Vous êtes sur la page 1sur 48

EF

"!   J  


 
'()*+,-.K0  

CHAPTER # 3 THREE-PHASE CIRCUITS


1. Introduction
Circuits or systems in which the ac sources operate at the same frequency but different
phases are known as poly phase. Fig. 1 shows a three-phase four-wire system. As
distinct from a single-phase system, a three-phase system is produced by a generator
(alternator), whose cross-sectional view is shown in Fig. 2(a). The alternator basically
consists of a rotating magnet (called the rotor) surrounded by a stationary winding
(called the stator). Three separate windings or coils with terminals a-a', b-b', and c-c'
are electrically placed 120 apart around the stator. Because the coils are placed 120
apart, the induced voltages in the coils are equal in magnitude but out of phase by
120 as shown in Fig. 2 (b). Since each coil can be regarded as a single-phase
generator by itself, the three-phase generator can supply power to both single-phase
and three-phase loads.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 1
EF "!   J  
 
'()*+,-.K0  

Generator (Source) side Load side

Fig. 1, Three-phase, 4-wire circuit

(a) 3-phase alternator (b) 3-phase voltages

Fig. 2, Generating 3-phase voltages

A typical three-phase system consists of three voltage sources connected to loads by


three or four wires (or transmission lines) using both step-up and step-down
transformers is shown in Fig. 3. The connection to a particular home is shown in Fig.
4. Finally the connection inside rooms is shown in Fig. 5.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 2
EF "!   J  
 
'()*+,-.K0  

Fig. 3, Three-phase system

Fig. 4, Connection to a particular home

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 3
EF "!   J  
 
'()*+,-.K0  

Fig. 5, Connection to a particular room

2. Balanced three-phase circuits

The three-phase sources, explained before, can be connected either wye (Y) or delta
() as shown in Fig. 6.

(a) Wye (Y) Connection (b) Delta () Connection

Fig. 6, Three-phase connection (Generator side)

Consider the wye-connected voltages in Fig. 6(a). The voltages Van, Vbn, and Vcn are
respectively between lines a, b, and c, and the neutral line n. These voltages are called
phase voltages. If the voltage sources have the same amplitude and frequency and

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 4
EF "!   J  
 
'()*+,-.K0  

are out of phase with each other by 120, the voltages are said to be balanced. This
gives

There are two possible combinations. One possibility is called positive (abc) sequence
This sequence is produced when the phasor diagram rotates counterclockwise. The
phase sequence is determined by the order in which the phasors pass through a fixed
point in the phase diagram. This can be expressed mathematically as:

The other possibility is called negative (acb) sequence and expressed mathematically
as:

Like the generator connections, a three-phase load can be either wye-connected or


delta-connected, depending on the end application as shown in Fig. 7.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 5
EF "!   J  
 
'()*+,-.K0  

(a) Wye (Y) Connection (b) Delta () Connection


Fig. 7, Three-phase connection (Load side)
For a balanced wye-connected load,

whereZY is the load impedance per phase. For a balanced delta-connected load,

where Z is the load impedance per phase.

Y-connected load can be transformed into a -connected load, or vice versa as:

Since both the three-phase source and the three-phase load can be either Y or , we
have four possible connections:

Y-Y connection (i.e., Y-connected source with a Y-connected load)


Y- connection (i.e., Y-connected source with a -connected load)
- connection (i.e., -connected source with a -connected load)
-Y connection (i.e., -connected source with a Y-connected load)

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 6
EF "!   J  
 
'()*+,-.K0  

It is appropriate to mention here that a balanced delta-connected load is more common


than a balanced Y-connected load. This is due to the ease with which loads may be
added or removed from each phase of a delta-connected load. This is very difficult
with a Y-connected load because the neutral may not be accessible. On the other hand,
delta connected sources are not common in practice because of the circulating current
that will result in the delta-mesh if the three-phase voltages are slightly unbalanced.

2.1 Balanced Y-Y three-phase circuits

Any balanced three-phase system can be reduced to an equivalent Y-Y system.


Therefore, analysis of this system should be regarded as the key to solving all
balanced three-phase systems.

Consider the 3-phase, Y-Y circuit shown in Fig. 8. Assuming the positive sequence,
the phase voltages (or line-to-neutral voltages) are:

   0, 
   120      120

Fig. 8, Y-Y three-phase circuit

The line-to-line voltages or simply line voltages Vab, Vbc, and Vca are related to the
phase voltages. mathematically as:
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 7
EF "!   J  
 
'()*+,-.K0  

Similarly, we can obtain

The relation between phase and line voltages can be proved Vectorially as in Fig. 9.

Fig. 9, Relation between phase and line voltages in Y connected circuits

From phasor diagram shown above, it is clear that the magnitude of the line voltages
VL is 3 times the magnitude of the phase voltages Vp, or

  3 

where and
Also the line voltages lead their corresponding phase voltages by 30.

Applying KVL to each phase in Fig. 8, we obtain the line currents as:

We can readily infer that the line currents add up to zero,

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 8
EF "!   J  
 
'()*+,-.K0  

so that

So that the voltage VnN is zero. Therefore, neutral line can thus be removed without
affecting the system. In fact, in long distance power transmission, conductors are used
with the earth itself acting as the neutral conductor. Power systems designed in this
way are well grounded at all critical points to ensure safety.

The line current is the current in each line, and the phase current is the current in each
phase of the source or load. In Y-Y, the line current is the same as the phase current.

  
An alternative way of analyzing a balanced Y-Y system is to consider the per phase
equivalent circuit given in Fig. 10. We look at one phase, say phase a, and analyze the
single-phase equivalent circuit. Then applying KVL for this circuit to get the same
values for the line currents.

Fig. 10, Equivalent single phase circuit


Once the current Ia is obtained, we use the phase sequence to obtain other line
currents.

EX. 1. Final Exam, First semester (1432/1433)

Three equal impedances, 60 + j30 each, are -connected to a positive sequence 100-
V three-phase supply as shown in Fig. 11. Another three equal impedances, 40 + j10
each, are Y-connected across the same circuit at the same points.

Determine:

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 9
EF "!   J  
 
'()*+,-.K0  

a) The line currents


(b) The total complex power supplied to the two loads
(c) The power factor of the two loads combined

Fig. 11

Convert the delta connected load with impedance 60 + J 30 to star connected on

for balanced load, ZY = Z / 3 = 20 + J 10

This converted Y load becomes in parallel with the original Y load

ZY = (20+J10) // (40+J10) = 13.5+J5.5

for positive sequence supply

Va = 1000 Vb = 100 120 Vc = 100120

The line current can be calculated as:


 1000
    6.86 22.166 
 13.5  5.5

100 120

   6.86 142.166 
 13.5  5.5
 100120
    6.8697.834 
 13.5  5.5

Total Complex power supplied to the two loads = 3Va Ia*= 31006.8622.166

= 1905.9027 + J 776.4655 VA

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 10
EF "!   J  
 
'()*+,-.K0  

Power factor of the combined load is cosine the angle between the voltage and current

= cos(22.166) = 0.9261 Lagging

Report:

A Y-connected balanced three-phase generator with an impedance of 0.4+j0.3 per


phase is connected to a Y-connected balanced load with an impedance of 24 + j19
per phase. The line joining the generator and the load has an impedance of 0.6 + j0.7
per phase. Assuming a positive sequence for the source voltages and that Van =
120 30 V, find: (a) the line voltages, (b) the line currents.

three-phase circuits
2.2 Balanced Y-

The balanced Y-delta system is shown in Fig. 12, where the source is Y-connected and
the load is -connected. There is no neutral connection from source to load for this
case. Assuming the positive sequence, the phase voltages are again:

Fig. 12. Y- three-phase circuit


The line voltages are given as:

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 11
EF "!   J  
 
'()*+,-.K0  

The line voltages are equal to the voltages across the load impedances for this system
configuration. From these voltages, we can obtain the phase currents as:

These currents have the same magnitude but are out of phase with each other by 120.

The line currents are obtained from the phase currents by applying KCL at nodes A, B,
and C. Thus,

This gives that

The relation between phase and line currents for -connected circuits is shown in
Fig.13.

Fig. 13, Relation between phase and line currents in -connected circuits

From phasor diagram above, the magnitude IL of the line current is 3 times the
magnitude Ip of the phase current, or
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 12
EF "!   J  
 
'()*+,-.K0  

  3 
where

and

Also, the line currents lag the corresponding phase currents by 30.

EX. 2. Final Exam, Second semester (1428/1429)


Determine the phase and line currents of the delta connected, +ve sequence load shown in
Fig. 14. Known that Z = 60 45

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 13
EF "!   J  
 
'()*+,-.K0  

An alternative way of analyzing the Y- circuit is to transform the -connected load


to an equivalent Y-connected load. Using the -Y transformation formula

EX. 2. Final Exam, First semester (1430/1431)


For the three-phase Y- circuit shown in Fig. 15, calculate the line and phase currents
of the load. Assume that ZL = 12 + j2

Fig. 15
"#$%#
 4  '0.667
&
Converting the 3-ph load from to Y then load impedance ZY =

In that case the transmission line impedance (ZT) will be in series with ZY
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 14
EF "!   J  
 
'()*+,-.K0  

Overall load impedance = ZY + ZT = 4 + j0.667 + 1 + j2 = 5 + j2.667


() "---
  17.647 28.075 A
*+ $ *, .$%#.//0
IA (Line) =

IB (Line) =17.647 28.075 120  17.647 148.075 A


IC (Line) =17.647 28.075  120  17.647 91.925 A
"
&
As we know, for connection, IPh is less than ILine by and lead by 30
"0./10
28.075  30  10.1891.925 A
&
IAB (Phase) =

IBC (Phase) = 10.1891.925 120  10.189 118.075 A


IBC (Phase) = 10.1891.925  120  10.189121.925 A
Report:

One line voltage of a balanced Y-connected source is VAB = 180 20 V. If the


source is connected to a -connected load of 20 40, find the phase and line
currents. Assume the abc sequence.

2.3 Balanced -
three-phase circuits

The source as well as the load is delta-connected as shown in Fig. 16. Our goal is to
obtain the phase and line currents as usual. Assuming a positive sequence, the phase
voltages for a delta-connected source are:

Fig. 16, Delta-Delta 3-phase system

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 15
EF "!   J  
 
'()*+,-.K0  

The line voltages are the same as the phase voltages. From Fig. 16, assuming there is
no line impedances, the phase voltages of the delta connected source are equal to the
voltages across the impedances; that is,

Hence, the phase currents are

The line currents Ia, Ib and Ic are greater than the phase current by 3 and lag the
corresponding phase current by 30.

EX. 3. First Mid-term Exam, First semester (1431/1432)

A three-phase, positive sequence - connected circuit with a line impedance of 1 +


j3 . The line feeds a balanced load, which absorbs a total complex power of 12 + j5
kVA. If the line voltage VAB at the load side is 2400 V, calculate:

a) The line and phase currents at the load side,


b) The line voltage (Vab) at the source side
c) The source power factor.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 16
EF "!   J  
 
'()*+,-.K0  

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 17
EF "!   J  
 
'()*+,-.K0  

Report:

A positive-sequence, balanced -connected source supplies a balanced -connected


load. If the impedance per phase of the load is 18+j12 and Ia = 22.5 35 A, find
IAB and VAB.

2.4 Balanced -Y three-phase circuits

Consider the -Y circuit in Fig. 17. Again, assuming the abc sequence, the phase
voltages of a delta-connected source are:

Fig. 17, -Y 3-phase system

At source side, the line voltages, given above, are also same as the phase voltages.

At load side the phase voltage VAN is less than the line voltage VAB by 3 and lags it
by 30, therefore, the line current (which equals the phase current) Ia can be obtained
as:

we obtain the other line currents Ib and Ic using the positive phase sequence,
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 18
EF "!   J  
 
'()*+,-.K0  

EX. 1. First Mid-Term Exam, First semester (1429/1430)

For the 3-phase, +ve sequence circuit shown in Fig. 18, if Vab = 44010. Calculate
the load currents, and then calculate the complex power at the source side.

Fig. 18, 3-phase -Y circuit

Report:

In a balanced -Y, negative sequence circuit, Vac = 240 15 and ZY = (12 + j15) .
Calculate the line currents.
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 19
EF "!   J  
 
'()*+,-.K0  

3. Power in Balanced 3-phase systems

For a Y-connected load, let the phase voltages are:

where Vp is the rms value of the phase voltage.


If the load impedance is ZY = Z , then the phase currents lag behind their
corresponding phase voltages by . Thus,

where Ip is the rms value of the phase current.

The total instantaneous power in the load is the sum of the instantaneous powers in the
three phases; that is,

Based on the trigonometric relation:

Assuming that = cos(2t - )

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 20
EF "!   J  
 
'()*+,-.K0  

Thus the total instantaneous power in a balanced three-phase system is constant. It


does not change with time as the instantaneous power of each phase does. This result
is true whether the load is Y- or -connected.

-The active power (P) can be calculated as:

2  3   cos 6  3   cos 6

-Also, The reactive power (Q) can be calculated as:

7  3   sin 6  3   sin 6

- -The complex power (S) can be calculated as:

:  3    3  

First mid-term exam (Repeated), second semester 1433/1434

Four 3-phase, Y-connected, positive-sequence, balanced loads are connected to a 380-


V, 50-Hz line, as shown in Fig. 19-A. Rewrite Table 1 in your answer sheet and fill
the missing values.

Table 1
Combined
Load #1 Load#2 Load #3 Load #4
Load
Apparent Power ? ? 20 kVA 35 kVA ?
Active Power ? 30 kW 15 kW ? ?
Reactive Power 35 kVAR ? ? 20 kVAR ?
Line Current ? ? ? ? ?
Power Factor 0.6 lag 0.8 lead ? (lag) ? ?

To raise the combined load power factor to 0.98 lag, three capacitors -connected in
parallel with the combined load as shown in Fig. 19-B. Calculate the kVAR rating of
each capacitor, then find the capacitance of each capacitor.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 21
EF "!   J  
 
'()*+,-.K0  

Fig. 19-A

Fig. 19-B

Load #1

Q1 = 35 kVAR

P.F.1 = 0.6 lag 1 = cos-1 0.6 = 53.13 sin(1) = 0.8

S1 = Q1/ sin(1) = 35000/0.8 = 43.75 kVA

P1 = S1 cos (1) = 43750 0.6 = 26.25 kW

I1(Line) = S1/(3 VL) = 43750 / (3 380) = 66.47 A

Load #2

P2 = 30 kW

P.F.2 = 0.8 lead 2 = cos-1 0.8 = 36.87 sin(2) = 0.6

S2 = P2/ P.F.2 = 30000/0.8 = 37.5 kVA

Q2 = S1 sin (2) = 37500 0.6 = - 22.5 kVAR

I2(Line) = S2/(3 VL) = 37500 / (3 380) = 56.975 A

Load #3

S3 = 20 kVA

P3 = 15 kW

p.F.3 = P3/S3 = 15/20 = 0.75 lag 3 = cos-1 0.75 = 41.41 sin(3) = 0.6614

Q3 = S3 sin(3) = 20000/0.6614 = 13.229 kVAR

I3(Line) = S3/(3 VL) = 20000 / (3 380) = 30.3869 A

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 22
EF "!   J  
 
'()*+,-.K0  

Load #4

S4 = 35 kVA

Q1 = 20 kVAR

sin(4) =Q4/S4 = 20/35 =0.5714 4 =sin-1 0.5714=34.85 P.F.4=cos 0.5714 = 0.8207 lag

P4 = S4 cos (4) = 35000 0.8207 = 28.7245 kW

I4(Line) = S4/(3 VL) = 35000 / (3 380) = 53.177 A

Combined Load

P (Total) = P1 + P2 + P3 + P4 = 99.9745 kW

Q (Total) = Q1 - Q2 + Q3 + Q4 = 45.729 kVAR

Complex power = 99.9745 + J 45.729 = 109.9365 24.5797 kVA

S (Total) = 109.9365 kVA

P.F. (Total) = cos (24.5797) = 0.9094 Lag

I (Total) = S (Total) /(3 VL) = 109936.5 / (3 380) = 167.0312 A

Table 1 Load #1 Load#2 Load #3 Load #4 Combined Load


Apparent Power 43.75 kVA 37.5 kVA 20 kVA 35 kVA 109.936 kVA
Active Power 26.25 kW 30 kW 15 kW 28.7245 kW 99.9745 kW
Reactive Power 35 kVAR 22.5 kVAR 13.229 kVAR 20 kVAR 45.729 kVAR
Line Current 66.47 A 56.975 A 30.3869 A 53.177 A 167.0312 A
Power Factor 0.6 lag 0.8 lead 0.75 (lag) 0.82 Lag 0.9094 Lag
The new P.F = 0.98 (new) =cos-1 0.98 = 11.4783

kVAR of each capacitor = P{tan(old) tan (new)}/3 = 8.4762 kVAR

7 8476.2
<    186.845 @A
2= >  # 2= ? 50 ? 380#

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 23
EF "!   J  
 
'()*+,-.K0  

Final Exam, First semester 1429/1430

Load #1: 250 kVA, 0.8 P.F. lag

Load #2: 300 kVA, 0.95 P.F. lead

Load #3: 450 kVA, unity P.F.

The above three parallel-connected, three-phase loads are fed by a balanced three-
phase source. If the line voltage is 13.8 kV, calculate the line current and the power
factor of the source.

ST = 200 + j150 + 285 j93.65 + 450

4. Unbalanced Three-phase systems

An unbalanced system is due to unbalanced voltage sources or an unbalanced load. To


simplify analysis, we will assume balanced source voltages, but an unbalanced load.

4.1 Y-Y four-wire and three-wire Unbalanced 3-phase systems

Figure 20 shows an example of an unbalanced 3-phase system.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 24
EF "!   J  
 
'()*+,-.K0  

Fig. 20, Unbalanced, 4-wire, Y-connected load

Since the load is unbalanced, ZA, ZB, and ZC are not equal. The line currents are
determined directly by Ohms law as

This set of unbalanced line currents produces current in the neutral line, which is not
zero as in a balanced system, and can be calculated as:

In a three-wire system where the neutral line is absent, we can still find the line
currents Ia, Ib, and Ic using mesh analysis.

First mid-term exam, second semester 1432/1433

A Y-Y, 4-wire, Three-Phase circuit with load shown in Fig. 21. The line voltages all
have the same magnitude and are in a positive phase sequence. If Vab =250 V;

a) Calculate the line currents and the neutral current


b) Calculate the complex power for the 3-phase load
c) Calculate the dissipated power at the load side
d) Find the power factor of each load

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 25
EF "!   J  
 
'()*+,-.K0  

Fig. 22

the Y-Y circuit can be as follows:

a) Since positive sequence then:

Vab = 2500 V Van = 144.3376-30 V

Vbc = 250-120 V Vbn = 144.3376-150 V

Vbc = 250+120 V Vcn = 144.3376+90 V

Since 4-wire circuit, then

 144.3376 30
    3.60844 90  #
 4060


 144.3376 150

   2.4056 105  #

60 45
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 26
EF "!   J  
 
'()*+,-.K0  

 144.3376 90
    7.216990  #
 200

the neutral current In is

In = - (Ia + Ib + Ic) = - 1.4277115.8544 A #

The complex power for load at phase #a =

(3.60844)2 4060 = 520.833660=260.4168+j451.0551 VA

The complex power for load at phase #b =

(2.4056)2 60-45 = 347.2147-45 = 245.5179 - j245.5179 VA

The complex power for load at phase #c =

(7.2169)2 200 = 1041.67290 = 1041.6729VA

b) The total complex power = 1561.19667.5652 = 1547.6076 + j 205.5373 VA ##

c) The dissipated power at load side is the real part of the complex load power =

1547.6076 W ###

d) the power factor of load at phase #a = cos(-90-(-30)) = cos (-60) = 0.5 lag

the power factor of load at phase #b = cos(-105-(-150)) = cos (45) = 0.707 lead

the power factor of load at phase #c = cos(90-90) = cos (0) = 1.0

First mid-term exam, first semester 1433/1434

For the three-phase circuit with negative sequence shown in Fig. 23, if Vb = 12030
determine: a) The line and phase currents,

b) The active power dissipated in phase A load,


c) The complex power delivered by the source.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 27
EF "!   J  
 
'()*+,-.K0  

Fig. 23

the Y-Y circuit can be as follows:

a) Since negative sequence and Vb=12030 then:

Va = 120-90 V, Vc = 120150 V

Taking KVL for both current I1 and I2 as follows:

for loop I1

120 90 12030  " C4060  60 45D # C60 45D

207.864 120  " C62.91 7.11D # C60 45D C1D

for loop I2

12030 120150  " C60 45D  # C60 45  200D

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 28
EF "!   J  
 
'()*+,-.K0  

207.8460  " C60 45D  # C75.48 34.2D C2D

Equations (1) and (2) can be arranged in matrix form as follows:

207.846 120 62.91 7.11 60 45 


E FE F G "H
207.8460 60 45 75.48 34.2 #

 62.91 7.11 60 45 I" 207.846 120


G "H  E F E F
# 60 45 75.48 34.2 207.8460

 1 75.48 34.2 60 45 207.846 120


G "H  E F E F
# 35977.434 60 45 62.91 7.11 207.8460

 4.594 116.1
G "H  E F
# 1.3718 86.49

Since the load is Y connected, so that the phase and line currents are equal and are
calculated as follows:

  "  4.594 116.1  #


 # "  3.46852.63  #

  #  1.371893.51  #

b) The Active power for load at phase #a =

(4.5931)2 20 = 421.931 W

The complex power for load at phase #a =

(4.5931)2 4060 = 843.86360 VA

The complex power for load at phase #b =

(3.468)2 60-45 = 721.6214-45 VA

The complex power for load at phase #c =


Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 29
EF "!   J  
 
'()*+,-.K0  

(1.3718)2 200 = 37.6370 VA

c) The total complex power = 994.59212.811 VA ##

First mid-term exam, second semester 1433/1434

In the unbalanced Y-Y, three-phase circuit shown in Fig. 24, calculate the phase and
line currents if the neutral wire is a) connected b) not connected. Take Vp = 240 V
rms.

Fig. 24

If the neutral wire is connected,

given that Vph = 240 v (rms), then phase and line currents are:

2400
   2.4 90 
'100
240 120

  4.0 120 
60
240120
   3.0120 
80
If the neutral wire is NOT connected,
given that Vph = 240 v (rms), then phase and line currents are:
loop I1
2400 240 120  " J60  '100K # J60K

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 30
EF "!   J  
 
'()*+,-.K0  

415.692230  " J60  '100K # J60K


loop I2
240 120 240120  # J140K " J60K
415.6922 90  # J140K " J60K

in matrix form

415.692230 60  '100 60 "


E FE F G H
415.6922 90 60 140 #

" 60  '100 60 I" 415.692230


G H  E F E F
# 60 140 415.6922 90

 C60  '100D ? 140 60 ? 60  1480071.0754

 1 140 60 415.692230
G "H  G H E F
# 60 60  '100 415.6922 90

 3.147 66.36
G "H  E F
# 4.351 82.243

Therefore, the phase and line currents are:


  "  3.147 66.36 
  #  4.35197.757

 # "  4.351 82.243 3.147 66.36  1.58 115.3 

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 31
EF "!   J  
 
'()*+,-.K0  

Report:

First Mid-term Exam, First semester (1432/1433)

For the three-phase, 3-wire, Y-Y


circuit shown, if the source has
positive sequence with phase voltage
va = 1100. Calculate:
a) The line and phase currents,
b) The source complex power,
c) The total dissipated power
through the transmission line,
d) The total complex power
supplied to the load.

4.2 -
Unbalanced 3-phase systems
Final exam, second semester 1433/1434
For the three-phase, positive-sequence circuit shown in Fig. 25, if the supply voltage
Vab is 100V, find the real power absorbed by the load.

Fig. 25
Since +ve sequence, Vab = 100 v, Vbc = 100120 v and Vca = 100 120 v.

For loop aABba:

100 = I1 (18 J6) I2 (5) I3 (8 J6) .(1)

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 32
EF "!   J  
 
'()*+,-.K0  

For loop cbBCc

100120 = I1 (5) + I2 (20) I3 (10) (2)

For loop ABCA

0 = I1 (8 J6) I2 (10) + I3 (22 J3) (3)

Arrange the above 3 equations in matrix form as:

100 18 '6 5 C8 j6D I"


M100 120N  M 5 20 10 N MI# N
0 C8 j6D 10 22 j3 I&

The solution is:

I" 18 '6 5 C8 j6D I" 100


MI# N  M 5 20 10 N M100 120N
I& C8 j6D 10 22 j3 0
Then the three currents can be obtained as:

I1 = 6.682-38.326 A

I2 = 8.725-92.935 A

I3 = 6.857-77.486 A

Another solution:

Multiplying Eqn. (3) by 2.0

0 = I1 (16 J12) I2 (20) + I3 (44 J6) (4)

Then add Eqn. (4) to Eqn. (2)

100120 = I1 (21+J12) + I3 (34 J6) (5)

Multiplying Eqn. (1) by 4.0

400 = I1 (72 J24) I2 (20) I3 (32 J24) ...(6)

Then add Eqn. (6) to Eqn. (2)

360.56 13.9 = I1 (67 J24) + I3 (42 + J24) (7)

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 33
EF "!   J  
 
'()*+,-.K0  

From Eqn. (5), we can get an expression for I3


100 120 C 21  12D"
&   2.9 110 C0.7160.263D"
34 6

Substituting by the value of I3 in eqn. (7)

360.56 13.9 = I1 (67 J24) + {2.9110 0.7 160.263 I1 }(42 + J24)

360.56 13.9 = I1 (67 J24) +140.28340.255 +33.86130.52 I1

360.56 13.9 140.28340.255 = 45.034 2.22 I1

So that I1 = 6.678 38.337 A ###

Substituting by the value of I1 to get I3

I3 = 6.855 77.55 A ###

From Eqn. (1) we can get the value of I2 as

100=6.678 38.337 (18J6) 5I2 6.855 77.55(8J6)

100= 126.706 56.772 5I2 68.55 114.42

I2 = 8.72692.93 A ###

The current through the 8 resistance of the branch AB = I1 I3


= 6.678 38.337 6.855 77.55 = 4.54434.159 A
Then the power dissipated in 8 resistance (P1) = (4.544)28 = 165.196 W
The current through the 4 resistance of the branch CA = I3 =6.855 77.55 A
Then the power dissipated in 4 resistance (P2) = (6.855)24 = 187.964 W
The current through the 10 resistance of the branch BC = I2 I3
= 8.72692.93 6.855 77.55 = 2.79133.593 A
Then the power dissipated in 10 resistance (P3) = (2.79)210 = 77.841 W
The real power absorbed by the load = P1 + P2 + P3 = 165.196 + 187.964 + 77.841
= 431 W

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 34
EF "!   J  
 
'()*+,-.K0  

Final Exam, Second semester (1432/1433)


Consider the three-phase, - system shown in Fig. 26, where Z1 = 8 + j6 ,
Z2 = 4.2 j2.2 , and Z3 = 10 + j0.
a) Find the phase currents IAB, IBC, ICA.
b) Calculate line currents IaA, IbB, and IcC.

Fig. 26

5. Matlab Applications

In this section we will build a simulink model for balanced - system and a balanced
Y-Y system. We will present the phase and line quantities. Take R=5, L=1 mH
Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 35
EF "!   J  
 
'()*+,-.K0  

Three-phase, -
, Balanced Circuit (Positive Sequence) (Va=50
0)

Oscilloscope 3

Oscilloscope 1

Oscilloscope 2

Oscilloscope 1

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 36
EF "!   J  
 
'()*+,-.K0  

Oscilloscope 2

Oscilloscope 3

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 37
EF "!   J  
 
'()*+,-.K0  

0)
Three-phase, Y-Y, Balanced Circuit (Positive Sequence) (Va=50

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 38
EF "!   J  
 
'()*+,-.K0  

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 39
EF "!   J  
 
'()*+,-.K0  

Configuring the simulation parameters

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 40
EF "!   J  
 
'()*+,-.K0  

Electric Circuit Analysis (EE 2020) < <DNLNL<E<e]<]]<


Sheet (2) Three-Phase Circuits
q]<mm<]]<DNE<k
Problem #1
A) If Vab = 400 V in a balanced Y-connected three-phase generator, find the phase
voltages, assuming the phase sequence is:
(a) abc (b) acb
B) What is the phase sequence of a balanced three-phase circuit for which Van =
160 30 V and Vcn = 160 90 V? Find Vbn.
C) Determine the phase sequence of a balanced three-phase circuit in which Vbn =
208 130 V and Vcn = 208 10 V. Obtain Van.
D) Assuming abc sequence, if Vca = 208 20 V in a balanced three-phase circuit,
find Vab, Vbc, Van, and Vbn.
E) Given that the line voltages of a three-phase Y-connected circuit are:
Vab = 420 0, Vbc = 420 120 Vac = 420 120 V
Find the phase voltages Van, Vbn, and Vcn.

Problem #2
A) For the Y-Y circuit shown in Fig. 1, find the line currents, the line voltages, and
the load voltages.

Fig. 1 Problem 2-A


B) Obtain the line currents in the three-phase circuit shown in Fig. 2.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 41
EF "!   J  
 
'()*+,-.K0  

Fig. 2 Y-Y Problem 2-B

C) A balanced Y-Y, four-wire system has phase voltages Van = 120 0, Vbn = 120
120Vcn = 120 120 V. The load impedance per phase is 19 + j13 , and
the line impedance per phase is 1 + j2 . Solve for the line currents and neutral
current.

D) For the circuit shown in Fig. 3, determine the current in the neutral line.

Fig. 3 Y-Y Problem 2-D

Problem #3
A) For the positive-sequence, three-phase circuit shown in Fig. 4, IbB = 30 60 A
and VBC = 220 10 V. Find Van, VAB, IAC, and Z.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 42
EF "!   J  
 
'()*+,-.K0  

Fig. 4. Problem 3-A


B) Find the line and phase currents at the load side in the Y- circuit shown in Fig.
5. Take Z = 60 45.

Fig. 5. Problem 3-B

C) In a Y-, 3-ph circuit, the source is a balanced, positive sequence with Van =
120 0 V. It feeds a balanced load with Z = 9 + j 12 per phase through a
balanced line with Zl = 1 + j 0.5 per phase. Calculate the phase voltages and
currents at the load side.
Problem #4
A) Find the currents Ia , Ib, and Ic in the 3-ph network shown in Fig. 6. Take Z =
12 j15 , ZY = 4 + j6 , and Zl = 2 .

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 43
EF "!   J  
 
'()*+,-.K0  

Fig. 6. Problem 4-A


B) For the - circuit shown in Fig. 7. Find the line and phase currents. Assume
that the load impedance Zl = 12 + j9 per phase.

Fig. 7. Problem 4-B


C) A balanced delta-connected source has phase voltage Vab = 416 30 V and a
positive phase sequence. If this is connected to a balanced delta-connected
load, find the line and phase currents. Take the load impedance per phase as
60 30 and line impedance per phase as 1 + j1 .
Problem #5
A) In the circuit of Fig. 8, if Vab = 440 10, Vbc = 440 250, Vca = 440 130
V, find the line currents and the load voltages.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 44
EF "!   J  
 
'()*+,-.K0  

Fig. 8. Problem 5-A


B) A delta-connected generator supplies a balanced Y-connected load with an
impedance of 30 60 . If the line voltages of the generator have a
magnitude of 400 V and are in the positive phase sequence, find the line currents
and the phase voltages at the load.

Problem #6
A) A balanced Y-connected load absorbs a 3-ph power of 5 kW at a leading power
factor of 0.6 when connected to a line voltage of 240 V. Find the impedance of
each phase and the total complex power of the load.

B) A balanced Y-load is connected to a 60-Hz three-phase source with Vab = 240


0V. The load has pf = 0.5 lagging and each phase draws 5 kW. (a)
Determine the load impedance ZY . (b) Find Ia, Ib, and Ic.

C) A three-phase source delivers 4800 VA to a Y-connected load with a phase


voltage of 208 V and a power factor of 0.9 lagging. Calculate the source line
current and the source line voltage.

D) Given the circuit in Fig. 9 below, find the total complex power absorbed by the
load.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 45
EF "!   J  
 
'()*+,-.K0  

Fig. 9. Problem 6-D

E) The following three parallel-connected three-phase loads are fed by a balanced


three-phase source.
Load #1: 250 kVA, 0.8 pf lagging
Load #2: 300 kVA, 0.95 pf leading
Load #3: 450 kVA, unity pf

If the line voltage is 13.8 kV, calculate the line current and the power factor of the
source. Assume that the line impedance is zero.

F) Assume that the two balanced loads shown in Fig. 10 are supplied by an 840-V
rms 60-Hz line.
Load #1: Y-connected with 30+j40 per phase,
Load #2: balanced three-phase motor drawing 48 kW at a power factor of 0.8
lagging.
Assuming abc sequence, calculate:
a) The complex power absorbed by the combined load,
b) The kVAR rating of each of the three capacitors -connected in parallel with
the load to raise the power factor to unity,
c) The current drawn from the supply at unity power factor condition.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 46
EF "!   J  
 
'()*+,-.K0  

Fig. 10 Problem 6-F


Problem #7
A) Find the real power absorbed by unbalanced 3-phase load given in Fig. 11.

Fig. 11 Problem 7-A


B) A balanced, positive-sequence Y-connected source has Van = 240 0V rms
and supplies an unbalanced delta-connected load via a transmission line with
impedance 2 + j3 per phase. (a) Calculate the line currents if ZAB = 40 + j15
, ZBC = 60 , ZCA = 18 j12. (b) Find the complex power supplied by
the source.

C) Consider the - system shown in Fig. 12. Take Z1 = 8 + j6 , Z2 = 4.2


j2.2 , Z3 = 10 + j0.
(a) Find the phase current IAB, IBC, ICA.
(b) Calculate line currents IaA, IbB, and IcC.

Fig. 12, Problem 7-C


Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 47
EF "!   J  
 
'()*+,-.K0  

D) In the Y-Y system shown in Fig. 13, loads connected to the source are
unbalanced.
(a) Calculate Ia, Ib, and Ic.
(b) Find the total power delivered to the load. Take Vp = 240 V rms.

Fig. 13, Problem 7-D

E) A balanced three-phase Y-source with VP = 210 V rms drives a Y-connected


three-phase load with phase impedance ZA = 80, ZB = 60 + j90, and ZC =
j80. Calculate the line currents and total complex power delivered to the load.
Assume that the neutrals are connected.

Chapter Three: Three-Phase Circuits By Dr. Ahmed Mustafa Hussein EE2020 Page 48

Vous aimerez peut-être aussi