault YES
33 Overvoltage YES
34 Undervoltage YES
35 Phase balance current protection YES
36 Incomplete sequence
37 Tripcircuit monitoring relay
38 Under and over frequency relay YES
39 Phase sequence relay YES YES
40 Overload
41 Lock-out relay YES
42 Automatic Transfer Scheme YES
43 Synchro-check relay
44 Bucholz relay YES
45 Voltmeter
MEASURING AC AND INDICATING (see Note 5 &12)
2 Quantity 1 nos
3 Panel identification number
4 Type of switching device VCB
Rated current switching device
5 630A
A Rated current MV fuses (see Note 1)
6
7 Rated voltage 7.2 kV
8 Operating voltage 6.6 kV
9 Rated frequency 50 Hz
10 Rated short-duration power-freq. withstand voltage 20 kV
11 Rated lightning impulse withstand voltage 60 kV
12 Busbar insulation VTS
13 VOLTAGE TRANSFORMERS FOR METERING
Secondary
14 VTS
VA Rating
15 VTS
16 VA Class VTS
17 VOLTAGE TRANSFORMERS FOR PROTECTION
Secondary
18 VTS
VA Rating
19 VTS
20 VA Class VTS
21 CURRENT TRANSFORMERS FOR METERING
Secondary
22 VTS
A Rating
23 VTS
24 VA Class VTS
25 CURRENT TRANSFORMERS FOR PROTECTION
Ratio
26 VTS
Amp Rating
27 VTS
28 VA Class VTS
29
30 RELAYS (see note 2)
31 Overcurrent YES
32 Earth fault YES
33 Overvoltage
34 Undervoltage
35 Phase balance current protection
36 Incomplete sequence
37 Tripcircuit monitoring relay
38 Under and over frequency relay
39 Overload
40 Lock-out relay YES
41 Automatic Transfer Scheme YES
42 Synchro-check relay
43 Bucholz relay
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
44 MEASURING
Voltmeter AC AND INDICATING (see Note 5 &12)
45 Energy Analyser (see Note 13) VTS
46 YES
47 Ammeter AC YES
48 Frequency meter YES
49 Power-factor meter YES
50 Ammeter DC
51 Wattmeter
52 Reactive volt-ampere meter
53 Watt-hour meter
54 Maximum-demand indicator
55 INDICATION LAMPS
56 Open YES
57 Close YES
58 Fault YES
59 Others Motor Charging, Earth Switch, Test etc YES
60 MAIN TERMINALS
61 Incoming / Outgoing Cable Entry TBA
62 Cable data VTS
63 Size VTS
64 Specification VTS
65 CONTROL AND CT CABLE TERMINALS
66 Control Cable : Size and quantity (see note 4) To PMS By Supplier
67 CT Cable: Size VTS
REMARKS:
Vendor shall complete DATA SHEET
TBC=To Be Confirmed, NA=Not Applicable, TBA=To Be Advised, VTS=Vendor To Specify
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
2 Quantity 1 nos
3 Panel identification number
4 Type of switching device VCB
Rated current switching device
5 630A
A Rated current MV fuses (see Note 1)
6
7 Rated voltage 7.2 kV
8 Operating voltage 6.6 kV
9 Rated frequency 50 Hz
10 Rated short-duration power-freq. withstand voltage 20 kV
11 Rated lightning impulse withstand voltage 60 kV
12 Busbar insulation VTS
13 VOLTAGE TRANSFORMERS FOR METERING
Secondary
14 110/√3
15 VA Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
20 VA Class 3P
21 CURRENT TRANSFORMERS FOR METERING
Secondary
22 400/1 (VTC)
23 A Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
24 VA Class 0.5
25 CURRENT TRANSFORMERS FOR PROTECTION
Ratio
26 400/1 (VTC)
27 Amp Rating BY VENDOR AS PER ACTUAL VT SIZING CALCULATION IN ACCORDANCE WITH
THE INSTALLED BURDEN
28 VA Class 5P
29
30 RELAYS (see note 2)
31 Overcurrent YES
32 Earth fault YES
33 Overvoltage YES
34 Undervoltage YES
35 Phase balance current protection YES
36 Incomplete sequence
37 Tripcircuit monitoring relay
38 Under and over frequency relay YES
39 Overload
40 Lock-out relay YES
41 Automatic Transfer Scheme YES
42 Synchro-check relay
43 Bucholz relay
CLIENT ENAR PETROLEUM REFINING FACILITY DOCUMENT NO. 238-4-DSE-003
44 Voltmeter
MEASURING AC AND INDICATING (see Note 5 &12)
23 VA Class 0.2 (AS PER IEC 60044-2) 0.2 (AS PER IEC 60044-2)
24 VOLTAGE TRANSFORMERS FOR PROTECTION
25 Secondary 110/√3 OR 120/√3 V 110/√3 OR 120/√3 V
26 VA Rating BY VENDOR AS PER ACTUAL VT BY VENDOR AS PER ACTUAL VT SIZING
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE
ACCORDANCE WITH THE INSTALLED INSTALLED BURDEN
BURDEN
27 VA Class 3P 3P
28 CURRENT TRANSFORMERS FOR METERING
29 Secondary 100/1 (VTC) 100/1 (VTC)
30 A Rating BY VENDOR AS PER ACTUAL CT BY VENDOR AS PER ACTUAL CT SIZING
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE
ACCORDANCE WITH THE INSTALLED INSTALLED BURDEN
BURDEN
35 VA Class 5P 5P
36 SOFT STARTER
37 Soft starter Required Required
38 Starting Current 200–600% 200–600%
39 Motor Protection Functions (see note 14) Required Required
40 Metering Functions (see note 15) Required Required
41 Communication Hard wire,Modbus,RS-485,RS-422,RS- Hard wire,Modbus,RS-485,RS-422,RS-232 & etc
232 & etc
42 HMI (see note 16) Required Required
43 Programmable Outputs (see note 17) Required Required
23 VA Class 0.2 (AS PER IEC 60044-2) 0.2 (AS PER IEC 60044-2)
24 VOLTAGE TRANSFORMERS FOR PROTECTION
25 Secondary 110/√3 OR 120/√3 V 110/√3 OR 120/√3 V
26 VA Rating BY VENDOR AS PER ACTUAL VT BY VENDOR AS PER ACTUAL VT SIZING
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE
ACCORDANCE WITH THE INSTALLED BURDEN
INSTALLED BURDEN
27 VA Class 3P 3P
28 CURRENT TRANSFORMERS FOR METERING
29 Secondary 100/1 VTC 100/1 VTC
30 A Rating BY VENDOR AS PER ACTUAL VT BY VENDOR AS PER ACTUAL VT SIZING
SIZING CALCULATION IN CALCULATION IN ACCORDANCE WITH THE
ACCORDANCE WITH THE INSTALLED BURDEN
INSTALLED BURDEN
35 VA Class 5P 5P
36 SOFT STARTER
37 Soft starter Required Required
38 Starting Current 200–600% 200–600%
39 Motor Protection Functions (see note 14) Required Required
40 Metering Functions (see note 15) Required Required
41 Communication Hard wire,Modbus,RS-485,RS- Hard wire,Modbus,RS-485,RS-422,RS-232 & etc
422,RS-232 & etc