LIST OF PANEL

Đơn Số
Stt Nội dung Nhà sản xuất Ghi chú
vị lượng
I MAIN SWITCHBOARD

1 MSB-TX-2 EDHP/VN Tủ 1 BUSDUCT


2 MSB_TX_5 (MSB_BAKUP) EDHP/VN Tủ 1 BUSDUCT
3 MSB_TX_1 EDHP/VN Tủ 1 BUSDUCT
4 MSB-G-IT-A EDHP/VN Tủ 1 BUSDUCT
5 MSB-G-IT-B EDHP/VN Tủ 1 BUSDUCT
6 MSB-G-M-A EDHP/VN Tủ 1 BUSDUCT
7 MSB-G-M-B EDHP/VN Tủ 1 BUSDUCT
8 MSB-F2-GL EDHP/VN Tủ 1 ATS Neutral Overlaping

II SSB/ MPB/ DB BOARD

9 ATS-IT-F3A CET/VN Tủ 1 ATS, BUSDUCT


10 ATS-IT-F3B CET/VN Tủ 1 ATS, BUSDUCT
11 SB-PDU-F3-A CET/VN Tủ 1 BUSDUCT
12 SB-PDU-F3-B CET/VN Tủ 1 BUSDUCT
13 SB-MBL-BF-B CET/VN Tủ 1 Wrong name (SB-MBL-1F-B)
14 SB-MBL-BF-A CET/VN Tủ 1 Wrong name (SB-MBL-1F-A)
15 SB-MBL-F1-B CET/VN Tủ 1 ATS Neutral Overlaping, BUSDUCT
16 SB-MBL-F1-A CET/VN Tủ 1 ATS Neutral Overlaping, BUSDUCT
17 SB-MBL-F1-CH-B CET/VN Tủ 1 ACB - ATS, BUSDUCT
18 SB-MBL-F1-CH-A CET/VN Tủ 1 ACB - ATS, BUSDUCT
CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 1
Đơn Số
Stt Nội dung Nhà sản xuất Ghi chú
vị lượng
19 SB-MBL-F3B CET/VN Tủ 1 ATS
20 SB-MBL-F3A CET/VN Tủ 1 ATS
21 CP-CME-F1B CET/VN Tủ 1
22 CP-CME-F1A CET/VN Tủ 1
23 CP-CME-F3B CET/VN Tủ 1
24 CP-CME-F3A CET/VN Tủ 1
25 DB-MBL-BF CET/VN Tủ 1 ATS
26 DB-MBL-F1 CET/VN Tủ 1 ATS
27 DB-MBL-F3 CET/VN Tủ 1 ATS
28 CP-CH-F1-01 CET/VN Tủ 1 ATS Neutral Overlaping
29 CP-CH-F1-02 CET/VN Tủ 1 ATS Neutral Overlaping
30 SB-CHWP-F1-A CET/VN Tủ 1
31 SB-CHWP-F1-B CET/VN Tủ 1
32 CP-CHWP-F1-01 CET/VN Tủ 1 ATS
33 CP-CHWP-F1-02 CET/VN Tủ 1 ATS
34 SP-CDH-F3B CET/VN Tủ 1
35 SP-CDH-F3A CET/VN Tủ 1
36 SB-SP-BF-B CET/VN Tủ 1 Wrong name (SB-SP-1F-B)
37 SB-SP-BF-A CET/VN Tủ 1 Wrong name (SB-SP-1F-A)
38 SB-PPC-A CET/VN Tủ 1
39 SB-PPC-B CET/VN Tủ 1
40 SB-MNBL-F2-B CET/VN Tủ 1
41 SB-MNBL-F2-A CET/VN Tủ 1
CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 2
Đơn Số
Stt Nội dung Nhà sản xuất Ghi chú
vị lượng
42 CP-CME-UPS-F2-B CET/VN Tủ 1
43 CP-CME-UPS-F2-A CET/VN Tủ 1
44 SB-F1-B CET/VN Tủ 1
45 SB-F1-A CET/VN Tủ 1
46 CP-DP-F1-B CET/VN Tủ 1
47 CP-DP-F1-A CET/VN Tủ 1
48 DB-GL-BF CET/VN Tủ 1
49 DB-GL-F1 CET/VN Tủ 1
50 DB-GL-F3~6 CET/VN Tủ 4
51 DB-GL-RT CET/VN Tủ 1
52 DB-COM-F3~6 CET/VN Tủ 4
53 DB-COM-F2 CET/VN Tủ 1
54 DB-OFFICE-F2 CET/VN Tủ 1
55 DB-CL-OFFICE-F2 CET/VN Tủ 1
56 SB-SE-F1 CET/VN Tủ 1 ATS
57 SB-GH/SO-F1A CET/VN Tủ 1
58 SB-GH/SO-F1B CET/VN Tủ 1
59 DB-GL-RT-L CET/VN Tủ 1
60 SB-SCC-F2A CET/VN Tủ 1
61 SB-SCC-F2B CET/VN Tủ 1
62 SB-GS-F1-A CET/VN Tủ 1
63 SB-GS-F1-B CET/VN Tủ 1
64 SB-GS-F2-A CET/VN Tủ 1
CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 3
Đơn Số
Stt Nội dung Nhà sản xuất Ghi chú
vị lượng
65 SB-GS-F2-B CET/VN Tủ 1
66 SB-GS-F3-A CET/VN Tủ 1
67 SB-GS-F3-B CET/VN Tủ 1
68 CP-GS-F2-B CET/VN Tủ 1
69 CP-GS-F2-A CET/VN Tủ 1
70 DB_COM_L_F3 CET/VN Tủ 1
71 DB_DHL_L_F3 CET/VN Tủ 1
72 DB_DHL_L_F2 CET/VN Tủ 1
73 DB_DHL_F3 CET/VN Tủ 1
74 MCCB BOX 40A CET/VN Tủ 4
75 MCCB BOX 63A CET/VN Tủ 1
76 CP_CT_RT_01 CET/VN Tủ 1
77 CP_CT_RT_02 CET/VN Tủ 1
78 CP_CDWP _F1_01 CET/VN Tủ 1
79 CP_CDWP _F1_02 CET/VN Tủ 1
80 CP_FAN_RT CET/VN Tủ 1
81 DB_FFP CET/VN Tủ 1
82 CP_MUWP_1A,1B,2A,2B CET/VN Tủ 4

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 4


DRAWING NO. 1202
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

1 MSB_TX_2 MAIN 1,555.54


3P4W 380/220V
INCOMING Q01 From TRF02 (3125KVA) ACB 4P 5000 5000 100 LISG O O 4P+E(50%) - 4W3P, 5000A CU BUSDUCT
Q02 From TRF05 (3125KVA) ACB 4P 5000 5000 100 LISG O O 5000A COPPER BUSBARS

SSD 100kA MCCB 3P 100 100 120 TMA

CAPACITOR BANK MAIN ACB 3P 2000 2000 85 LI


(24 sets x 50kVAr) 1~24 MCCB 3P 125 125 36 TMD X 24 sets of MCCB, Contactor, Reactor & Capacitor

OUTGOING
R01 SB_MBL_F1_CH_A ACB 4P 4000 4000 85 LISG O O 845.20 4P+E(50%) - 4W3P, 4000A CU BUSDUCT
R02 SB_MBL_F1_CH_B ACB 4P 4000 4000 85 LISG O O 825.20 4P+E(50%) - 4W3P, 4000A CU BUSDUCT
CHỈ CHẠY TẢI A HOẶC B
R03 SB_MBL_F1_A ACB 4P 2500 2000 85 LISG O O 710.34 4P+E(50%) - 4W3P, 2000A CU BUSDUCT
R04 SB_MBL_F1_B ACB 4P 2500 2000 85 LISG O O 709.54 4P+E(50%) - 4W3P, 2000A CU BUSDUCT

TOTAL 3,090.28

2 MSB_TX_5 MAIN 3,087.54


3P4W 380/220V
INCOMING Q01 From TRF05 (3125KVA) ACB 4P 5000 5000 100 LISG O O 4P+E(50%) - 4W3P, 5000A CU BUSDUCT
CẤP DỰ PHÒNG CHO CẢ
MSB_TX_1&2
SSD 100kA MCCB 3P 100 100 120 TMA

R01 TO MSB_TX1 & TX2 5000A COPPER BUSBARS

TOTAL 1,555.54

3 MSB_TX_1 MAIN 1,532.00


3P4W 380/220V
INCOMING Q01 From TRF01 (3125KVA) ACB 3P+N 5000 5000 100 LISG O O 4P+E(50%) - 4W3P, 5000A CU BUSDUCT
Q02 From TRF05 (3125KVA) ACB 3P+N 5000 5000 100 LISG O O 5000A COPPER BUSBARS

SSD 100kA MCCB 3P 100 100 120 TMA

OUTGOING
R01 ATS_IT_F3A ACB 3P 2500 2500 85 LISG O O 1,532.00 CHỈ CHẠY TẢI A HOẶC B 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
R02 ATS_IT_F3B ACB 3P 2500 2500 85 LISG O O 1,532.00 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
R03 ACB SOCKET for ATS_IT_F6A (FUTURE) ACB 3P 2500 85 LSIG 3P+E(50%) - 3W3P, 2000A CU BUSDUCT
R04 ACB SOCKET for ATS_IT_F6B (FUTURE) ACB 3P 2500 85 LSIG 3P+E(50%) - 3W3P, 2000A CU BUSDUCT

TOTAL 3,064.00

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 5


DRAWING NO. 1203
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

4 SB_PDU_F3_A MAIN 1,453.00


3P3W 380V
INCOMING Q01 ATS_IT_F3B_R01 External Bypass DS 3P 2500 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
Q02 UPS F3_A_4 / ATS_IT_F3A_R02 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q03 UPS F3_A_3 / ATS_IT_F3A_R03 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q04 UPS F3_A_2 / ATS_IT_F3A_R04 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q05 UPS F3_A_1 / ATS_IT_F3A_R05 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120

SSD 100kA MCCB 3P 100 100 120 TMA

OUTGOING R01 PDU_F3_A_1 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R02 PDU_F3_A_2 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R03 PDU_F3_A_3 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R04 PDU_F3_A_4 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R05 PDU_F3_A_5 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R06 PDU_F3_A_6 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R07 PDU_F3_A_7 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R08 Network/MMR room 01 F3 B MCCB 3P 16 16 18 TMD 9.00 0.99 CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
R09 Network/MMR room 02 F3 B MCCB 3P 16 16 18 TMD 9.00 0.99 CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5

TOTAL 0.00 0.00 0.00 1,453.00

5 ATS_IT_F3A MAIN 1,532.00


3P3W 380V
INCOMING Q01 From MSB_TX_1_R01 DS 3P 2500 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
Q02 From MSB_G_IT_A_R01 DS 3P 2500 3P+E(50%) - 3W3P, 2500A AL BUSDUCT
Q ATS ATS 3P 2500 O

OUTGOING R01 SB_PDU_F3_A External Bypass ACB 3P 2500 2500 50 LSIG O O 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
R02 UPS F3_A_4 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R03 UPS F3_A_3 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R04 UPS F3_A_2 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R05 UPS F3_A_1 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R06 Batteries Rectifier A MCCB 3P 250 200 36 LSI O 92.00 CU/XLPE/PVC 1C-95mm2 x3 + E 1C-50

TOTAL 0.00 0.00 0.00 1,532.00

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 6


DRAWING NO. 1204
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

6 SB_PDU_F3_B MAIN 1,453.00


3P3W 380V
INCOMING Q01 ATS_IT_F3B_R01 External Bypass DS 3P 2500 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
Q02 UPS F3_B_4 / ATS_IT_F3B_R02 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q03 UPS F3_B_3 / ATS_IT_F3B_R03 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q04 UPS F3_B_2 / ATS_IT_F3B_R04 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
Q05 UPS F3_B_1 / ATS_IT_F3B_R05 ACB 3P 1000 800 50 LSIG O O CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120

SSD 100kA MCCB 3P 100 100 120 TMA

OUTGOING R01 PDU_F3_B_1 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R02 PDU_F3_B_2 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R03 PDU_F3_B_3 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R04 PDU_F3_B_4 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R05 PDU_F3_B_5 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R06 PDU_F3_B_6 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R07 PDU_F3_B_7 MCCB 3P 400 400 36 LSI O 205.00 0.99 CU/XLPE/PVC 1C-240mm2 x3 + E 1C-120
R08 Network/MMR room 01 F3 B MCCB 3P 16 16 18 TMD 9.00 0.99 CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
R09 Network/MMR room 02 F3 B MCCB 3P 16 16 18 TMD 9.00 0.99 CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5

TOTAL 0.00 0.00 0.00 1,453.00

7 ATS_IT_F3B MAIN 1,532.00


3P3W 380V
INCOMING Q01 From MSB_TX_1_R02 DS 3P 2500 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
Q02 From MSB_G_IT_B_R05 DS 3P 2500 3P+E(50%) - 3W3P, 2500A AL BUSDUCT
Q ATS ATS 3P 2500 O

OUTGOING R01 SB_PDU_F3_B External Bypass ACB 3P 2500 2500 50 LSIG O O 3P+E(50%) - 3W3P, 2500A CU BUSDUCT
R02 UPS F3_B_4 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R03 UPS F3_B_3 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R04 UPS F3_B_2 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R05 UPS F3_B_1 ACB 3P 1000 800 50 LSIG O O 360.00 CU/XLPE/PVC (3x1C-240mm2)x3 + E 3x1C-120
R06 Batteries Rectifier B MCCB 3P 250 200 36 LSI O 92.00 CU/XLPE/PVC 1C-95mm2 x3 + E 1C-50

TOTAL 0.00 0.00 0.00 1,532.00

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 7


DRAWING NO. 1207
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

8 MSB_G_IT_A MAIN 1,532.00


3P3W 380V
INCOMING Q01 From AMF_IT_1_R01 ACB 3P 3200 3200 85 LSIG O O 3P+E(50%) - 3W3P, 3200A AL BUSDUCT
Q02 ACB SOCKET from AMF_IT_2 (FUTURE) ACB 3P 3200 85 LSIG `
Q03 ACB SOCKET from AMF_IT_3 (FUTURE) ACB 3P 3200 85 LSIG
Q04 ACB SOCKET from AMF_IT_4 (FUTURE) ACB 3P 3200 85 LSIG
Q05 From AMF_IT_5_R01 ACB 3P 3200 3200 85 LSIG O O 3P+E(50%) - 3W3P, 3200A AL BUSDUCT

C TO MSB_G_IT_B DS 4P 6300 6300A COPPER BUSBARS

OUTGOING R01 ATS_IT_F3A ACB 3P 2500 2500 O O 1,532.00 3P+E(50%) - 3W3P, 2500A AL BUSDUCT
R02 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R03 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R04 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R05 ACB SOCKET from FUTURE ACB 3P 1000 85 LSIG

TOTAL 0.00 0.00 0.00 1,532.00

9 MSB_G_IT_B MAIN 1,532.00


3P3W 380V
INCOMING Q01 From AMF_IT_5_R02 ACB 3P 3200 3200 85 LSIG O O 3P+E(50%) - 3W3P, 3200A AL BUSDUCT
Q02 ACB SOCKET from AMF_IT_2 (FUTURE) ACB 3P 3200 SOCKET 85 LSIG `
Q03 ACB SOCKET from AMF_IT_3 (FUTURE) ACB 3P 3200 SOCKET 85 LSIG
Q04 ACB SOCKET from AMF_IT_4 (FUTURE) ACB 3P 3200 SOCKET 85 LSIG
Q05 From AMF_IT_5_R02 ACB 3P 3200 3200 85 LSIG O O 3P+E(50%) - 3W3P, 3200A AL BUSDUCT

C TO MSB_G_IT_A DS 4P 6300 6300A COPPER BUSBARS

OUTGOING R01 ATS_IT_F3B ACB 3P 2500 2500 O O 1,532.00 3P+E(50%) - 3W3P, 2500A AL BUSDUCT
R02 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R03 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R04 ACB SOCKET from FUTURE ACB 3P 2500 85 LSIG
R05 ACB SOCKET from FUTURE ACB 3P 1000 85 LSIG

TOTAL 0.00 0.00 0.00 1,532.00

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 8


DRAWING NO. 1209
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status
Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

10 MSB_G_M_A MAIN 1,732.66


3P4W 380/220V
INCOMING Q01 From AMF_IT_5_R04 ACB 4P 3200 3200 66 LSIG O O 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
Q02 From AMF_M_1_R01 ACB 4P 3200 3200 66 LSIG O O 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
Q03 ACB SOCKET from FUTURE ACB 4P 3200 66 LSIG FUTURE

C TO MSB_G_M_B DS 4P 5000 5000A COPPER BUSBARS

OUTGOING R01 SB_MBL_F3_A ACB 4P 4000 3200 66 LSIG O O 177.12 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
R02 SB_MBL_F1_A ACB 4P 2500 2000 66 LSIG O O 710.34 4P+E(50%) - 4W3P, 2000A AL BUSDUCT
R03 SB_MBL_F1_CH_A ACB 4P 4000 3200 66 LSIG O O 845.20 4P+E(50%) - 4W3P, 4000A AL BUSDUCT
R04 To Generator Room Fans MCCB 4P 63 63 50 LSI O CU/XLPE/PVC CABLE 1C-16mm2 x 4 + E16

TOTAL 0.00 0.00 0.00 1,732.66

11 MSB_G_M_B MAIN 1,711.86


3P4W 380/220V
INCOMING Q01 From AMF_IT_5_R05 ACB 4P 3200 3200 66 LSIG O O 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
Q02 From AMF_M_1_R02 ACB 4P 3200 3200 66 LSIG O O 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
Q03 ACB SOCKET from FUTURE ACB 4P 3200 66 LSIG FUTURE

C TO MSB_G_M_A DS 4P 5000 5000A COPPER BUSBARS

OUTGOING R01 SB_MBL_F3_B ACB 4P 4000 3200 66 LSIG O O 177.12 4P+E(50%) - 4W3P, 3200A AL BUSDUCT
R02 SB_MBL_F1_B ACB 4P 2500 2000 66 LSIG O O 709.54 4P+E(50%) - 4W3P, 2000A AL BUSDUCT
R03 SB_MBL_F1_CH_B ACB 4P 4000 3200 66 LSIG O O 825.20 4P+E(50%) - 4W3P, 4000A AL BUSDUCT
R04 To Generator Room Fans MCCB 4P 63 63 50 LSI O CU/XLPE/PVC CABLE 1C-16mm2 x 4 + E16

TOTAL 0.00 0.00 0.00 1,711.86

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 9


DRAWING NO. 1210
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

12 SB_MBL_F1_B MAIN 709.54


3P4W 380/220V
INCOMING Q01 From MSB_TX_2_R04 DS 4P 2000 4P+E(50%) - 4W3P, 2000A CU BUSDUCT
Q02 From MSB_G_M_B_R02 DS 4P 2000 4P+E(50%) - 4W3P, 2000A AL BUSDUCT
NEUTRAL OVERLAP Q ATS WITH NEUTRAL OVERLAP ATS 4P 2000 O

OUTGOING R01 SB_MBL_F3_B MCCB 4P 400 400 36 LSI O O 177.12 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
R02 MSB General Loads MSB_F2_GL MCCB 4P 800 800 36 LSI O O 412.40 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R03 CP_CME_UPS_F2_B MCCB 4P 250 200 36 LSI O O 62.61 CU/XLPE/PVC 1C-120mm2 x4 + E 1C-70
R04 SB_F1_B MCCB 4P 250 200 36 LSI O O 52.91 CU/XLPE/PVC 1C-120mm2 x4 + E 1C-70
R05 Aux. Load Genset CP_AL_G_B MCCB 4P 25 25 36 LSI O O 4.50 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6

TOTAL 0.00 0.00 0.00 709.54

13 SB_MBL_F1_A MAIN 710.34


3P4W 380/220V
INCOMING Q01 From MSB_TX_2_R03 DS 4P 2000 4P+E(50%) - 4W3P, 2000A CU BUSDUCT
Q02 From MSB_G_M_A_R02 DS 4P 2000 4P+E(50%) - 4W3P, 2000A AL BUSDUCT
NEUTRAL OVERLAP Q ATS WITH NEUTRAL OVERLAP ATS 4P 2000 O

OUTGOING R01 SB_MBL_F3_A MCCB 4P 400 400 36 LSI O O 177.12 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
R02 MSB General Loads MSB_F2_GL MCCB 4P 800 800 36 LSI O O 412.40 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R03 CP_CME_UPS_F2_A MCCB 4P 250 200 36 LSI O O 62.61 CU/XLPE/PVC 1C-120mm2 x4 + E 1C-70
R04 SB_F1_A MCCB 4P 250 200 36 LSI O O 53.71 CU/XLPE/PVC 1C-120mm2 x4 + E 1C-70
R05 Aux. Load Genset CP_AL_G_A MCCB 4P 25 25 36 LSI O O 4.50 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6

TOTAL 0.00 0.00 0.00 710.34

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 10


DRAWING NO. 1210
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

14 CP_CH_F1_01 MAIN 342.60


3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_CH_A_R05 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
Q02 From SB_MBL_F1_CH_B_R05 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
NEUTRAL OVERLAP Q ATS WITH NEUTRAL OVERLAP ATS 4P 800 O

OUTGOING R01 Cooling Tower CP_CT_RT_01 MCCB 4P 100 100 36 LSI O 26.50 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R02 Condenser Water Pump CP_CDWP_F1_01 MCCB 4P 160 160 36 LSI O 30.20 CU/XLPE/PVC 1C-35mm2 x4+ E 1C-25
R03 Chiller CH_F1_01 MCCB 4P 800 700 36 LSI O O 285.90 0.85 CU/XLPE/PVC (2x1C-240mm2)x4 + E 2x1C-185

TOTAL 0.00 0.00 0.00 342.60

15 CP_CH_F1_02 MAIN 342.60


3P4W 380/220V
INCOMING 1 From SB_MBL_F1_CH_A_R04 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
2 From SB_MBL_F1_CH_B_R04 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
NEUTRAL OVERLAP 3 ATS WITH NEUTRAL OVERLAP ATS 4P 800 O

OUTGOING R01 Cooling Tower CP_CT_RT_02 MCCB 4P 100 100 36 LSI O 26.50 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R02 Condenser Water Pump CP_CDWP_F1_02 MCCB 4P 160 160 36 LSI O 30.20 CU/XLPE/PVC 1C-35mm2 x4+ E 1C-25
R03 Chiller CH_F1_02 MCCB 4P 800 700 36 LSI O O 285.90 0.85 CU/XLPE/PVC (2x1C-240mm2)x4 + E 2x1C-185

TOTAL 0.00 0.00 0.00 342.60

16 SB_MBL_F1_CH_B MAIN 825.20


3P4W 380/220V
INCOMING Q01 From MSB_TX_2_R02 DS 4P 4000 4P+E(50%) - 4W3P, 4000A CU BUSDUCT
Q02 From MSB_G_M_B_R03 DS 4P 4000 4P+E(50%) - 4W3P, 4000A AL BUSDUCT
Q ATS ATS 4P 4000 O

OUTGOING R01 MCCB SOCKET for CHILLER PUMP 5 (FUTURE) MCCB 4P 800 50 LSI
R02 MCCB SOCKET for CHILLER PUMP 4 (FUTURE) MCCB 4P 800 50 LSI
R03 MCCB SOCKET for CHILLER PUMP 3 (FUTURE) MCCB 4P 800 50 LSI
R04 To CHILLER PUMP 2 CP_CH_F1_02 MCCB 4P 800 800 50 LSI O O 342.60 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R05 To CHILLER PUMP 1 CP_CH_F1_01 MCCB 4P 800 800 50 LSI O O 342.60 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R06 SB_CHWP_F1_A MCCB 4P 400 400 50 LSI O O 70.00 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
R07 SB_CHWP_F1_B MCCB 4P 400 400 50 LSI O O 70.00 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120

TOTAL 0.00 0.00 0.00 825.20

17 SB_MBL_F1_CH_A MAIN 845.20


3P4W 380/220V
INCOMING Q01 From MSB_TX_2_R01 DS 4P 4000 4P+E(50%) - 4W3P, 4000A CU BUSDUCT
Q02 From MSB_G_M_A_R03 DS 4P 4000 4P+E(50%) - 4W3P, 4000A AL BUSDUCT
Q ATS ATS 4P 4000 O

OUTGOING R01 MCCB SOCKET for CHILLER PUMP 5 (FUTURE) MCCB 4P 800 50 LSI
R02 MCCB SOCKET for CHILLER PUMP 4 (FUTURE) MCCB 4P 800 50 LSI
R03 MCCB SOCKET for CHILLER PUMP 3 (FUTURE) MCCB 4P 800 50 LSI
R04 To CHILLER PUMP 2 CP_CH_F1_02 MCCB 4P 800 800 50 LSI O O 342.60 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R05 To CHILLER PUMP 1 CP_CH_F1_01 MCCB 4P 800 800 50 LSI O O 342.60 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
R06 UPS F1 CH 200kVA / SB_CHWP_F1_A MCCB 4P 400 400 50 LSI O O 90.00 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
R07 SB_CHWP_F1_B MCCB 4P 400 400 50 LSI O O 70.00 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120

TOTAL 0.00 0.00 0.00 845.20

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 11


DRAWING NO. 1211
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Power Factor Circuit
(kA) (mA) Unit R
MCB)

18 CP_CHWP_F1_01 MAIN 31.00


3P4W 380/220V
INCOMING Q01 From SB_CHWP_F1_A_R05 DS 4P 125 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q02 From SB_CHWP_F1_B_R05 DS 4P 125 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q ATS ATS 4P 125
MCCB 4P 160 125 15 LSI O O

O
OUTGOING CHWP_F1_01 DIRECT TO VSD 30.00 0.86 VSD O (BMS) O O O CU/XLPE/PVC 1C-25mm2 x3+ E 1C-16
R01 Control Panel CP_CH_01 MCB 2P 16 C 15 1.00 0.86 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.00 0.00 0.00 30.00

19 CP_CHWP_F1_02 MAIN 31.00


3P4W 380/220V
INCOMING Q01 From SB_CHWP_F1_A_R04 DS 4P 125 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q02 From SB_CHWP_F1_B_R04 DS 4P 125 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q ATS ATS 4P 125
MCCB 4P 160 125 15 LSI O O

O
OUTGOING CHWP_F1_02 DIRECT TO VSD 30.00 0.86 VSD O (BMS) O O O CU/XLPE/PVC 1C-25mm2 x3+ E 1C-16
R01 Control Panel CP_CH_02 MCB 2P 16 C 15 1.00 0.86 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.00 0.00 0.00 30.00

20 SB_CHWP_F1_A MAIN 70.00


3P4W 380/220V
INCOMING Q01 UPS F1 CH (200KVA) / SB_MBL_F1_CH_A_R06 DS 4P 400 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q02 From SB_MBL_F1_CH_B_R06 DS 4P 400 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120

OUTGOING R01 CP CHWP_F1_05 MCCB 4P 160 125 15 LSI O O


R02 CP CHWP_F1_04 MCCB 4P 160 125 15 LSI O O
R03 CP CHWP_F1_03 MCCB 4P 160 125 15 LSI O O
R04 CP CHWP_F1_02 MCCB 4P 160 125 15 LSI O O 31.00 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R05 CP CHWP_F1_01 MCCB 4P 160 125 15 LSI O O 31.00 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R06 Control A MCCB 4P 100 63 15 LSI O O 8.00 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
R07 CPM Master MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SPARE MCB 2P 16 C 15

TOTAL 0.00 0.00 0.00 70.00

21 SB_CHWP_F1_B MAIN 70.00


3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_CH_A_R07 DS 4P 400 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q02 From SB_MBL_F1_CH_B_R07 DS 4P 400 CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120

OUTGOING R01 CP CHWP_F1_05 MCCB 4P 160 125 15 LSI O O


R02 CP CHWP_F1_04 MCCB 4P 160 125 15 LSI O O
R03 CP CHWP_F1_03 MCCB 4P 160 125 15 LSI O O
R04 CP CHWP_F1_02 MCCB 4P 160 125 15 LSI O O 31.00 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R05 CP CHWP_F1_01 MCCB 4P 160 125 15 LSI O O 31.00 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R06 Control B MCCB 4P 100 63 15 LSI O O 8.00 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
R07 CPM Slave MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SPARE MCB 2P 16 C 15

TOTAL 0.00 0.00 0.00 70.00

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 12


DRAWING NO. 1212
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status
Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

22 CP_CME_F1B MAIN 19.41


3P4W 380/220V
INCOMING Q01 From SB_F1_B_R02 DS 80 O CU/XLPE/PVC 1C-25mm2 x4 + E 1C-16

OUTGOING R01 FCU_Chiller Plant Room FCU-G-2 MCB 4P 20 C 10 4.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
R02 FCU_Chiller Plant Room FCU-G-4 MCB 4P 20 C 10 4.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
CẬP NHẬT TÊN TẢI R03 FCU_Battery Room FCU-G-6 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R04 FCU_UPS Room FCU-G-8 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R05 FCU_Switchroom FCU-G-10 MCB 4P 20 C 10 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
R06 FCU_Telco Room 1 FCU-G-12 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R07 DX_MSB Room IDU-G-02-DX / ODU-G-02-DX MCB 4P 20 C 10 3.35 0.85 CU/XLPE/PVC 1C-4mm2 x4 + E 1C-4
HV Room Fan
EAF run → FAF run,
R08 Exhaust Air Fan HV Room EAF_1F_01B MCB 3P 16 C 10 0.37 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
EAF stop → FAF stop,
(TH) (BMS)
R09 Fresh Air Fan HV Room FAF_1F_01B MCB 3P 16 C 10 0.37 0.70 and vice versa O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
Genset Room Fan
Exhaust Air Fan Genset Room O O
R10 EAF_1F_03 MCB 3P 16 C 10 0.75 0.70 (TH) (BMS) O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
Electrical Room Fan
Exhaust Air Fan Electrical Room
EAF run → FAF run,
R11 EAF_1F_04 MCB 3P 16 C 10 0.75 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
EAF stop → FAF stop,
(TH) (BMS)
R12 Fresh Air Fan Electrical Room FAF_1F_02 MCB 3P 16 C 10 0.75 0.70 and vice versa O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
R13 SPARE MCB 4P 32 C 10
O O
R14 Exhaust Air Fan Battery Room EAF_1F_05 MCB 2P 16 C 10 0.06 0.70 (BMS) (Sw) O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R15 SPARE MCB 2P 16 C 10
R16 SPARE MCB 2P 16 C 10
R17 IDU_CASSETTE- IDU-G-05 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
- Pair 1 runs,
R18 IDU_CASSETTE- IDU-G-06 MCB 2P 16 C 10 0.23 0.85 Pair 2 stops CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
and vice
R19 IDU_CASSETTE- IDU-G-07 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
versa.
R20 IDU_CASSETTE- IDU-G-08 MCB 2P 16 C 10 0.23 0.85 - BMS send 2 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
ON/OFF
R21 Water Leakage CP MCB 2P 16 C 10 signals to 2 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
CPs, interlock
R22 Exhaust Air Fan Genset Room EAF-F1-G02,04,06 & Spare MCCB 3P+N 40 40 18 TMD 0.70 CU/XLPE/PVC 1C-10mm2 x4 + E 1C-10
at the Panels
& BMS also

TOTAL 0.65 0.60 0.82 17.34

23 CP_CME_F1A MAIN 18.01


3P4W 380/220V
INCOMING Q01 From SB_F1_A_R02 DS 80 O CU/XLPE/PVC 1C-25mm2 x4 + E 1C-16

OUTGOING R01 FCU_Chiller Plant Room FCU-G-1 MCB 4P 20 C 10 4.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
R02 FCU_Chiller Plant Room FCU-G-3 MCB 4P 20 C 10 4.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
CẬP NHẬT TÊN TẢI R03 FCU_Battery Room FCU-G-5 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R04 FCU_UPS Room FCU-G-7 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R05 FCU_Switchroom FCU-G-11 MCB 4P 20 C 10 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x4 + E 1C-2.5
R06 FCU_Telco Room 2 FCU-G-9 MCB 2P 16 C 10 0.37 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R07 DX_Fire Control Room IDU-G01-DX / ODU-G-01-DX MCB 4P 20 C 10 3.35 0.85 CU/XLPE/PVC 1C-4mm2 x4 + E 1C-4
HV Room Fan
EAF run → FAF run,
R08 Exhaust Air Fan HV Room EAF_1F_01A MCB 3P 16 C 10 0.37 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
EAF stop → FAF stop,
(TH) (BMS)
R09 Fresh Air Fan HV Room FAF_1F_01A MCB 3P 16 C 10 0.37 0.70 and vice versa O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5
Genset Room Fan
Exhaust Air Fan Genset Room O O
R10 EAF_1F_02 MCB 3P 16 C 10 0.75 0.70 (TH) (BMS) O O O CU/XLPE/PVC 1C-2.5mm2 x3 + E 1C-2.5

R11 SPARE MCB 3P+N 16 C 10


R12 SPARE MCB 3P+N 16 C 10
R13 SPARE MCB 4P 32 C 10
R14 SPARE MCB 2P 16 C 10
Fuel Pump Room Fan
Exhaust Air Fan Fuel Pump Room
EAF run → FAF run,
R15 EAF_1F_06 MCB 2P 16 C 10 0.06 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
Fresh Air Fan Fuel Pump Room EAF stop → FAF stop,
(BMS) (Sw)
R16 FAF_1F_03 MCB 2P 16 C 10 0.11 0.70 and vice versa O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R17 IDU_CASSETTE- IDU-G-01 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R18 IDU_CASSETTE- IDU-G-02 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R19 IDU_CASSETTE- IDU-G-03 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R20 IDU_CASSETTE- IDU-G-04 MCB 2P 16 C 10 0.23 0.85 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R21 Water Leakage CP MCB 2P 16 C 10 CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R22 Exhaust Air Fan Genset Room EAF-F1-G01,03,05 & Spare MCCB 3P+N 40 40 18 TMD 0.70 CU/XLPE/PVC 1C-10mm2 x4 + E 1C-10

TOTAL 0.60 0.65 0.93 15.84

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 13


DRAWING NO. 1212
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status
Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 14


DRAWING NO. 1212
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

24 DB_MBL_F1 MAIN 10.00


3P4W 380/220V
INCOMING Q01 From SB_F1_A_R01 MCB 4P 32 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q02 From SB_F1_B_R03 MCB 4P 32 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q ATS ATS 4P 32
Q RCCB 4P 32 100 O

OUTGOING Lighting M&E Areas (DB_COM_L_F1) DIRECT TO LIGHTING PANEL 10.00 0.90 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 10.00

25 CP_DP_F1_B MAIN 8.60


3P4W 380/220V
INCOMING Q01 From SB_F1_B_R02 MCB 4P 32 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
RCCB 4P 32 30

OUTGOING R01 Fuel Transfer Pump FTP-GF-1B (CP) MCB 3P 20 C 10 3.70 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 Fuel Transfer Pump FTP-GF-2B (CP) MCB 3P 20 C 10 3.70 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 SPARE MCB 3P 16 C 10
R04 CP_DIESEL_B MCB 2P 16 C 10 1.20 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.20 0.00 0.00 7.40

26 CP_DP_F1_A MAIN 10.80


3P4W 380/220V
INCOMING Q01 From SB_F1_A_R03 MCB 4P 32 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
RCCB 4P 32 30

OUTGOING R01 Fuel Transfer Pump FTP-GF-1A (CP) MCB 3P 20 C 10 3.70 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 Fuel Transfer Pump FTP-GF-2A (CP) MCB 3P 20 C 10 3.70 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 Fuel Polishing Pump FPP-GF-1A (CP) MCB 3P 16 C 10 2.20 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R04 CP_DIESEL_A MCB 2P 16 C 10 1.20 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.20 0.00 0.00 9.60

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 15


DRAWING NO. 1212
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

27 SB_F1_B MAIN 52.91


3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_B_R04 SD 4P 400 CU/XLPE/PVC 1C-120mm2 x4+ E 1C-70

OUTGOING R01 CP_DP_F1_B MCCB 4P 63 32 C 25 LSI O 8.60 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 CP_CME_F1B MCCB 4P 100 80 25 LSI O 19.41 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R03 DB_MBL_F1 MCB 4P 32 C 25 O 10.00 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
R04 SB_MBL_BF_B MCCB 4P 100 63 25 LSI O 14.90 CU/XLPE/PVC 1C-16mm2 x2+ E 1C-16
R05 SPARE MCB 4P 32 C 25 O
R06 SPARE MCB 4P 32 C 25 O
R06 Control MV_1.1~1.3 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R07 Control MV_2.1~2.3 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R08 Control MV_5.1~5.3 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R09 Control Dry Trans. 05 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R10 DDC_F1_1 MCB 2P 16 C 15 By Other
R11 DDC_F1_2 MCB 2P 16 C 15 By Other
R12 DDC_F1_3 MCB 2P 16 C 15 By Other
R13 DDC_F1_4 MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 52.91

28 SB_F1_A MAIN 53.71


3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_A_R04 SD 4P 400 CU/XLPE/PVC 1C-120mm2 x4+ E 1C-70

OUTGOING R01 DB_MBL_F1 MCB 4P 32 C 25 O 10.00 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6


R02 CP_CME_F1A MCCB 4P 100 80 25 LSI O 18.01 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R03 CP_DP_F1_A MCCB 4P 63 32 C 25 LSI O 10.80 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
R04 SB_MBL_BF_A MCCB 4P 100 63 25 LSI O 14.90 CU/XLPE/PVC 1C-16mm2 x2+ E 1C-16
R05 SPARE MCB 4P 32 C 25 O
R06 SPARE MCB 4P 32 C 25 O
R06 Control MV_1~5 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R07 Heater MV_1~5 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R08 Control Dry Trans. 01 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R09 Control Dry Trans. 02 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2x2+ E 1C-2.5
R10 DDC_F1_1 MCB 2P 16 C 15 By Other
R11 DDC_F1_2 MCB 2P 16 C 15 By Other
R12 DDC_F1_3 MCB 2P 16 C 15 By Other
R13 DDC_F1_4 MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 53.71

CMC - PANEL DETAIL 20210723_R07 (add PF & KW).xlsx Page 16


DRAWING NO. 1213
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

29 SB_SP_BF_B MAIN 11.90


3P4W 380/220V
INCOMING Q01 From SB_MBL_BF_B_R02 MCB 4P 40 C 15 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
RCCB 4P 40 300 O

OUTGOING R01 Make-up Water Transfer Pump CP_MUWP_1B MCB 4P 32 C 15 5.50 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 Make-up Water Transfer Pump CP_MUWP_2B MCB 4P 32 C 15 5.50 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R03 Pump Control B MCB 2P 20 C 15 0.90 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 0.90 0.00 0.00 11.00

30 SB_SP_BF_A MAIN 11.90


3P4W 380/220V
INCOMING Q01 From SB_MBL_BF_B_R01 MCB 4P 40 C 15 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
RCCB 4P 40 300 O

OUTGOING R01 Make-up Water Transfer Pump CP_MUWP_1A MCB 4P 32 C 15 5.50 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 Make-up Water Transfer Pump CP_MUWP_2A MCB 4P 32 C 15 5.50 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R03 Pump Control A MCB 2P 20 C 15 0.90 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 0.90 0.00 0.00 11.00

31 DB_MBL_BF MAIN 3.00


3P4W 380/220V
INCOMING Q01 From SB_MBL_BF_A_R01 MCB 4P 16 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q02 From SB_MBL_BF_B_R02 MCB 4P 16 C 10 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q ATS ATS 4P 16
Q RCCB 4P 16 100 O

OUTGOING Lighting M&E Areas (DB_COM_L_BF) DIRECT TO LIGHTING PANEL 3.00 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4

TOTAL 0.00 0.00 0.00 3.00

32 SB_MBL_BF_B MAIN 14.90


3P4W 380/220V
INCOMING Q01 From SB_F1_B_R04 DS 4P 63 O CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16

OUTGOING R01 SB_SP_BF_B MCB 4P 40 C 15 O 11.90 CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16


R02 DB_MBL_BF MCB 4P 16 C 15 O 3.00 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6
R03 DDC_BF MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 14.90

33 SB_MBL_BF_A MAIN 14.90


3P4W 380/220V
INCOMING Q01 From SB_F1_A_R04 DS 4P 63 O CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16

OUTGOING R01 SB_SP_BF_A MCB 4P 40 C 15 O 11.90 CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16


R02 DB_MBL_BF MCB 4P 16 C 15 O 3.00 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6
R03 DDC_BF MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 14.90

Page 17 of 45
DRAWING NO. 1213
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

34 SB_SE_F1 MAIN 16.94


3P4W 380/220V
INCOMING Q01 From CP_CME_UPS_F2_A_R04 MCCB 4P 40 40 15 LSI CU/XLPE/PVC 1C-16mm2 x4+ E 1C-6
Q02 From CP_CME_UPS_F2_B_R04 MCCB 4P 40 40 15 LSI CU/XLPE/PVC 1C-16mm2 x4+ E 1C-6
Q ATS ATS 4P 40
Q RCCB 4P 40 300 O

OUTGOING R01 Anti-Crash Road Blocker MCB 4P 32 C 15 5.20 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 Barrier MCB 2P 16 C 15 0.22 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 Crash Rated Drop Arm Barrier MCB 2P 32 C 15 4.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 Metal Detector MCB 2P 16 C 15 0.12 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 Crash Rated Sliding Bollards MCB 4P 32 C 15 6.90 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R06 SPARE MCB 4P 32 C 15
R07 SPARE MCB 4P 16 C 15
R08 SPARE MCB 4P 16 C 15
R09 SPARE MCB 2P 32 C 15
R10 SPARE MCB 2P 16 C 15

TOTAL 0.22 4.50 0.12 12.10

NOTE: CÁC TẢI ĐANG SAI KHÁC Ở SINGLE LINE VÀ PLANT CHART, TẠM THIẾT KẾ NHƯ TRÊN, CHỜ PHẢN HỒI TỪ CMC SẼ TRIỂN KHAI TIẾP

35 SB_GH/SO_F1_A MAIN 9.50


3P4W 380/220V
INCOMING Q01 From SB_MNBL_F2_A MCCB 4P 63 32 LSI O O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

OUTGOING R01 SPACE MCB 4P 16 C 15 O


R02 SPACE MCB 4P 16 C 15 O
R03 SPACE MCB 4P 16 C 15 O
R04 Delivery Guardhouse MCB 2P 20 C 15 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 Main Guardhouse MCB 2P 20 C 15 3.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 Security Office MCB 2P 20 C 15 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 3.00 3.50 3.00 0.00

NOTE: CHƯA XÁC ĐỊNH STS LÀ 3P HAY 1P, DO ĐÓ TỦ NÀY TẠM THIẾT KẾ NHƯ TRÊN, CHỜ PHẢN HỒI TỪ CMC SẼ TRIỂN KHAI TIẾP

36 SB_GH/SO_F1_B MAIN 9.50


3P4W 380/220V
INCOMING Q01 From SB_MNBL_F2_B MCCB 4P 63 32 LSI O O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

OUTGOING R01 SPACE MCB 4P 16 C 15 O


R02 SPACE MCB 4P 16 C 15 O
R03 SPACE MCB 4P 16 C 15 O
R04 Delivery Guardhouse MCB 2P 20 C 15 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 Main Guardhouse MCB 2P 20 C 15 3.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 Security Office MCB 2P 20 C 15 3.00 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 3.00 3.50 3.00 0.00

NOTE: CHƯA XÁC ĐỊNH STS LÀ 3P HAY 1P, DO ĐÓ TỦ NÀY TẠM THIẾT KẾ NHƯ TRÊN, CHỜ PHẢN HỒI TỪ CMC SẼ TRIỂN KHAI TIẾP

Page 18 of 45
DRAWING NO. 1214
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

37 SB_CDH_F3B MAIN 143.85


3P4W 380/220V
INCOMING 1 From SB_MBL_F3B_R02 DS 4P 250 CU/XLPE/PVC 1C-185mm2 x4 + E 1C-95

OUTGOING R01 CRAH _F3_01B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 CRAH _F3_02B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 CRAH _F3_03B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R04 CRAH _F3_04B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R05 CRAH _F3_05B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R06 CRAH _F3_06B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R07 CRAH _F3_07B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R08 CRAH _F3_08B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R09 CRAH _F3_09B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R10 CRAH _F3_10B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R11 CRAH _F3_11B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R12 CRAH _F3_12B MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R13 Fresh Air DHU_F3_01B MCB 2P 16 C 15 0.87 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R14 Dehumidifier DU_F3_01B MCCB 4P 100 80 15 LSI O 20.05 0.85 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
R15 Fresh Air DHU_F3_02B MCB 2P 16 C 15 0.87 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R16 Dehumidifier DU_F3_02B MCCB 4P 100 80 15 LSI O 20.05 0.85 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16

TOTAL 0.87 0.87 0.00 142.10

38 SB_CDH_F3A MAIN 143.85


3P4W 380/220V
INCOMING 1 From SB_MBL_F3A_R02 DS 4P 250 CU/XLPE/PVC 1C-185mm2 x4 + E 1C-95

OUTGOING R01 CRAH _F3_01A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 CRAH _F3_02A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 CRAH _F3_03A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R04 CRAH _F3_04A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R05 CRAH _F3_05A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R06 CRAH _F3_06A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R07 CRAH _F3_07A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R08 CRAH _F3_08A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R09 CRAH _F3_09A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R10 CRAH _F3_10A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R11 CRAH _F3_11A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R12 CRAH _F3_12A MCCB 4P 63 32 15 LSI O 8.50 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R13 Fresh Air DHU_F3_01A MCB 2P 16 C 15 0.87 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R14 Dehumidifier DU_F3_01A MCCB 4P 100 80 15 LSI O 20.05 0.85 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
R15 Fresh Air DHU_F3_02A MCB 2P 10 C 15 0.87 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R16 Dehumidifier DU_F3_02A MCCB 4P 100 80 15 LSI O 20.05 0.85 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16

ĐÃ THAY ĐỔI
TOTAL 0.87 0.87 0.00 142.10

Page 19 of 45
DRAWING NO. 1214
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

39 CP_CME_F3B MAIN 16.21


3P4W 380/220V
INCOMING Q01 From SB_MBL_F3B_R03 DS 4P 63 CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16

OUTGOING R01 FCU_Electrical Room FCU-3F-1B MCB 2P 16 C 15 0.41 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R02 FCU_Network 1 FCU-3F-2B MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 FCU_Network 2 FCU-3F-3B MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 FCU_Battery room 1 FCU-3F-4B MCB 4P 16 C 15 1.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R05 FCU_Battery room 2 FCU-3F-5B MCB 4P 16 C 15 1.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R06 FCU_UPS room 1 FCU-3F-6B MCB 4P 20 C 15 4.00 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R07 FCU_UPS room 2 FCU-3F-7B MCB 4P 20 C 15 4.00 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R08 SPARE MCB 2P 16 C 15
R09 SPARE MCB 2P 16 C 15
R10 SPARE MCB 2P 16 C 15
R11 IDU_CASSETTE IDU-3F-01 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 IDU_CASSETTE IDU-3F-03 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 IDU_CASSETTE IDU-3F-05 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
Battery Room 1&2 Fan
EAF run →
R14 Exhaust Air Fan Battery Room 2 EAF_3F_01B MCB 2P 16 C 15 0.33 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
FAF run,
(PB) (BMS)
R15 Fresh Air Fan Battery Room 2 FAF_3F_01B MCB 2P 16 C 15 0.50 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R16 Water Leakage CP MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R17 Water Leakage CP MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R18 Water Leakage CP MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 0.96 2.37 1.87 11.00

- Pair
1
runs,
Pair 2
40 CP_CME_F3A MAIN 16.01 stops
and
3P4W 380/220V
vice
INCOMING Q01 From SB_MBL_F3A_R03 DS 4P 63 versa. CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16
- BMS
send
OUTGOING R01 FCU_Electrical Room FCU-3F-1A MCB 2P 16 C 15 0.41 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R02 FCU_Network 1 FCU-3F-2A MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 FCU_Network 2 FCU-3F-3A MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 FCU_Battery room 1 FCU-3F-4A MCB 4P 16 C 15 1.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R05 FCU_Battery room 2 FCU-3F-5A MCB 4P 16 C 15 1.50 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R06 FCU_UPS room 1 FCU-3F-6A MCB 4P 20 C 15 4.00 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R07 FCU_UPS room 2 FCU-3F-7A MCB 4P 20 C 15 4.00 0.85 CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R08 Staging room FCU-3F-8 MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SPARE MCB 2P 16 C 15
R10 SPARE MCB 2P 16 C 15
R11 IDU_CASSETTE IDU-3F-01 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 IDU_CASSETTE IDU-3F-03 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 IDU_CASSETTE IDU-3F-05 MCB 2P 16 C 15 0.03 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
Battery Room 1&2 Fan
EAF run →
R14 Exhaust Air Fan Battery Room 2 EAF_3F_01A MCB 2P 16 C 15 0.33 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
FAF run,
(PB) (BMS)
R15 Fresh Air Fan Battery Room 2 FAF_3F_01A MCB 2P 16 C 15 0.50 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R16 Water Leakage CP MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R17 Water Leakage CP MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R18 SPARE MCB 2P 16 C 15

TOTAL 0.96 2.37 1.67 11.00

Page 20 of 45
DRAWING NO. 1214
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

41 DB_MBL_F3 MAIN 13.93


3P4W 380/220V
INCOMING Q01 From SB_MBL_F3A_R01 MCCB 4P 100 50 15 LSI CU/XLPE/PVC 1C-10mm2 x2+ E 1C-10
Q02 From SB_MBL_F3B_R04 MCCB 4P 100 50 15 LSI CU/XLPE/PVC 1C-10mm2 x2+ E 1C-10
Q ATS ATS 4P 50
Q RCCB 4P 50 300 O

OUTGOING R01 Lighting M&E Areas (DB-COM-L-F3) MCCB 4P 32 32 15 TMD 2.98 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 Lighting Data Hall (DB-DHL-L-F3) MCCB 4P 32 32 15 TMD 5.45 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 Lighting Data Hall (DB-DHL-L-F2) MCCB 4P 32 32 15 TMD 5.50 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 13.93

42 SB_MBL_F3_B MAIN 177.12


3P4W 380/220V
INCOMING Q01 From PLUG-IN 3F-2 MCCB 4P 400 400 25 LSI CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q02 SB_MBL_F1_B_R01 MCCB 4P 400 400 25 LSI CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q ATS ATS 4P 400 O

OUTGOING R01 SB_PPC_B MCCB 4P 25 20 25 LSI O O 3.13 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6


R02 SB_CDH_F3B MCCB 4P 250 250 25 LSI O O 143.85 CU/XLPE/PVC 1C-185mm2 x4 + E 1C-95
R03 CP_CME_F3B MCCB 4P 100 63 25 LSI O O 16.21 CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16
R04 DB_MBL_F3 MCCB 4P 100 50 25 LSI O O 13.93 CU/XLPE/PVC 1C-10mm2 x4 + E 1C-10
R05 DDC_F3_1 MCB 2P 16 C 15 By Other
R06 DDC_F3_2 MCB 2P 16 C 15 By Other
R07 DDC_F3_3 MCB 2P 16 C 15 By Other
R08 DDC_F4 MCB 2P 16 C 15 By Other
R09 DDC_F5 MCB 2P 16 C 15 By Other
R10 DDC_F6 MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 177.12

43 SB_MBL_F3_A MAIN 177.12


3P4W 380/220V
INCOMING Q01 From PLUG-IN 3F-1 MCCB 4P 400 400 25 LSI CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q02 SB_MBL_F1_A_R01 MCCB 4P 400 400 25 LSI CU/XLPE/PVC (2x1C-120mm2)x4 + E 1C-120
Q ATS ATS 4P 400 O

OUTGOING R01 SB_PPC_A MCCB 4P 25 20 25 LSI O O 3.13 CU/XLPE/PVC 1C-6mm2 x4 + E 1C-6


R02 SB_CDH_F3A MCCB 4P 250 250 25 LSI O O 143.85 CU/XLPE/PVC 1C-185mm2 x4 + E 1C-95
R03 CP_CME_F3A MCCB 4P 100 63 25 LSI O O 16.21 CU/XLPE/PVC 1C-16mm2 x4 + E 1C-16
R04 DB_MBL_F3 MCCB 4P 100 50 25 LSI O O 13.93 CU/XLPE/PVC 1C-10mm2 x4 + E 1C-10
R05 DDC_F3_1 MCB 2P 16 C 15 By Other
R06 DDC_F3_2 MCB 2P 16 C 15 By Other
R07 DDC_F3_3 MCB 2P 16 C 15 By Other
R08 DDC_F4 MCB 2P 16 C 15 By Other
R09 DDC_F5 MCB 2P 16 C 15 By Other
R10 DDC_F6 MCB 2P 16 C 15 By Other

TOTAL 0.00 0.00 0.00 177.12

Page 21 of 45
DRAWING NO. 1215
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

44 SB_MNBL_F2_B MAIN 39.80


3P4W 380/220V
INCOMING Q01 From UPS 60KVA / CP_CME_UPS_F2_B_R02 MCCB 4P 100 100 15 LSI O O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q02 From By Pass / CP_CME_UPS_F2_B_R03 DS 4P 100 O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16

OUTGOING R01 Security Command Center SB_SCC_F2_B MCCB 4P 63 32 15 LSI O 9.10 0.95 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 NOC Room MCB 4P 40 C 15 O 5.00 0.95 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R03 General Security CP_GS_F2_B MCCB 4P 63 40 15 LIS O 9.20 0.95 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R04 BMS / Control MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 Guardhuses & Security Office SB_GH/SO_F1B MCCB 4P 63 32 15 LIS O 9.50 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R06 Gensets Control MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 Fire Control Panel MCB 2P 16 C 15 0.50 0.95 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 LV SB Control B MCB 4P 32 C 15 O 5.50 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R09 ASD Panel (for 24VDC) MCB 2P 16 C 15 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 Mechanical 1FL (for 24VDC) MCB 2P 16 C 15 CU/XLPE//FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 Mechanical 4FL (for 24VDC) MCB 2P 16 C 15 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 PA Power BF~3F MCB 2P 20 C 15 CU/XLPE/PVC 1C-4mm2 x2+ E 1C-4
R13 DDC_F2_1 MCB 2P 16 C 15 By Other
R14 DDC_F2_2 MCB 2P 16 C 15 By Other
R15 DDC_F2_3 MCB 2P 16 C 15 By Other

TOTAL 0.50 0.50 0.50 38.30

45 SB_MNBL_F2_A MAIN 39.80


3P4W 380/220V
INCOMING Q01 From UPS 60KVA / CP_CME_UPS_F2_A_R02 MCCB 4P 100 100 15 LSI O O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
Q02 From By Pass / CP_CME_UPS_F2_A_R03 DS 4P 100 O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16

OUTGOING R01 Security Command Center SB_SCC_F2_A MCCB 4P 63 32 15 LSI O 9.10 0.95 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 NOC Room MCB 4P 40 C 15 O 5.00 0.95 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R03 General Security CP_GS_F2_A MCCB 4P 63 40 15 LIS O 9.20 0.95 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R04 BMS / Control MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 Guardhuses & Security Office SB_GH/SO_F1A MCCB 4P 63 32 15 LIS O 9.50 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R06 Gensets Control MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
For IG55 BF&1F R07 Fire Control Panel MCB 2P 16 C 15 0.50 0.95 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 LV SB Control A MCB 4P 32 C 15 O 5.50 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R09 IG55 Local Panel 2F (x5) MCB 2P 16 C 15 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 IG55 Main Panel 2F MCB 2P 16 C 15 CU/XLPE/FR/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 IG55 Local Panel 2F (x9) MCB 2P 32 C 15 CU/XLPE/FR/PVC 1C-6mm2 x2+ E 1C-6
R12 PA Power 4F~6F MCB 2P 20 C 15 CU/XLPE/PVC 1C-4mm2 x2+ E 1C-4
R13 DDC_F2_1 MCB 2P 16 C 15 By Other
R14 DDC_F2_2 MCB 2P 16 C 15 By Other
R15 DDC_F2_3 MCB 2P 16 C 15 By Other

TOTAL 0.50 0.50 0.50 38.30

Page 22 of 45
DRAWING NO. 1215
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

46 CP_CME_UPS_F2_B MAIN 62.61


3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_B_R03 DS 4P 200 O CU/XLPE/PVC 1C-120mm2 x4+ E 1C-70

OUTGOING R01 FCU Server Room. FCU_2F-1B MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R02 FCU Electrical Room. FCU_2F-2B MCB 2P 16 C 15 1.34 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
CẬP NHẬT TÊN TẢI
R03 UPS 60KVA / SB_MNBL_F2_B MCCB 4P 100 100 25 LSI O 41.80 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R04 SB_MNBL_F2_B - For By Pass MCCB 4P 100 100 25 LSI O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R05 To SB_SE_F1 MCCB 4P 63 40 25 LSI O 16.94 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Battery Room Fan
EAF run →
R06 Exhaust Air Fan Battery Room EAF_2F_01B MCB 2P 16 C 15 0.33 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
FAF run,
(PB) (BMS)
R07 Fresh Air Fan Battery Room FAF_2F_01B MCB 2P 16 C 15 0.56 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R08 Water Leakage CP MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SPARE MCB 2P 16 C 15

TOTAL 2.21 1.34 0.33 58.74


- Pair
1
runs,
Pair 2
stops
and
vice
versa.
- BMS
send
47 CP_CME_UPS_F2_A MAIN 62.61
3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_A_R03 DS 4P 200 O CU/XLPE/PVC 1C-120mm2 x4+ E 1C-70

OUTGOING R01 FCU Server Room. FCU_2F-1A MCB 2P 16 C 15 1.65 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R02 FCU Electrical Room. FCU_2F-2A MCB 2P 16 C 15 1.34 0.85 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
CẬP NHẬT TÊN TẢI
R03 UPS 60KVA / SB_MNBL_F2_A MCCB 4P 100 100 25 LSI O 41.80 CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R04 SB_MNBL_F2_A - For By Pass MCCB 4P 100 100 25 LSI O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16
R05 To SB_SE_F1 MCCB 4P 63 40 25 LSI O 16.94 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Battery Room Fan
EAF run →
R06 Exhaust Air Fan Battery Room EAF_2F_01A MCB 2P 16 C 15 0.33 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
FAF run,
(PB) (BMS)
R07 Fresh Air Fan Battery Room FAF_2F_01A MCB 2P 16 C 15 0.56 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R08 Water Leakage CP MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SPARE MCB 2P 16 C 15

TOTAL 2.21 1.34 0.33 58.74

Page 23 of 45
DRAWING NO. 1216
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

48 DB_GL_RT_L MAIN 49.00


3P4W 380/220V
SLD: 32,1 kW
INCOMING 1 Q01 From MSB General Loads DS 4P 100 O CU/XLPE/PVC 1C-35mm2 x4+ E 1C-16
MSB_F2_GL_R02

OUTGOING 1 R01 Lift 2 MCCB 4P 63 32 15 LSI O O 15.00 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 Cargo Lift MCCB 4P 63 63 15 LSI O O 19.00 0.85 CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16

INCOMING 2 Q02 From MSB General Loads MCCB 4P 63 32 15 LSI O O 15.00 0.85 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
MSB_F2_GL_R01

OUTGOING 2 Lift 1 DIRECT TO LIFT 1 CP CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 49.00

49 DB_GL_RT MAIN 21.08


3P4W 380/220V
INCOMING Q01 From TAP OFF 40A (MSB General Loads) DS 4P 100 O CU/XLPE/PVC 1C-35mm2 x4+ E 1C-16
MSB_F2_GL_R03

OUTGOING R01 FOR LIGHTING RCCB 4P 25 100


L1 LIGHTING MCB 2P 10 C 15 0.12 0.90 CU/XLPE/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.16 0.90 CU/XLPE/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 SPARE MCB 2P 10 C 15 0.65 0.90
L4 SPARE MCB 2P 10 C 15

O
EXTERNAL R02 LIGHTING RCBO 1P+N 20 10 30 1.20 0.90 (PB) O Auto by Photocel + Timer CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET S1 RCBO 1P+N 20 10 30 1.20 1.00 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SPARE RCBO 1P+N 20 10 30

R04 CP_FAN_RT MCCB 4P 63 63 15 LSI O O 17.75 CU/XLPE/FR/PVC 1C-16mm2 x4+ E 1C-16


R05 ĐOÀN NHẤT PUMP MCCB 3P 63 63 15 LSI O 0.85 By Other

TOTAL 0.12 2.56 0.65 17.75

50 DB_GL_F3 MAIN 29.32


3P4W 380/220V
INCOMING Q01 From TAP OFF 40A (MSB General Loads) MCCB 4P 100 40 15 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
MSB_F2_GL_R03

OUTGOING R01 DB_COM_F3 MCCB 4P 40 40 15 TMD O 24.02 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R02 DB_DHL_F3 MCCB 4P 32 32 15 TMD O 5.30 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 Others MCB 4P 32 C 15 O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 29.32

51 DB_GL_F4 MAIN 22.13


3P4W 380/220V
INCOMING Q01 From TAP OFF 40A (MSB General Loads) MCCB 4P 100 40 15 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
MSB_F2_GL_R03

OUTGOING R01 DB_COM_F4 MCCB 4P 40 40 15 TMD O 16.83 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R02 DB_DHL_F4 (Future) MCCB 4P 32 32 15 TMD O 5.30 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 Others MCB 4P 32 C 15 O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

Page 24 of 45
DRAWING NO. 1216
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

TOTAL 0.00 0.00 0.00 22.13

52 DB_GL_F5 MAIN 14.29


3P4W 380/220V
INCOMING Q01 From TAP OFF 40A (MSB General Loads) MCCB 4P 100 40 15 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
MSB_F2_GL_R03

OUTGOING R01 DB_COM_F5 MCCB 4P 40 40 15 TMD O 8.99 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R02 DB_DHL_F5 (Future) MCCB 4P 32 32 15 TMD O 5.30 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 Others MCB 4P 32 C 15 O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 14.29

53 DB_GL_F6 MAIN 14.32


3P4W 380/220V
INCOMING Q01 From TAP OFF 40A (MSB General Loads) MCCB 4P 100 40 15 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
MSB_F2_GL_R03

OUTGOING R01 DB_COM_F6 MCCB 4P 40 40 15 TMD O 9.02 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
R02 DB_DHL_F6 (Future) MCCB 4P 32 32 15 TMD O 5.30 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 Others MCB 4P 32 C 15 O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6

TOTAL 0.00 0.00 0.00 14.32

Page 25 of 45
DRAWING NO. 1216
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

54 SB_SCC_F2A MAIN 9.10


INCOMING Q01 From SB_MNBL_F2_A MCCB 4P 63 32 LSI O O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
3P4W 380/220V

OUTGOING R01 SPACE MCB 4P 16 C 15 O


R02 SPACE MCB 4P 40 C 15 O
R03 Equipment SCC STS MCB 2P 20 C 15 2.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 Sever for Security STS MCB 2P 20 C 15 6.60 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

ĐÃ THAY ĐỔI
TOTAL 2.50 6.60 0.00 0.00

NOTE: CHƯA XÁC ĐỊNH STS LÀ 3P HAY 1P, DO ĐÓ TỦ NÀY TẠM THIẾT KẾ NHƯ TRÊN, CHỜ PHẢN HỒI TỪ CMC SẼ TRIỂN KHAI TIẾP

55 SB_SCC_F2B MAIN 9.10


INCOMING Q01 From SB_MNBL_F2_B MCCB 4P 63 32 LSI O O CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
3P4W 380/220V

OUTGOING R01 SPACE MCB 4P 16 C 15 O


R02 SPACE MCB 4P 40 C 15 O
R03 Equipment SCC STS MCB 2P 20 C 15 2.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 Sever for Security STS MCB 2P 20 C 15 6.60 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

ĐÃ THAY ĐỔI
TOTAL 2.50 6.60 0.00 0.00

NOTE: CHƯA XÁC ĐỊNH STS LÀ 3P HAY 1P, DO ĐÓ TỦ NÀY TẠM THIẾT KẾ NHƯ TRÊN, CHỜ PHẢN HỒI TỪ CMC SẼ TRIỂN KHAI TIẾP

Page 26 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KVA - KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

56 MSB General Loads MAIN 412.40


MSB_F2_GL
3P4W 380/220V
INCOMING Q01 From SB_MBL_F1_A_R04 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
Q02 From SB_MBL_F1_B_R01 DS 4P 800 CU/XLPE/PVC (3x1C-240mm2)x4 + E 2x1C-185
NEUTRAL OVERLAP Q ATS WITH NEUTRAL OVERLAP ATS 4P 800 O

OUTGOING R01 DB_GL_RT_L Lift 1 MCCB 4P 63 63 25 LSI O 15.00 CU/XLPE/PVC 4x1C-6mm2 + E 1C-6
R02 DB_GL_RT_L Lift 2 & Cargo Lift MCCB 4P 100 100 25 LSI O 34.00 CU/XLPE/PVC 4x1C-35mm2 + E 1C-16
R03 BB_CL_1 (DB_GL_F3~6 + DB_GL_RT) MCCB 4P 400 400 25 LSI O 101.14 CU/XLPE/PVC 4x1C-240mm2 + E 1C-120
R04 DB_COM_F2 MCCB 4P 63 63 25 LSI O 21.40 CU/XLPE/PVC 4x1C-10mm2 + E 1C-10
Future R05 Data Hall Loads. Floor 2. DB_DHL_F2 MCCB 4P 63 63 25 LSI O 5.50 CU/XLPE/PVC 4x1C-6mm2 + E 1C-6
R06 DB_OFFICE_F2 MCCB 4P 160 160 25 LSI O 30.84 CU/XLPE/PVC 4x1C-70mm2 + E 1C-35
R07 DB_CL_OFFICE_F2 MCCB 4P 100 100 25 LSI O 10.80 CU/XLPE/PVC 4x1C-70mm2 + E 1C-35
R08 BB_CL_2 (DB_GL_F1 + DB_GL_BF) MCCB 4P 250 200 25 LSI O 39.72 CU/XLPE/PVC 4x1C-95mm2 + E 1C-50
R09 Fire Switchboard DB_FFP MCCB 4P 400 400 25 LSI O 154.00 CU/XLPE/FR/PVC 4x1C-185mm2 + E 1C-95

TOTAL 0.00 0.00 0.00 412.40

57 SB_PPC_A MAIN 3.13


3P4W 380/220V
INCOMING Q01 From SB_MBL_F3A_R04 MCB 4P 20 C 15 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
RCCB 4P 20 100

OUTGOING R01 Pressure Booter CP_CWPP_M1 MCB 4P 20 C 15 1.10 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 Hydraulic Unit CP_HYDR_1 MCB 4P 20 C 15 0.85 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 Vacuum Degasser CP_VACD_1 MCB 2P 16 C 15 1.18 0.93 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.18 0.00 0.00 1.95

58 SB_PPC_B MAIN 3.13


3P4W 380/220V
INCOMING Q01 From SB_MBL_F3B_R04 MCB 4P 20 C 15 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
RCCB 4P 20 100

OUTGOING R01 Pressure Booter CP_CWPP_M2 MCB 4P 20 C 15 1.10 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 Hydraulic Unit CP_HYDR_2 MCB 4P 20 C 15 0.85 0.85 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 Vacuum Degasser CP_VACD_2 MCB 2P 16 C 15 1.18 0.93 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 1.18 0.00 0.00 1.95

Page 27 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

59 DB_GL_BF MAIN 11.07


3P4W 380/220V
INCOMING Q01 From TAP OFF 63A (MSB General Loads) DS 4P 63 O CU/XLPE/PVC 1C-70mm2 x4+ E 1C-35
MSB_F2_GL_R08

OUTGOING R01 FOR LIGHTING RCCB 4P 32 100


L1 LIGHTING MCB 2P 10 C 15 0.46 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.04 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 15 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 15 0.40 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 15 0.80 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 SPARE MCB 2P 10 C 15
LE EXIT & EMER MCB 2P 10 C 15 0.09 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15

R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SPARE RCBO 1P+N 20 10 30

R06 BF-Dry Garbage 03 Exhaust Fan EAF_BF_02 MCB 2P 16 C 15 0.11 0.70 Sw CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 BF-Storage 7 Exhaust Fan EAF_BF_04 MCB 2P 16 C 15 0.94 0.70 Sw CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 BF-Storage 6 Exhaust Fan EAF_BF_05 MCB 2P 16 C 15 0.94 0.70 Sw CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 BF-Storage 5 Exhaust Fan EAF_BF_06 MCB 2P 16 C 15 0.80 0.70 Sw CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SPARE MCB 2P 16 C 15

Pump Room 2 Fan


EAF run →
R11 Exhaust Air Fan Pump Room 2 EAF_BF_03 MCB 2P 16 C 15 0.26 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
FAF run,
(TH) (BMS)
R12 Fresh Air Fan Pump Room 2 FAF_BF_02 MCB 2P 16 C 15 0.26 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x2 + E 1C-2.5
R13 CP-AEROSOL MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R14 SPARE MCB 2P 16 C 15

Thermal Storage area Fan


Exhaust Air Fan Thermal Storage area
EAF run →
R15 EAF_BF_01 MCB 4P 16 C 15 0.75 0.70 O O O O O CU/XLPE/PVC 1C-2.5mm2 x3+ E 1C-2.5
Fresh Air Fan Thermal Storage area FAF run,
(TH) (BMS)
R16 FAF_BF_01 MCB 4P 16 C 15 0.75 0.70 EAF stop → O O O CU/XLPE/PVC 1C-2.5mm2 x3+ E 1C-2.5
R17 SPARE MCB 4P 32 C 15
R18 SPARE MCB 4P 32 C 15
R19 SPARE MCB 4P 40 C 15
R20 DDC_RF_1 MCB 2P 16 C 15 0.10 0.95 By Other
R21 DDC_RF_2 MCB 2P 16 C 15 0.10 0.95 By Other
R22 DDC_RF_3 MCB 2P 16 C 15 0.10 0.95 By Other
R23 DDC_RF_4 MCB 2P 16 C 15 0.10 0.95 By Other

TOTAL 3.26 3.50 2.81 1.50

Page 28 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

60 DB_GL_F1 MAIN 28.65


3P4W 380/220V
INCOMING Q01 From TAP OFF 63A (MSB General Loads) DS 4P 63 O CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16
MSB_F2_GL_R08

OUTGOING R01 FOR LIGHTING RCCB 4P 32 100


L1 LIGHTING MCB 2P 10 C 15 0.12 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 15 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 15 0.88 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 15 0.70 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 15 0.68 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 15 0.80 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L8 LIGHTING MCB 2P 10 C 15 0.52 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L9 LIGHTING MCB 2P 10 C 15 0.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L10 LIGHTING MCB 2P 10 C 15 0.14 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L11 LIGHTING MCB 2P 10 C 15 0.10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L12 LIGHTING MCB 2P 10 C 15 0.07 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L13 LIGHTING MCB 2P 10 C 15 0.13 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L14 LIGHTING MCB 2P 10 C 15 0.84 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L15 LIGHTING MCB 2P 10 C 15 0.18 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L16 LIGHTING MCB 2P 10 C 15 0.25 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L17 LIGHTING MCB 2P 10 C 15 0.32 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L18 LIGHTING MCB 2P 10 C 15 0.08 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L19 SPARE MCB 2P 10 C 15
L20 SPARE MCB 2P 10 C 15
LE EXIT & EMER MCB 2P 10 C 15 0.30 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE1 EXIT & EMER MCB 2P 10 C 15 0.04 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15

O
EXTERNAL R02 LIGHTING RCBO 1P+N 20 10 30 0.09 0.90 (PB) O Auto by Photo Cell & Timer CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
O
EXTERNAL R03 LIGHTING RCBO 1P+N 20 10 30 0.40 0.90 (PB) O Auto by Photo Cell & Timer CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SOCKET OUTLET RCBO 1P+N 20 10 30 2.40 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 SOCKET OUTLET RCBO 1P+N 20 10 30 2.10 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 SOCKET OUTLET RCBO 1P+N 20 10 30 2.10 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R14 SOCKET OUTLET RCBO 1P+N 20 10 30 0.60 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R15 SPARE RCBO 1P+N 20 10 30 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5

O O
R16 Exhaust Air Fan Toilet Room 01 TEAF_1F_01 MCB 2P 16 C 15 0.94 0.70 (PB) (BMS) O O O CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R17 SPARE MCB 2P 32 C 15
R18 SPARE MCB 2P 40 C 15

R19 Dock Leverler CP1 MCB 4P 32 C 15 1.13 0.85 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
R20 Dock Leverler CP2 MCB 4P 32 C 15 1.13 0.85 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6

TOTAL 7.26 10.80 8.34 2.25

Page 29 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

61 DB_COM_F2 MAIN 21.41


3P4W 380/220V
INCOMING Q01 From MSB General Loads DS 4P 40 O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
MSB_F2_GL_R04

OUTGOING R01 FOR LIGHTING RCCB 4P 32 100


L1 LIGHTING MCB 2P 10 C 15 0.28 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 SPARE MCB 2P 10 C 15
L4 LIGHTING MCB 2P 10 C 15 0.56 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 SPARE MCB 2P 10 C 15
L6 SPARE MCB 2P 10 C 15
L7 SPARE MCB 2P 10 C 15
L8 SPARE MCB 2P 10 C 15
L9 SPARE MCB 2P 10 C 15
FROM DB_DHL_L_F2 L10 LIGHTING MCB 2P 10 C 15 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F2 L11 LIGHTING MCB 2P 10 C 15 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F2 L12 LIGHTING MCB 2P 10 C 15 0.52 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F2 L13 LIGHTING MCB 2P 10 C 15 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F2 L14 LIGHTING MCB 2P 10 C 15 0.36 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F2 L15 LIGHTING MCB 2P 10 C 15 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L16 SPARE MCB 2P 10 C 15
LE EXIT & EMER MCB 2P 10 C 15 0.10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE1 EXIT & EMER MCB 2P 10 C 15 0.07 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F2 LE EXIT & EMER MCB 2P 10 C 15 0.08 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F2 LE EXIT & EMER MCB 2P 10 C 15 0.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15

R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 SOCKET OUTLET RCBO 1P+N 20 10 30 0.60 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 SOCKET OUTLET RCBO 1P+N 20 10 30 2.10 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 SPARE RCBO 1P+N 20 10 30

O O
R14 Exhaust Air Fan Toilet Room 02 TEAF_2F_01 MCB 2P 16 C 15 0.26 0.70 (PB) (BMS) O O O CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R15 SPARE MCB 2P 16 C 15

R16 OTHER MCB 3P 25 C 15


R17 OTHER MCB 3P 25 C 15
R18 OTHER MCB 3P 25 C 15
R19 OTHER MCB 3P 25 C 15

TOTAL 9.16 7.76 4.49 0.00

Page 30 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

SLD: 78,5kW
62 DB_OFFICE_F2 MAIN 30.84
3P4W 380/220V
INCOMING Q01 From MSB General Loads DS 4P 250 O CU/XLPE/PVC 1C-70mm2 x4+ E 1C-35
MSB_F2_GL_R06

OUTGOING R01 FOR LIGHTING RCCB 4P 32 100


L1 LIGHTING MCB 2P 10 C 15 0.18 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.18 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 15 0.02 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 15 0.25 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 15 1.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 15 0.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 15 0.00 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L8 LIGHTING MCB 2P 10 C 15 0.00 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L9 LIGHTING MCB 2P 10 C 15 0.80 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L10 LIGHTING MCB 2P 10 C 15 0.56 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L11 LIGHTING MCB 2P 10 C 15 0.20 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L12 LIGHTING MCB 2P 10 C 15 0.76 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L13 LIGHTING MCB 2P 10 C 15 0.40 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 15 0.37 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15

R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 SOCKET OUTLET RCBO 1P+N 20 10 30 0.90 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SOCKET OUTLET RCBO 1P+N 20 10 30 2.70 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SOCKET OUTLET RCBO 1P+N 20 10 30 0.90 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 SOCKET OUTLET RCBO 1P+N 20 10 30 2.10 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R14 SOCKET OUTLET (S17) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R15 SOCKET OUTLET (S18) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R16 SOCKET OUTLET (S19) RCBO 1P+N 20 10 30 0.90 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R17 SOCKET OUTLET (S29) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R18 SPARE RCBO 1P+N 20 10 30

R19 OTHER MCB 3P 25 C 15


R20 OTHER MCB 3P 25 C 15
R21 OTHER MCB 3P 25 C 15
R22 OTHER MCB 3P 25 C 15

TOTAL 11.29 11.21 8.34 0.00

Page 31 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

63 DB_CL_OFFICE_F2 MAIN 10.80


3P4W 380/220V
INCOMING Q01 From MSB General Loads DS 4P 100 O CU/XLPE/PVC 1C-70mm2 x4+ E 1C-35
MSB_F2_GL_R07

OUTGOING R01 AHU Unit AHU_2F_01 MCCB 4P 63 32 15 LSI O O 5.00 0.95 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R02 AHU Unit AHU_2F_02 MCCB 4P 63 32 15 LSI O O 5.00 0.95 CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
R03 OTHER RCCB 4P 40 30 O
SLD: Other 17kW
MCCB 4P 25 16 15 LSI CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
Liên động O O
R04 Fresh Air Fan Office Room FAF_2F_02 MCB 2P 16 C 15 0.80 0.70 AHU (BMS) (Sw) O O O CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 VAV Box MCB 2P 16 C 15
R06 VAV Box MCB 2P 16 C 15 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

CẬP NHẬT THEO YÊU CẦU MR. MINH MECHANICAL


TOTAL 0.80 0.00 0.00 10.00

Page 32 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

64 DB_COM_F3 MAIN 24.02


3P4W 380/220V
INCOMING Q01 From DB_GL_F3_R01 DS 4P 40 O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 FOR LIGHTING RCCB 4P 25 100


L1 LIGHTING MCB 2P 10 C 15 1.12 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.28 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 15 0.28 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 15 0.15 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 SPARE MCB 2P 10 C 15
L8 SPARE MCB 2P 10 C 15
L9 SPARE MCB 2P 10 C 15
LE EXIT & EMER MCB 2P 10 C 15 0.18 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE1 EXIT & EMER MCB 2P 10 C 15 0.17 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15

R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 3.90 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SOCKET OUTLET RCBO 1P+N 20 10 30 3.00 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R11 SOCKET OUTLET RCBO 1P+N 20 10 30 3.30 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R12 SOCKET OUTLET RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R13 SPARE RCBO 1P+N 20 10 30

O O
R14 Exhaust Air Fan Toilet Room 03 TEAF_3F_01 MCB 2P 16 C 15 0.06 0.70 (PB) (BMS) O O O CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

R15 SPARE MCB 2P 16 C 15

R16 OTHER MCB 3P 25 C 15


R17 OTHER MCB 3P 25 C 15
R18 OTHER MCB 3P 25 C 15
R19 OTHER MCB 3P 25 C 15

TOTAL 8.54 8.19 7.29 0.00

Page 33 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

65 DB_COM_F4 MAIN 16.83


3P4W 380/220V
INCOMING Q01 From DB_GL_F4_R01 DS 4P 40 O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 FOR LIGHTING RCCB 4P 25 100


L1 LIGHTING MCB 2P 10 C 15 1.12 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 15 0.28 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 15 0.15 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 SPARE MCB 2P 10 C 15
FROM DB_DHL_L_F4 L8 LIGHTING MCB 2P 10 C 15 0.33 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_DHL_L_F4 L9 SPARE MCB 2P 10 C 15
LE1 EXIT & EMER MCB 2P 10 C 15 0.19 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE2 EXIT & EMER MCB 2P 10 C 15 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15
1.00
R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 3.90 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SOCKET OUTLET (S7) RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R06 SOCKET OUTLET (S8) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R07 SOCKET OUTLET (S9) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R08 SOCKET OUTLET (S10) RCBO 1P+N 20 10 30 0.60 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SOCKET OUTLET (S11) RCBO 1P+N 20 10 30 1.80 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R10 SPARE RCBO 1P+N 20 10 30
R11 SPARE RCBO 1P+N 20 10 30
R12 SPARE RCBO 1P+N 20 10 30
R13 SPARE RCBO 1P+N 20 10 30

R14 SPARE MCB 2P 16 C 15


R15 SPARE MCB 2P 16 C 15

R16 OTHER MCB 3P 25 C 15


R17 OTHER MCB 3P 25 C 15
R18 OTHER MCB 3P 25 C 15
R19 OTHER MCB 3P 25 C 15

TOTAL 4.55 6.19 6.09 0.00

Page 34 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

66 DB_COM_F5 MAIN 8.99


3P4W 380/220V
INCOMING Q01 From DB_GL_F5_R01 DS 4P 40 O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 FOR LIGHTING RCCB 4P 25 100


L1 LIGHTING (L2) MCB 2P 10 C 15 0.15 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 SPARE MCB 2P 10 C 15
L3 SPARE MCB 2P 10 C 15
L4 SPARE MCB 2P 10 C 15
L5 SPARE MCB 2P 10 C 15
FROM DB_COM_L_F5 L6 LIGHTING MCB 2P 10 C 15 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F5 L7 LIGHTING MCB 2P 10 C 15 0.44 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 15 0.06 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE1 EXIT & EMER MCB 2P 10 C 15 0.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15
FROM DB_COM_L_F5 LE EXIT & EMER MCB 2P 10 C 15 0.08 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F5 LE SPARE MCB 2P 10 C 15
1.00
R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 2.40 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SPARE RCBO 1P+N 20 10 30
R06 SPARE RCBO 1P+N 20 10 30
R07 SPARE RCBO 1P+N 20 10 30
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 2.40 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SPARE RCBO 1P+N 20 10 30
R10 SPARE RCBO 1P+N 20 10 30
R11 SPARE RCBO 1P+N 20 10 30
R12 SPARE RCBO 1P+N 20 10 30
R13 SPARE RCBO 1P+N 20 10 30

R14 SPARE MCB 2P 16 C 15


R15 SPARE MCB 2P 16 C 15

R16 OTHER MCB 3P 25 C 15


R17 OTHER MCB 3P 25 C 15
R18 OTHER MCB 3P 25 C 15
R19 OTHER MCB 3P 25 C 15

TOTAL 4.19 1.64 3.16 0.00

Page 35 of 45
DRAWING NO. 1217
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

67 DB_COM_F6 MAIN 9.02


3P4W 380/220V
INCOMING Q01 From DB_GL_F6_R01 DS 4P 40 O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 FOR LIGHTING RCCB 4P 25 100


L1 SPARE MCB 2P 10 C 15
L2 LIGHTING MCB 2P 10 C 15 0.15 0.90 CU/XLPE/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 SPARE MCB 2P 10 C 15
L4 SPARE MCB 2P 10 C 15
L5 SPARE MCB 2P 10 C 15
FROM DB_COM_L_F6 L6 LIGHTING MCB 2P 10 C 15 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F6 L7 LIGHTING MCB 2P 10 C 15 0.44 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 15 0.09 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE1 EXIT & EMER MCB 2P 10 C 15 0.16 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 15
FROM DB_COM_L_F6 LE EXIT & EMER MCB 2P 10 C 15 0.08 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
FROM DB_COM_L_F6 LE SPARE MCB 2P 10 C 15

R02 SOCKET OUTLET RCBO 1P+N 20 10 30 1.20 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R03 SOCKET OUTLET RCBO 1P+N 20 10 30 1.50 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R04 SOCKET OUTLET RCBO 1P+N 20 10 30 2.40 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R05 SPARE RCBO 1P+N 20 10 30
R06 SPARE RCBO 1P+N 20 10 30
R07 SPARE RCBO 1P+N 20 10 30
R08 SOCKET OUTLET RCBO 1P+N 20 10 30 2.40 1.00 CU/PVC 1C-2.5mm2 x2+ E 1C-2.5
R09 SPARE RCBO 1P+N 20 10 30
R10 SPARE RCBO 1P+N 20 10 30
R11 SPARE RCBO 1P+N 20 10 30
R12 SPARE RCBO 1P+N 20 10 30
R13 SPARE RCBO 1P+N 20 10 30

R14 SPARE MCB 2P 16 C 15


R15 SPARE MCB 2P 16 C 15

R16 OTHER MCB 3P 25 C 15


R17 OTHER MCB 3P 25 C 15
R18 OTHER MCB 3P 25 C 15
R19 OTHER MCB 3P 25 C 15

TOTAL 4.04 1.82 3.16 0.00

Page 36 of 45
DRAWING NO. 1218
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Status
Feeder No. Panel Name Load Name Interlock Remark

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

68 SB_GS_F1_A MAIN 4.20


1P2W 220V
INCOMING 1 From CP_GS_F2_A_R08 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F1_A (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 PCM A / F1_A (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 GS_F1_STS MCB 2P 16 C 15 2.1 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R04 CP_CBS_A MCB 2P 10 C 15 1.1 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 1.00 0.00 0.00 3.20

69 SB_GS_F1_B MAIN 4.20


1P2W 220V
INCOMING 1 From CP_GS_F2_B_R08 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F1_B (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 PCM B / F1_B (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R03 GS_F1_STS MCB 2P 16 C 15 2.1 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R04 CP_CBS_B MCB 2P 10 C 15 1.1 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 1.00 0.00 0.00 3.20

70 SB_GS_F2_A MAIN 0.90


1P2W 220V
INCOMING 1 From CP_GS_F2_A_R01 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F1_A (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 GS_F2_STS MCB 2P 16 C 15 0.40 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 0.90 0.00 0.00 0.00

71 SB_GS_F2_B MAIN 0.90


1P2W 220V
INCOMING 1 From CP_GS_F2_B_R01 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F1_B (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 GS_F2_STS MCB 2P 16 C 15 0.40 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 0.90 0.00 0.00 0.00

Page 37 of 45
DRAWING NO. 1218
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Status
Feeder No. Panel Name Load Name Interlock Remark

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

72 SB_GS_F3_A MAIN 1.20


1P2W 220V
INCOMING 1 From CP_GS_F2_A_R02 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F3_A (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 GS_F3_STS MCB 2P 16 C 15 0.70 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 1.20 0.00 0.00 0.00

73 SB_GS_F3_B MAIN 1.20


1P2W 220V
INCOMING 1 From CP_GS_F2_B_R02 MCB 2P 16 C 15 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
RCCB 2P 20 100

OUTGOING R01 PCM Remote I/O / F3_B (50W) MCB 2P 10 C 15 0.50 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R02 GS_F3_STS MCB 2P 16 C 15 0.70 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 1.20 0.00 0.00 0.00

Page 38 of 45
DRAWING NO. 1218
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Status
Feeder No. Panel Name Load Name Interlock Remark

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

74 CP_GS_F2_B MAIN 7.50


3P4W 380/220V
INCOMING 1 From SB_MNBL_F2_B_R03 MCCB 4P 100 40 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 BMS/General Security Switch. Floor 2. MCB 2P 32 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
C P_G S_F2_B
R02 BMS/General Security Switch. Floor 3. MCB 2P 40 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
CP_GS_F3_B
R03 BMS/General Security Switch. Floor 4. MCB 2P 32 C 15 0.95 FUTURE
CP_GS_F4_B
R04 BMS/General Security Switch. Floor 5. MCB 2P 16 C 15 0.95 FUTURE
CP_GS_F5_B
R05 BMS/General Security Switch. Floor 6. MCB 2P 32 C 15 0.95 FUTURE
CP_GS_F6_B
R06 BMS/General Security Switch. RT. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
GS_RT_STS
R07 BMS/General Security Switch. Basement. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
GS_BM_STS
R08 BMS/General Security Switch. Floor 1. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
CP_GS_F1_B

TOTAL 0.00 0.00 0.00 7.50

75 CP_GS_F2_A MAIN 7.50


3P4W 380/220V
INCOMING 1 From SB_MNBL_F2_A_R02 MCCB 4P 100 40 LSI O O CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

OUTGOING R01 BMS/General Security Switch. Floor 2. MCB 2P 32 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
C P_G S_F2_A
R02 BMS/General Security Switch. Floor 3. MCB 2P 40 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
CP_GS_F3_A
R03 BMS/General Security Switch. Floor 4. MCB 2P 32 C 15 0.95 FUTURE
CP_GS_F4_A
R04 BMS/General Security Switch. Floor 5. MCB 2P 16 C 15 0.95 FUTURE
CP_GS_F5_A
R05 BMS/General Security Switch. Floor 6. MCB 2P 32 C 15 0.95 FUTURE
CP_GS_F6_A
R06 BMS/General Security Switch. RT. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
GS_RT_STS
R07 BMS/General Security Switch. Basement. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
GS_BM_STS
R08 BMS/General Security Switch. Floor 1. MCB 2P 16 C 15 0.95 CU/XLPE/PVC 1C-6mm2 x2+ E 1C-6
CP_GS_F1_A

TOTAL 0.00 0.00 0.00 7.50

Page 39 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

76 DB_COM_L_F3 MAIN 2.98


3P4W 380/220V
INCOMING Q01 From DB_MBL_F3_R01 MCCB 4P 32 32 TMD CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q RCCB 4P 32 100 O

OUTGOING L1 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5


L2 LIGHTING MCB 2P 10 C 10 0.44 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 SPARE MCB 2P 10 C 10
L4 SPARE MCB 2P 10 C 10
L5 SPARE MCB 2P 10 C 10
L6 LIGHTING MCB 2P 10 C 10 0.80 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 10 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L8 LIGHTING MCB 2P 10 C 10 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 10 0.18 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE SPARE MCB 2P 10 C 10 0.90

TOTAL 1.08 0.92 0.98 0.00

77 DB_DHL_L_F3 MAIN 5.45


3P4W 380/220V
INCOMING Q01 From DB_MBL_F3_R02 MCCB 4P 32 32 TMD CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q RCCB 4P 32 100 O

OUTGOING L1 LIGHTING MCB 2P 10 C 10 0.48 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5


L2 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 10 0.52 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 10 0.36 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L8 LIGHTING MCB 2P 10 C 10 0.52 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L9 LIGHTING MCB 2P 10 C 10 0.60 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L10 LIGHTING MCB 2P 10 C 10 0.24 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
SPARE MCB 2P 10 C 10
LE EXIT & EMER MCB 2P 10 C 10 0.33 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
SPARE MCB 2P 10 C 10

TOTAL 1.92 1.48 2.05 0.00

78 DB_DHL_L_F2 MAIN 5.50


3P4W 380/220V
INCOMING Q01 From DB_MBL_F3_R03 MCCB 4P 32 32 TMD CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q RCCB 4P 32 100 O

OUTGOING L1 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5


L2 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
SPARE MCB 2P 10 C 10 0.90

TOTAL 0.00 0.00 0.00 0.00

Page 40 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

79 DB_DHL_F3 MAIN 5.30


3P4W 380/220V
INCOMING Q01 From DB_GL_F3_R02 MCCB 4P 32 32 TMD CU/XLPE/PVC 1C-6mm2 x4+ E 1C-6
Q RCCB 4P 32 100 O
0.90
OUTGOING L1 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L2 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L3 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L4 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L5 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L6 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L7 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L8 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L9 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L10 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
L11 LIGHTING MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
LE EXIT & EMER MCB 2P 10 C 10 0.90 CU/PVC 1C-1.5mm2 x2+ E 1C-1.5
SPARE MCB 2P 10 C 10

TOTAL 0.00 0.00 0.00 0.00

80~83 MCCB_BOX_40A 4 sets MAIN 0.00


3P4W 380/220V
INCOMING BUSBAR
IN CU/XLPE/PVC 4x1C-240mm2 + E 1C-120
OUT CU/XLPE/PVC 4x1C-240mm2 + E 1C-120

OUTGOING R01 TO DB PANEL MCCB 4P 40 40 25 TMD CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10

TOTAL 0.00 0.00 0.00 0.00

84 MCCB_BOX_63A 1 set MAIN 0.00


3P4W 380/220V
INCOMING BUSBAR
IN CU/XLPE/PVC 4x1C-95mm2 + E 1C-50
OUT CU/XLPE/PVC 4x1C-70mm2 + E 1C-35

OUTGOING R01 TO DB PANEL MCCB 4P 63 63 25 TMD CU/XLPE/PVC 1C-16mm2 x4+ E 1C-16

ĐÃ THAY ĐỔI
TOTAL 0.00 0.00 0.00 0.00

Page 41 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

84 CP_CT_RT_01 MAIN 26.50


3P4W 380/220V
INCOMING Q01 From CP_CH_F1_01_R01 MCCB 4P 100 100 25 TMD O O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16

BOM 125/100, NẾU ĐỔI ĐƯỢC 100/100 THÌ OK,


KHÔNG THÌ SỬ DỤNG 125/100 VẪN BÌNH THƯỜNG O
OUTGOING R01 Cooling Tower CT_F7_1 MCCB 3P 100 75 25 TMD 18.50 0.80 VSD O (BMS) O O O CU/XLPE/PVC 1C-16mm2 x3+ E 1C-16
Bơm bùn R02 CTCP-F7-1 MCCB 4P 40 40 25 TMD 7.50 0.85 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
Water Level C.P R03 CP-WLC-1 MCB 2P 16 C 15 0.40 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R04 CP-Chemical MCB 2P 16 C 15 0.10 0.90 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5

TOTAL 0.40 0.10 0.00 26.00

85 CP_CT_RT_02 MAIN 26.40


3P4W 380/220V
INCOMING Q01 From CP_CH_F1_02_R01 MCCB 4P 100 100 25 TMD O O CU/XLPE/PVC 1C-25mm2 x4+ E 1C-16

O
OUTGOING R01 Cooling Tower CT_F7_2 MCCB 3P 100 75 25 TMD 18.50 0.80 VSD O (BMS) O O O CU/XLPE/PVC 1C-16mm2 x3+ E 1C-16
Bơm bùn R02 CTCP-F7-2 MCCB 4P 40 40 25 TMD 7.50 0.85 CU/XLPE/PVC 1C-10mm2 x4+ E 1C-10
Water Level C.P R03 CP-WLC-2 MCB 2P 16 C 15 0.40 0.95 CU/XLPE/PVC 1C-2.5mm2 x4+ E 1C-2.5
R04 SPARE MCB 2P 16 C 15

TOTAL 0.40 0.00 0.00 26.00

86 CP_CDWP_F1_01 MAIN 30.20


3P4W 380/220V
INCOMING Q01 From CP_CH_F1_01_R02 MCCB 3P+N 160 160 25 TMD O O CU/XLPE/PVC 1C-35mm2 x4+ E 1C-25

O
OUTGOING Condenser Water Pump CDWP_F1_01 DIRECT TO VSD 30.00 0.86 VSD O (BMS) O O O CU/XLPE/PVC 1C-25mm2 x3+ E 1C-25
R01 DDC_RF_CPM MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 0.20 0.00 0.00 30.00

87 CP_CDWP_F1_02 MAIN 30.20


3P4W 380/220V
INCOMING Q01 From CP_CH_F1_02_R02 MCCB 3P+N 160 160 25 TMD O O CU/XLPE/PVC 1C-35mm2 x4+ E 1C-25

O
OUTGOING Condenser Water Pump CDWP_F1_02 DIRECT TO VSD 30.00 0.86 VSD O (BMS) O O O CU/XLPE/PVC 1C-25mm2 x3+ E 1C-25
R02 DDC_RF_CPM MCB 2P 16 C 15 0.20 0.95 CU/XLPE/PVC 1C-2.5mm2 x2+ E 1C-2.5

TOTAL 0.20 0.00 0.00 30.00

Page 42 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Control

Remote

Remote
Feeder No. Panel Name Load Name Power Factor Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Circuit
(kA) (mA) Unit R
MCB)

94 CP_MUWP_1B MAIN 5.60


3P4W 380/220V
INCOMING Q01 From SB_SP_BF_B_R01 MCB 4P 32 C 15 O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4

O
OUTGOING R01 Make-up Water Transfer Pump MUWPTP_B_1B MCB 3P 32 C 15 5.50 0.81 DOL O (BMS) O O O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 24VAC Block inside panel for Water Filter MCB 2P 10 C 15 0.10 0.90 24VDC - 240W Power on the Panel CU/XLPE/PVC 1C-1.5mm2 x2+ E 1C-1.5

TOTAL 0.10 0.00 0.00 5.50

95 CP_MUWP_2B MAIN 5.50


3P4W 380/220V
INCOMING Q01 From SB_SP_BF_B_R02 MCB 4P 32 C 15 O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4

ĐÃ THAY ĐỔI
O
OUTGOING R01 Make-up Water Transfer Pump MUWPTP_B_2B MCB 3P 32 C 15 5.50 0.81 DOL O (BMS) O O O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 SPARE MCB 2P 10 C 15

TOTAL 0.00 0.00 0.00 5.50

96 CP_MUWP_1A MAIN 5.60


3P4W 380/220V
INCOMING Q01 From SB_SP_BF_A_R01 MCB 4P 32 C 15 O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4

ĐÃ THAY ĐỔI
O
OUTGOING R01 Make-up Water Transfer Pump MUWPTP_B_1A MCB 3P 32 C 15 5.50 0.81 DOL O (BMS) O O O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
(SPARE) R02 24VAC Block inside panel for Water Filter MCB 2P 10 C 15 0.10 24VDC
0.90
Power on the Panel

TOTAL 0.10 0.00 0.00 5.50

97 CP_MUWP_2A MAIN 5.50


3P4W 380/220V
INCOMING Q01 From SB_SP_BF_A_R02 MCB 4P 32 C 15 O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4

ĐÃ THAY ĐỔI
O
OUTGOING R01 Make-up Water Transfer Pump MUWPTP_B_2A MCB 3P 32 C 15 5.50 0.81 DOL O (BMS) O O O CU/XLPE/PVC 1C-4mm2 x4+ E 1C-4
R02 SPARE MCB 2P 10 C 15

TOTAL 0.00 0.00 0.00 5.50

Page 43 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Feeder No. Panel Name Load Name Interlock Remark

Status

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local
Local

Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

100 CP_FAN_RT MAIN 17.75


3P4W 380/220V
INCOMING 1 From DB_GL_RT_R04 MCCB 4P 63 63 15 LSI O CU/XLPE/FR/PVC 1C-16mm2 x4+ E 1C-16

OUTGOING R01 Pressure Fan PSAF_RF_01_D MCCB 3P 50 50 15 TMD 11.00 0.70Pressure Diff. Sensor
VSD O O O O O CU/XLPE/FR/PVC 1C-10mm2 x6+ E 1C-10
R02 Pressure Fan PSAF_RF_02_D MCCB 3P 20 20 15 TMD 4.00 0.70Pressure Diff. Sensor
VSD O O O O O CU/XLPE/FR/PVC 1C-2.5mm2 x3+ E 1C-2.5
R03 Smoke Exhaust Fan SEAF_RF_01_D MCCB 3P 16 16 15 TMD 2.20 0.70MotorDamper x6 sets
DOL O O O O O CU/XLPE/FR/PVC 1C-2.5mm2 x3+ E 1C-2.5
R04 Fresh Air Fan FAF_RF_01_D MCCB 3P 16 16 15 TMD 0.55 0.70 DOL O O O O O CU/XLPE/FR/PVC 1C-2.5mm2 x3+ E 1C-2.5
All interlock with FAPush
Signal
Button BMS
R05 24VDC Power MCB 2P 16 16 15

TOTAL 0.00 0.00 0.00 17.75

NOTE: PHẦN CONTROL CỦA CÁC QUẠT NÀY ĐƯỢC THỰC HIỆN BỞI NHÀ THẦU KHÁC

Page 44 of 45
DRAWING NO.
Breaker Protection Relay Meter Load (KW) Control Signal
Circuit Cuver Power Control

Remote

Remote
Status
Feeder No. Panel Name Load Name Interlock Remark

Status

Status
by PB

Motor
Other
Icu RC Trip OC&EF

Local

Local
Auto

Trip
No. Type Pole AF AT (for OCR EFR PQM PM R-N S-N T-N R-S-T Factor Circuit
(kA) (mA) Unit R
MCB)

101 DB_FFP MAIN 154.00


3P4W 380/220V
INCOMING 1 From MSB General Loads DS 4P 400 O CU/XLPE/FR/PVC 4x1C-185mm2 + E 1C-95
MSB_F2_GL

OUTGOING R01 Electrical Pump EFP_7 MCCB 3P+N 250 225 25 TMD 75.00 0.92 Direct CU/XLPE/FR/PVC 4x1C-120mm2 + E 1C-70
R02 Electrical Pump EFP_8 MCCB 3P+N 250 225 25 TMD 75.00 0.92 Direct CU/XLPE/FR/PVC 4x1C-120mm2 + E 1C-70
R03 Jokey Pump JP_4 MCCB 3P+N 20 20 25 TMD 4.00 0.92 Direct CU/XLPE/FR/PVC 4x1C-2.5mm2 + E 1C-2.5
R04 ĐOÀN NHẤT PUMP MCCB 3P+N 20 20 25 TMD By Other
R05 SPARE MCB 2P 20 C 25

TOTAL 0.00 0.00 0.00 154.00

Page 45 of 45