Académique Documents
Professionnel Documents
Culture Documents
2 1
20 1.9 2.8 2
25 2.3 3.5 3
32 1.8 2.9 4.4 4
40 1.8 2.3 3.7 5.5 5
50 1.8 2.0 2.9 4.6 6.9 6
63 1.8 2.0 2.5 3.6 5.8 8.6 7
75 1.9 2.3 2.9 4.3 6.8 10.3 8
90 2.2 2.8 3.5 5.1 8.2 12.3 9
110 2.7 3.4 4.2 6.3 10.0 15.1 10
125 3.1 3.9 4.8 7.1 11.4 17.1 11
140 3.5 4.3 5.4 8.0 12.7 19.2 12
160 4.0 4.9 6.2 9.1 14.6 21.9 13
180 4.4 5.5 6.9 10.2 16.4 24.6 14
200 4.9 6.2 7.7 11.4 18.2 27.4 15
225 5.5 6.9 8.6 12.8 20.5 30.8 16
250 6.2 7.7 9.6 14.2 22.7 34.2 17
280 6.9 8.6 10.7 15.9 25.4 38.3 18
315 7.7 9.7 12.1 17.9 28.6 43.1 19
355 8.7 10.9 13.6 20.1 32.2 48.5 20
400 9.8 12.3 15.3 22.7 36.3 54.7 21
450 11.0 13.8 17.2 25.5 40.9 61.5 22
500 12.3 15.3 19.1 28.4 45.4 68.3 23
560 13.7 17.2 21.4 31.7 50.8 24
630 15.4 19.3 24.1 35.7 57.2 25
710 17.4 21.8 27.2 40.2 64.5 26
800 19.6 24.5 30.6 45.3 27
900 22.0 27.6 34.4 51.0 28
1000 24.5 30.6 38.2 56.7 29
1100 26.9 33.7 42.0 62.4 30
1200 29.4 36.7 45.9 68.0 31
1400 34.4 42.9 53.5 32
1600 39.2 49.0 61.2 33
Dn [mm] 2 1/2 3.2 4 6 10 16
Presiones nominales PN [bar]
HDPE PE80 DIN 8074 / ISO 4427
Espesor [mm]
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
2
7 1/2 21.3 1.65 2.11 - 2.41 2.77 - 3.73 - 0 - 4.78 2.77 3.73 7.47
8 3/4 26.7 1.65 2.11 - 2.41 2.87 - 3.91 - 0 - 5.56 2.87 3.91 7.82
9 1 33.4 1.65 2.77 - 2.9 3.38 - 4.55 - 0 - 6.35 3.38 4.55 9.09
10 1 1/2 48.3 1.65 2.77 - 3.18 3.68 - 5.08 - 0 - 7.14 3.68 5.08 10.15
11 2 60.3 1.65 2.77 - 3.18 3.91 - 5.54 - 0 - 8.74 3.91 5.54 11.07
12 3 88.9 2.11 3.05 - 4.78 5.49 - 7.62 - 0 - 11.13 5.49 7.62 15.24
13 4 114.3 2.11 3.05 - 4.78 6.02 - 8.56 - 11.13 - 13.49 6.02 8.56 17.12
14 5 141.3 2.77 3.4 - - 6.55 - 9.53 - 12.7 - 15.88 6.55 9.53 19.05
15 6 168.3 2.77 3.4 - - 7.11 - 10.97 - 14.27 - 18.26 7.11 10.97 21.95
16 8 219.1 2.77 3.76 6.35 7.04 8.18 10.31 12.7 15.09 18.26 20.62 23.01 8.18 12.7 22.23
17 10 273 3.4 4.19 6.35 7.8 9.27 12.7 15.09 18.26 21.44 25.4 28.58 9.27 12.7 25.4
18 12 323.8 3.96 4.57 6.35 8.38 10.31 14.27 17.48 21.44 25.4 28.58 33.32 9.53 12.7 25.4
19 14 355.6 3.96 6.35 7.92 9.53 11.13 15.09 19.05 23.83 27.79 31.75 35.71 9.53 12.7 -
20 16 406.4 4.19 6.35 7.92 9.53 12.7 16.66 21.44 26.19 30.96 36.53 40.49 9.53 12.7 -
21 18 457 4.19 6.35 7.92 11.13 14.27 19.05 23.83 29.36 34.93 39.67 45.24 9.53 12.7 -
22 20 508 4.78 6.35 9.53 12.7 15.09 20.62 26.19 32.54 38.1 44.45 50.01 9.53 12.7 -
23 22 559 4.78 6.35 9.53 12.7 - 22.23 28.58 34.93 41.28 47.63 53.98 9.53 12.7 -
24 24 610 5.54 6.35 9.53 14.27 17.48 24.61 30.96 38.89 46.02 52.37 59.54 9.53 12.7 -
25 26 660 - 7.92 12.7 15.88 - - - - - - - 9.53 12.7 -
26 28 711 - 7.92 12.7 - - - - - - - - 9.53 12.7 -
27 30 762 6.35 7.92 12.7 15.88 - - - - - - - 9.53 12.7 -
28 32 813 - 7.92 12.7 15.88 17.48 - - - - - - 9.53 12.7 -
29 34 864 - 7.92 12.7 15.88 17.48 - - - - - - 9.53 12.7 -
30 36 914 - 7.92 12.7 15.88 19.05 - - - - - - 9.53 12.7 -
31 38 965 - - - - - - - - - - - 9.53 12.7 -
32 40 1016 - - - - - - - - - - - 9.53 12.7 -
33 42 1067 - - - - - - - - - - - 9.53 12.7 -
34 44 1118 - - - - - - - - - - - 9.53 12.7 -
35 46 1168 - - - - - - - - - - - 9.53 12.7 -
36 48 1219 - - - - - - - - - - - 9.53 12.7 -
Index
2. Equation's derivation
Receiver volume
Compressor flow rate
3. Atlas Copco
Chapter 5. pdf
4. Pressure drop
According example [5]
Rev. cjc. 15.04.2016
www.piping-tools.net
Dimensioning _compressed_air_installations_Atlas_Copco
cjcruz[at]piping-tools.net
Compressor system design [1]
2.- Compressor
Compressed Air Requirement
The nedd consists of three compressed air consumers, with following requirements
Air flow rate of case 1. Units change from Nm³/min to l/s (FAD) Flow rate requirements
V2 = V1 * (P1 - RH1 * Psat.water_1) / (P2 - RH2 * Psat.water_2) * (T2 / T1) Eq. (21) V1 =
V1 = 12 Nm3/min V2 =
P1 = 101,325 Pa State 1: Normal air conditions V3 =
RH1 = 0 - State 2: Local amb. air conditions Total requirement to be sup
t1= 0 °C and also compressor intake Vreq_ =
T1 = 273.15 K conditions Considering a safety margi
Psat.water_1 = #VALUE! Pa SM =
P2= 101,325 Pa Free air delivery (FAD) is the volume The Safety Factor is
RH2 = 0.6 - of air delivered under the conditions SF =
t2= 30 °C of temperature and pressure existing The required flow rate is
T2 = 303 K at the compressor's intake (state 2). Vreq =
Psat.water_2 = #VALUE! Pa SF =
V2 = #VALUE! m /min (FAD)
3 Vreq =
V2 = #VALUE! l/s (FAD) Vreq =
Compressor power
Normal density
Mass flow rate of dry air rn = p / ( R * T)
Vreq_N = #VALUE! Nm3/h p= 101,325 Pa
With Safety Factor R= 286.9 J/(kg*K)
FS = 1.15 T= 273 K
rn = 1.29 kg/Nm3
Ambient conditions
Patm = 101.33 kPa Air mass flowrate
tatm = 30 °C m= Q*r
RH = 60 % Q= #VALUE! Nm3/h
rn = 1.29 kg/Nm3
Air isentropic exponent mda = #VALUE! kg_da/h
g= 1.4 mda = #VALUE! kg_da/s
Compressor
Compressor inlet conditions
Compressor
Compressor eficiency hc = 0.8 -
Compressor power Wc = #VALUE! kW
Compressor motor Wm = 185 kW
Frequency
f= 1 cycle/30 s
Buffer time (Note 1)
t = 30 s/cycle Vrec =0.25*(Q /( fmax * DPL_U ) )*( Tin_receiver/Tin_comp)
.
during a cycle .
DPop = 0.5 bar V = 450 l/s (FAD)
Compressor FAD flow rate t = 30 s/cycle
QC = 450.0 l/s FAD DPL_U = 0.5 bar
Compressor intake temperature Temperature at the air receiver inlet
tcomp_in = 20 °C Tin_receiver = 308.15 K
Tcomp_in = 293.15 K Compresors maximum intake temperature
Receiver inlet air temperature Tin_Comp = 293.15 K
trcv_in = tAC_air_out Vrec = 7,095 l
tAC_air_out = 35.0 °C Vrec = 7.10 m3
trcv_in = 35.0 °C
Trcv_in = 308.15 K
Reciver inlet pressure
Prcv_in = PAC_air_out For notes, see next page
PAC_air_out = 6.860 bar (g)
Prcv_in = 6.860 bar (g) For a general case, see: www.piping-tools.net
5.- Dryer
Inlet data
t1 = 35.0
q=ṁ da⋅[ ( h da,1−hda,2 ) + x1⋅h w,1−x 2⋅h w,2 ] (g)
f1 = #VALUE!
x1 = #VALUE!
q= mda * ( (h1 - h2) +x1*hW1 - x2*hW2 )
Outlet data
mda = #VALUE! kgda/s t2 = 5
hda,1 = #VALUE! kJ/kgda f2 = 100
hda,2 = #VALUE! kJ/kgda x2 = #VALUE!
x1 = #VALUE! kgw/kgda
x2 = #VALUE! kgw/kgda Change in water content
hw1 = #VALUE! kJ/kgw Dx = x1 - x 2
hw2 = #VALUE! kJ/kgw x1 = #VALUE!
q= #VALUE! kW x2 = #VALUE!
Dx = #VALUE!
f1
x1
x2
t2 t1
5. Dryer
Dryer inlet conditions
The water comming out of the refrigerant dryer wil be contaminated, since this water has been car
Aftercooler
Aftercooler pressure drop
Pressure drop in th system [1] 7 [kPa] < DP
Estimation example Let
DPAC =
DPAC =
Note 1. This example could not consider exactly the publication [1], Kelvin
since different equipments do not use allways the outputs from Kelv = 273.15
previous equipment.
Table 2. Consumer's requirements, with all air flows in l/s(FAD) and pressures in bar (g)
Consumer Air flow Pressure Dew Point
1 #VALUE! l/s (FAD) 6 bar(g) 5
2 67 l/s (FAD) 5.99 bar(g) 5
3 95 l/s (FAD) 4 bar(g) 5
P2 RH 2 Psat. water _ 2 T1
V1 V2 Eq. (21)
P1 RH 1 Psat. water _ 1 T2
State 2: FAD
Vreq = V2 = 1620.00 m3/h (FAD)
P2 = 101,325 Pa
RH2 = 0.6 -
Psat.water_2 = #VALUE! Pa
T2 = 303 K
Discharge temperature
Tdisch = Tin * ( 1 + ( ((Pdisch/Pin)^((k-1)/k) -1) / hc ) )
Tin = 303.15 K
Pin = 101.3 kPa
Pout = 801.3 kPa
k= 1.4 -
hc = 0.8 -
Tdisch = 608 K
tdisch = 335.2 ºC
k 1
P
desc k 1
P
Tdesc Tin 1 in
c
From
Compressor_power_and_air_discharge_ temperature
www.piping-tools.net
k -1
Note. Selection based on [5]
P2 k
c p T1 1
m
P1
P W (e)
c
k -1
P2 k
c p T1 1
m
P1
P W (e)
c
From
Compressor_power_and_air_discharge_ temperature
www.piping-tools.net
If the after cooler is part of the compressor, the cooling water will be a contaminated
water.
If the cooling occur in an heat exchanger, after the compresion, the cooling water
will be a clean water.
Heat balance
DHair = DHw
DHair = mw * D hw
DHair / D hw = mw
mw = DHair / Dhw
DHair = #VALUE! KW
Dhw = #VALUE! KJ/kg
mw = #VALUE! kg/s
mw = #VALUE! kg/s
After cooler outlet conditions
mair = S kg/s
DHair = #VALUE! KW
DPAC_air = 14.0 kPa
mw = S kg/s This is clean water, because in the heat exchanger there is not
DHw = #VALUE! KW a point were water and air with oil could come in contact
DPw_AC = 0.5 bar
.
Normal flow rate (Rem. is dry air) Prcv_in = 6.860
.Vreq_N = #VALUE! Nm3/h DPrcv_loss = #VALUE!
.
.
Vreq_N = #VALUE! Nm3/s Prcv_out_ini = #VALUE!
Prcv_out_final = Prcv_out_ini - Dpop
Application . Prcv_out_ini = #VALUE!
Vrcv = tbuffer * Vn * PN/ ( DPop) * (Trcv/TN) DPop = 0.5
.
tbuffer = 30 s/cycle Prcv_out_final = #VALUE!
Vn = #VALUE! Nm³/s
Pn = 1.01325 bar .
DPop = 0.5 bar Vcomp_N = Vrcv*(1/tcharge)*(DPop/PN)*(T
Trcv = 308.15 K Vrcv = #VALUE!
TN = 273.15 K tcharge = 60
Vrcv = #VALUE! m³ DPop = 0.5
PN = 1.01325
TN = 273.15
. Trcv = 308.15
.V req_N
= #VALUE!
w.piping-tools.net Air receivers volume calculation Vcomp_N = #VALUE!
Note 1
Buffer time is the time interval in which the the receiver is supplying the required air flow
bar (g) rate whithout receiving any compressor flow. The receiver is initially at a pressure P initial
bar and is able to deliver the required air flow rate until its pressure reach its minimum
bar(g) value Pfinal. A minimum of 15 minutes is recommended as a buffer time [10].
A large buffer time requires a large DPop
Note 2
This equation does not agree with the derived equation nor
ed an isothermal process with the in the web proposed equations. The Atlas Copco
equation replaces the value of the ambient pressure, in this
case 1.013 bar, by a value 0.25
°C
°C For a comparison of the Atlas Copco equation with other
equations published in the web and with the deducted
equation, see
www.piping-tools.net
Air receivers volume calculation
Note 3
The receiver volume, or buffer volume, is the tank volume needed to deliver the required
flow rate with a supply pressure pfinal_g , without compressor contribution, during
a time tbuffer.
Note 4
Refill time is the time required by the compressor to increase the
receiver pressure to its highest value.
iver volume
mair = S kg/s
DParc = #VALUE! kPa
kgw/kgda
kgw/kgda
kgw/kgda
Dryer outlet conditions
mair = #VALUE! kg/s The dryer exit presure, when the receiver is
V= 0.45 m³/s supplying at its minimum pressure is
DPdryer = 0.090 bar Pdryer_out_final is #VALUE! bar (g)
The maximum pressure drop between the dryer
mw_cond = #VALUE! kgw / h exit and the las consumption point has been
q= #VALUE! kW estimated as
DPpipes = 0.15 bar
Thus, the supplyed pressure is
Psupplyed = Pdryer_out_final - DPpipes
Pdryer_out_final = #VALUE! bar (g)
DPpipes = 0.15 bar
Psupplyed = #VALUE! bar
#VALUE!
e case, the water will be contaminated
J/(kg*K)
J/(kg*K)
Pa
-
°C
K
page 2 of 20
°C
°C
°C
page 4 of 20
page 5 of 20
g-1) / (g) ) - 1 )
kg_da/s
kJ/kg
K
-
-
-
kW
selected motor:
kW
Return
page 6 of 20
Return
arded as sufficient.
l be a contaminated
page 7 of 20
kg_da/s
KJ/kg
KW
page 8 of 20
page 9 of 20
Return
er there is not
page 10 of20
TN
p
Vreq _ N (18)
Trcv
bar (g)
bar
bar (g)
bar (g)
bar
bar (g)
.
*(DPop/PN)*(TN/Trcv) + Vreq_N
m³
s
bar
bar
K
K
Nm³/s
Nm³/s
page 11 of 20
page 13 of 20
page 14 of 20
Density in state 1
Enthalpy_t_p r1 = Sicro_Density_tdb_f_H
ºC t1 = 30 ºC
bar f1 = 50 %
kJ/kgw H= 0 m.a.s.l.
r1 = 1.155154124 kgda/m³
Dry air mass flow rate
Enthalpy_t_p m1 = V1 * r1
ºC V1 = 5 m³/s
bar r1 = 1.155154124 kgda/m³
kJ/kgw m1 = 5.77577062 kgda/s
Absolute humidity in state 1
x1 = Sicro_Absolute_Humidity_td .
Enthalpy_tdb_x_H t1 = 30 ºC
ºC f1 = 50 %
kgw / kgda H= 0 m.a.s.l.
kJ/kgda x1 = 0.013311014 kgw / kgda
Absolute humidity in state 2
x2 = Sicro_Absolute_Humidity_td .
Enthalpy_tdb_f_H t2 = 10 ºC
ºC f2 = 100 %
% H= 0 m.a.s.l.
m.a.s.l. x2 = 0.007630516 kgw / kgda
kJ/kgda
page 15 of 20
page 16 of 20
page 17 of 20
page 18 of 20
Return
page 19 of 20
page 20 of 20
0.14 bar
#VALUE! bar
0.08 bar
0.09 bar
0.08 bar
pressure drop in equipments
#VALUE! bar
pressure drop
DPequip + DPpipes
#VALUE! bar
0.15 bar
#VALUE! bar
Return
Enthalpy of water in state 1
hw1 = H2O_Enthalpy_t_p
t1 = 30 ºC
p= 1.01325 bar
hw1 = 125.7520702 kJ/kgw
Enthalpy of water in state 2
hw2 = H2O_Enthalpy_t_p
t2 = 10 ºC
p= 1.01325 bar
hw2 = 42.091837 kJ/kgw
M ass delivery during the buffer When the buffer time finishes, that
time of a cycle is when the receiver achieves its
minimum pressure (which is also
s kg
m buff m s the supply pressure), the compressor
cycle
starts supplying air to the receiver.
m : mass change [kg/cycle]
In this operation mode, the receiver
buff : buffer time. Time where the is receiving air from the compressor
receiver is delivering the required and at the same time is delivering the
constant mass flow rate m at the required flow rate to the system.
prescribed pressure, without any When the receiver reaches the
compressor inlet flow. maximum pressure (p final ), the
kg compressor stops and the charging
m buff m cycle (5) time chg finishes.
pv m³ m³ kg
From The volume flow rate can be
pv R T expressed as
pv m ³ v m ³ m kg
V (d)
R (a) s
kg
s
T
Replacing equation (d) into equation
Density of an ideal gas
p
p V V (c)
(b) R T
R T ona obtains
M ultiplying equation (b) p
V m v (e)
by the volume flow rate R T
p From ideal gas equation
V V (c) pv
R T R (a)
T
Microsoft Equation v p
3.0
Thus, the product can
T
be replaced by any group of variables
v, p and T corresponding to a given
state.
1
P
T
1
v P
1 R Trcv
f
V m comp _ in comp _ in Vcomp
f
T comp _ in
R
P op
V Pcomp _ in
f
1
v P
T
V m comp _ in comp _ in rcv
f
T comp _ in
Pop
Receiver vo lume
1
P
T
V m vcomp _ in comp _ in rcv (f) Microsoft Editor de
V [m ³] Pcomp _ in b
f
T comp _ in Pop
ecuaciones 3.0
Replacing
1
f
buffer
into equation
m3
Vcomp _ in
s Trcv K
V [m ³] Pcomp _ in bar (10)
cycles
f
T
Pop bar comp _ in
K
s
one gets
s m3
buffer Vcomp _ in s
V [m ³] Pcomp _ in bar cycle Trcv K (11)
Pop bar T comp _ in K
V Trcv
V Pcomp _ in buffer comp _ in
Pop T comp _ in
P
T
V buffer Vcomp _ in comp _ in rcv (12)
Pop
T comp _ in
m ch arg e PN Vcomp _ N Vreq _ N
1 1
TN R
(16)
V ch arg e PN Vcomp _ N Vreq _ N
1 1 R Trcv
T N R Pop
V ch arg e PN Vcomp _ N Vreq _ N
1 Trcv
T N Pop
T
V ch arg e PN Vcomp _ N Vreq _ N rcv
1
T N Pop
(17)
V ch arg e PN Vcomp _ N Vreq _ N
1 Trcv
T N Pop
T
V ch arg e PN Vcomp _ N Vreq _ N rcv
1
T N Pop
(17)
Microsoft Editor de
ecuaciones 3.0
Volume flow rate from Nm³/min From [4], page 6.2, equation (6).
Psat.water_t =
to l/s (FAD) t=
Psat.water_t =
Dehumidification
[4], page 6.12
Energy balance
Ėda,1 + Ė w,1= Ė da,1 + Ė w,1−q
ṁ da⋅hda,1 + ṁw,1⋅h w,1= ṁda⋅hda,2 +m
s m
3
m ch arg e PN Vcomp _ N Vreq _ N
1 1
TN R
(1
uffer Vcomp _ in
cycle s Trcv K
(11) T 1
Pop bar T comp _ in K V ch arg e PN Vcomp _ N Vreq _ N rcv (
T N Pop
Trcv 1 Pop T N
mp _ in
(12) Vcomp _ N V Vreq _ N (
Pop
mp _ in
Microsoft Equation
3.0
ch arg e PN Trcv
R Trcv
(3)
Pini - P final
uation (3) into equation
1
(2)
final
Trcv
P final
he operational pressure difference
1
(2)
final
Trcv
P final
he operational pressure difference
nal
olume becomes
cv
(4) Microsoft Equation
3.0
p
, the receiver kg
The delivered mass per cycle is m buff m cycle (5)
e compressor kg
m buff m (5) one obtains
delivering the cycle
1 kg
he system. m m cycle (7)
where the mass flow rate m is a constant f
ches the m V (6) Replacing equation
), the m V (6)
nal The nominal requiremen t is a constant
the charging into equation (7), one gets
volume flow rate delivered at a constant 1
m V (8)
pressure. f
e
e Replacing equation
v p 1
V m (e)
(d) T R
equation into equation
1
(c) m V (8)
f
one gets
(e) 1 v p 1
m m
f T R
Applying this equation for the
(a)
state at compressor' s inlet
can
1 vcomp _ in pcomp _ in
1
m m
(9)
variables f
T comp _ in
R
Microsoft Equation
3.0
a given
Microsoft Equation
3.0
Receiver vo lume
m3
V
f Pop T comp _ in
Vcomp _ in Trcv
V Pcomp _ in
f Pop T comp _ in
Receiver vo lume
m3
Vcomp _ in
s Trcv K
V [m ³] Pcomp _ in bar (10)
cycles
f
T
Pop bar comp _ in
K Microsoft Editor de
s ecuaciones 3.0
P
m Vcomp _ N Vreq _ N N ch arg e
R T N
m ch arg e PN Vcomp _ N Vreq _ N
1 1
TN R
(16)
Microsoft Editor de
ecuaciones 3.0
From equation
T
V ch arg e PN Vcomp _ N Vreq _ N rcv
1
T N Pop
(17)
1 TN
Vcomp _ N Vreq _ N V Pop
ch arg e PN Trcv
1 Pop T N
Vcomp _ N V Vreq _ N (18)
ch arg e PN Trcv
1 TN
Vcomp _ N Vreq _ N V Pop
ch arg e PN Trcv
1 Pop T N
Vcomp _ N V Vreq _ N (18) Microsoft Editor de
From [4], page 6.2, equation (6). Valid for a range of 0 to 200ºC
exp( -5800.2206/(t+273.15) + 1.3914993 + -0.048640239*(t+273.15) + 0.000041764768*(t+273.15 )^2 + -0.000000014452093*(t+273.15 )^3 + 6.5459673*ln(t
0 ºC
611.2 Pa
(13)
Trcv
(14)
T comp _ in
Trcv
(15)
TN
N T1
1
R
(16)
N
Trcv 1
(17)
T N Pop
Vreq _ N (18)
Microsoft Equation
3.0
Page 2 of 10
Page 3 of 10
Page 4 of 10
Page 5 of 10
Page 6 of 10
Page 7 of 10
Page 8 of 10
Page 9 of 10
Eq. (22)
*(t+273.15 )^3 + 6.5459673*ln(t+273.15 ) )
T1
water _ 2
Eq. (21)
water _ 1 T2
Page 10 of 10
(d )
( e)
Microsoft Equation
3.0
+ ṁ w,2⋅h w,2 +q (a )
(d )
( e)
Microsoft Equation
3.0
+ ṁ w,2⋅h w,2 +q (a )
da,2 − ṁ w,2⋅hw,2
hw,1 −ṁw,2⋅hw,2
− ṁw,2⋅h w,2 (f )
− ṁw,2⋅h w,2 (f )
w,1− ṁ da⋅x 2⋅hw,2
−x 2⋅h w,2 ] (g )
5.1 Example of dimensioning compressed air installations
Result is valid for relative air humidity RH 2 = 0 % (instead of 60%) , t2 = 35 °C (instead of 30 °C)
and ambient local pressure P i = 0.74 bar (instead of 1 bar)
A result of 225 l/s (FAD) comes from a pressure P = 100 kPa and a temperature of t = 30
For a pressure P = 74 kPa, a temperature of t = 35 ºC and a relative humidity of RH = 0 %
This equation does not agree with the derived equation nor with the in the web proposed equa
is
replaced for a pressure. In this case, the value 0.25 should be replaced by the value of the co
So the result would be 6.972 * ( 1/0.25) = 27.89m³. See sheet Receiver.
according Atlas Copco, 5.1 kW
[1]
5 °C (instead of 30 °C) Q= 309 l/s(FAD)
file:///E:/Motores/Electric%20Motors%20%281%20to%20500%20HP_0.746%20to%20375%20kW%29%20_%20Office%20of%
products/6885
kW%29%20_%20Office%20of%20Energy%20Efficiency.htm
nimum nominal efficiency standard at 100% of nominal full load
(Energy Efficient - least stringent level)
Corresponds to Table 2 in the CAN/CSA C390-1
Energy Efficiency Standard (Percentage)
Open Enclosed
4 Pole 6 Pole 8 Pole 2 Pole 4 Pole 6 Pole 8 Pole
82.5 80 74 75.5 82.5 80 74
84 84 75.5 82.5 84 85.5 77
84 85.5 85.5 84 84 86.5 82.5
86.5 86.5 86.5 85.5 87.5 87.5 84
86.5 86.5 86.5 85.5 87.5 87.5 84
87.5 87.5 87.5 87.5 87.5 87.5 85.5
87.5 87.5 87.5 87.5 87.5 87.5 85.5
88.5 88.5 88.5 88.5 89.5 89.5 85.5
89.5 90.2 89.5 89.5 89.5 89.5 88.5
91 90.2 89.5 90.2 91 90.2 88.5
91 91 90.2 90.2 91 90.2 89.5
91.7 91.7 90.2 91 92.4 91.7 89.5
92.4 92.4 91 91 92.4 91.7 91
93 93 91 91.7 93 93 91
93 93 91.7 92.4 93 93 91.7
93.6 93.6 92.4 93 93.6 93.6 91.7
94.1 93.6 93.6 93 94.1 93.6 93
94.1 94.1 93.6 93.6 94.5 94.1 93
94.5 94.1 93.6 94.5 94.5 94.1 93.6
95 94.5 93.6 94.5 95 95 93.6
95 94.5 93.6 95 95 95 94.1
95 94.5 93.6 95 95 95 94.1
95.4 95.4 94.5 95.4 95 95 94.5
95.4 95.4 - 95.4 95.4 95 -
95.4 95.4 - 95.4 95.4 95 -
95.4 - - 95.4 95.4 - -
95.8 - - 95.4 95.4 - -
95.8 - - 95.4 95.8 - -
Free Air Delivery (FAD) Water vapor partial pressure
Replacing equation
p v p w_sat (c)
Ideal gas law applied to the p v p w_sat
where
dry air (a) fraction of the p w_sat : saturated water pressure (Pa) into equation
humid air (ha) : air relative humidity (-) p -p T
v 2 v 1 1 v1 2
pa v R T p p 2 - pv 2 T1
v Microsoft Equation
Free air delivery (FAD) is the volume of air delivered under the conditions of
temperature and pressure existing at the compressor's intake (state 2).
into equation V2 = V1 * (P1 - RH1 * Psat.water_1) / (P2 - RH2 * Psat.water_2) * (T2 / T1)
p -p T
v 2 v 1 1 v1 2 (d) 1.- Normal flow rate (state 1) to FAD flow rate (state 2)
p 2 - pv 2 T1
one obtains Normal air conditions (State 1)
V1 = 480 Nm3/h
p1 - p w_sat_1 1 T2
v 2 v1 (21) P1 = 101,325 Pa
p 2 - p w_sat_2 2 T1 f1 = RH1 = 0 -
t1= 0 °C
Microsoft Equation
3.0
T1 = 273 K
Psat.water_1 = f(t1)
p1 - p w_sat_1 1 T2 Psat.water_1 = #VALUE! Pa
v 2 v1 (21)
p 2 - p w_sat_2 2 T1 FAD conditions (State 2))
P2 = 73,400 Pa
f2 = RH2 = 0.42 -
t2= 22 °C
Psat.water_2 = f(t2)
Psat.water_2 = #VALUE! Pa
T2 = 295 K
V2 = #VALUE! m3/h (FAD)
V1 = V2 * (P2 - RH2 * Psat.water_2) / (P1 - RH1 * Psat.water_1) * (T1 / T2) Normal density
rn = p / ( R * T)
2.- FAD flow rate (state 2) to Normal flow rate (state 1) p= 101,325
R= 286.9
FAD conditions (State 2)) T= 273
V2 = #VALUE! m3/h (FAD) rn = 1.29
P2 = 98,000 Pa
RH2 = 0.4 -
t2= 22 °C
Psat.water_2 = f(t2)
Psat.water_2 = #VALUE! Pa
T2 = 295 K
V1 = #VALUE! Nm3/h
Rev. cjc. 15.04.2016
(21)
p / ( R * T)
Pa
J/(kg*K)
K
kg/Nm3
[1] http://www.atlascopco.dk/Images/CAM_05_CALCULATION_tcm48-705084.pdf
[1a]
Compressed_Air_Manual_tcm46-1249312
[1b] http://pdf.directindustry.fr/pdf/atlas-copco-compresseurs/manuel-air-comprime-atlas-copco/8358-185247
[2]
http://www.ecompressedair.com/library-pages/aftercoolers.aspx
[4]
[5]
http://www.nrcan.gc.ca/energy/regulations-codes-standards/products/6885
[11]
http://www.engineeringtoolbox.com/air-altitude-pressure-d_462.html
Microsoft Equation
3.0
Microsoft Equation
3.0
atlas-copco/8358-185247-_60.html