Vous êtes sur la page 1sur 2

Characteristics :

Reference ATS-48C17Y-
Control Voltage 230/400 Vac
Current Rating MAX 170 A
Nominal Current 156 A
Structure :
Device ATS-48C17Y-
Serial Number XX X0 07 340 037
Version V1.1IEXX
Vendor Name TELEMECANIQUE
Serial Number XX X0 03 103 415
Version V1.1IEXX
Vendor Name
Power Board
Serial Number XX X0 FF FFF FFF
Version V1.1IEXX
Vendor Name
Configurations :
Software Release : 1.9.2.0

Settings parameters list

Code Long Label Current Value Default Value Min Value Max Value Logical address
>Â Â Settings
 In  Motor nominal current  88.4 A  156.0 A  68.0 A  221.0 A  4026Â
 ILt  Coefficient of current limit  400 %    400 %  150 %  700 %  4039Â
 ACC  Acceleration ramp time  10 s  15 s  1 s  60 s  4043Â
 tQ0  Initial torque on starting  15 %  20 %  0 %  100 %  4037Â
 StY  Choice of stop type  Freewheel stop    Freewheel stop  4029Â
 dEC  Deceleration ramp time  15 s    15 s  1 s  60 s  4044Â
 EdC  Freewheel thr'hld on braking  20 %    20 %  0 %  100 %  4038Â
 EbA  Pseudo DC braking level  20 %    20 %  20 %  100 %  4042Â
 brC  Int level of braking torque  50 %    50 %  0 %  100 %  4041Â
>Â Â 2nd motor parameters
 In2  Motor 2 nominal current  156.0 A Â  156.0 A  68.0 A  221.0 A  4300Â
 IL2  Motor 2 current limit  400 % Â  400 %  150 %  544 %  4304Â
 AC2  Motor 2 Acceleration time  15 s Â  15 s  1 s  60 s  4305Â
 tQ2  Motor 2 starting torque  20 % Â  20 %  0 %  100 %  4302Â
 dE2  Motor 2 deceleration time  15 s Â  15 s  1 s  60 s  4306Â
 Ed2  Freewheel level dec2  20 % Â  20 %  0 %  100 %  4303Â
 tL2  Motor 2 Torque limit  Off Â  Off  10 %  200 %  4301Â
 tI2  Motor 2 decel loop gain  40 % Â  40 %  10 %  50 %  4307Â
>Â Â Advanced protections
 tHP  Motor thermal protection  10    10  4034Â
 PtC  Activate PTC protection  OFF    OFF  4106Â
 OIL  I overcurrent threshold  Fault  OFF  OFF  Alarm  4108Â
 LOC  Overcurrent level  125 %  80 %  50 %  300 %  4109Â
 tOL  Overcurrent time  10.0 s    10.0 s  0.1 s  60.0 s  4110Â
 ULL  Underload activation  Alarm  OFF  OFF  Alarm  4103Â
 LUL  Underload threshold  60 %    60 %  20 %  100 %  4104Â
 tUL  Underload time  60 s    60 s  1 s  60 s  4105Â
 PHL  Phase loss level  10 %    10 %  5 %  10 %  4101Â
 PHP  Phase Loss Activation  On    On  Off  Off  4102Â
 PHr  Phase rotation protection  123  No  4030Â
 tbS  Time before starting  2 s    2 s  0 s  999 s  4032Â
 tLS  Start too long  Off    Off  10 s  999 s  4033Â
 ArS  Automatic restart  Off    Off  4100Â
>Â Â Advanced IO
 LI3  Logic Input LI3 assignment  Fault reset  force freewheel  4022Â
 LI4  Logic Input LI4 assignment  Forced local    Forced local  4048Â
 r1  Relay R1  Relay fault Â  Relay fault  4050Â
 r3  Relay R3 assignment  Motor powered Â  Motor powered  4052Â
 IPr  Motor preheat level  0 % Â  0 %  0 %  100 %  4045Â
 tPr  Time before preheat  5 min Â  5 min  0 min  999 min  4046Â
 LO1  Logic Output LO1 assignment  Mot therm alarm Â  Mot therm alarm  4023Â
 LO2  Logic Output LO2 assignment  Motor powered Â  Motor powered  4049Â
 AO  Analogue output AO assign  Motor current Â  Motor current  4024Â
 0_4  AO scaling  020 Â  020  4053Â
 ASC  Analogue output scaling AO  200 % Â  200 %  50 %  500 %  4025Â
>Â Â Advanced communication
 Add  Starter address  2  0  0  31  2290Â
 tbr  Baud rate  19.2    19.2  2292Â
 For  Communication protocol  8E1  8n1  2293Â
 tLP  Time-Out  5.0 s    5.0 s  0.1 s  60.0 s  2295Â
>Â Â Advanced setting
 tLI  Torque limit  Off Â  Off  10 %  200 %  4036Â
 bSt  Voltage boost level  Off Â  Off  Off  100 %  4028Â
 dLt  Start in delta configuration  off Â  off  4054Â
 SSt  Test on low power motor  off Â  off  4057Â
 CLP  Torque control  on Â  on  4107Â
 LSC  Stator loss compensation  50 % Â  50 %  0 %  90 %  4027Â
 tIG  Braking loop gain  40 % Â  40 %  10 %  50 %  4047Â
 CSC  Activate cascade function  Off Â  Off  4058Â
 Uln  Line Voltage  460 V  400 V  180 V  750 V  4055Â
 FrC  Supply frequency  Auto detection    Auto detection  4056Â