CONTENT
1.0 OBJECTIVE
The objective of the potable water distribution system is as follows:
a. To store and supply potable water to the following buildings of the plant:
GT building -11/12/21/22
ST building-10/20
Electrical building
Air cooled condenser electrical building -10/20
Chemical dosing building-10/20
GIS control building
CCR building
Water treatment plant building
H2 building
Canteen building
Administrative building
Main gate
Workshop building
Warehouse building
One (1) no. of level transmitter (00GKB20CL101) is provided for the tank to control
municipal water supply pumps and to interface with the pneumatic on/off valve
(00GKB45AA061) located in the municipal water supply line. One local level gauge
(00GKB20CL501) is provided for the local level measurement.
Manual isolation valves are provided at the suction side (00GKB12/13AA001) and
discharge side (00GKB14/15AA002) of the pumps to isolate each pump from the
running plant for maintenance or repair. At the discharge side, a non return valve
(00GKB14/15AA001) is provided for each pump to avoid reverse flow of water.
The potable water distribution system will supply potable water from potable water
storage tank to the above listed consumers of the plant through 1 no. of hydro
pneumatic tank.
One (1) no. of level transmitter (00GKB10CL101) is provided on the potable water
tank for permissive, interlock and protection of the potable water supply pumps,
municipal water supply pumps and potable water feed pumps. One (1) No. of level
transmitter (00GKB10CL102) is also provided on the potable water tank for
monitoring the level.
Manual isolation valves are provided at the suction side (00GKB02/03AA001) and
discharge side (00GKB04/05AA002) of the pumps to isolate each pump from the
running plant for maintenance or repair. At the discharge side, a non return valve
(00GKB04/05AA001) is provided for each pump to avoid reverse flow of water.
measurement.
One connection from service air system is provided to pre-charge the potable water
hydro pneumatic tank initially.
Inlet water line is provided to the tank with a Pneumatic on/off valve
(00GKB09AA061) and a NRV (00GKB09AA001). One (1) no. of pressure control
valve (00GKB20AA071) and one (1) no. of pressure transmitter (00GKB20CP101)
are provided at the downstream of the hydro pneumatic tank to maintain the
constant pressure at the consumer ends.
One (1) no. of pressure transmitter (00GKB30CP101) is provided on the tank for the
pressure monitoring of the tank and to operate the pneumatic on/off valve
(00GKB09AA061) based on the pressure in the tank and also for starting the potable
water supply pumps. One pressure safety valve (00GKB30AA101) is provided on
the tank to avoid over pressurization. One vent line with valve (00GKB30AA501) and
drain line with valve (00GKB30AA401) is provided on the tank.
Prior to starting of the pump, the system must be filled through gravity by opening
municipal water supply pump’s suction valves (00GKB12/13AA001) and discharge
isolation valves (00GKB14/15AA002) to allow priming of the municipal water supply
pump and partial filling of the municipal water distribution pipe line prior to start up.
During normal operation, the municipal water pump will supply the municipal water
from the municipal water buffer tank to potable storage tank based on the level
Projet N°. Client Rev Feuille Suit F.
KAIS 1 266,71 MW-site KIS EM 641 053 02 6 11
One municipal water supply pump will be in stand by condition and will start, in case
of the running pump electrical common fault or if the discharge header pressure falls
low(0.8 bar(g)) for certain time when the other pump is running. The discharge
header pressure is monitored by pressure transmitter (00GKB19CP101), which
provides signal to DCS.
Prior to starting of the pump, the system must be filled through gravity by opening
potable water supply pump’s suction valves (00GKB02/03AA001) and discharge
isolation valves (00GKB04/05AA002) to allow priming of the potable water supply
pump and partial filling of the potable water distribution pipe line prior to start up.
Potable water supply pumps will take suction from potable water storage tank and
pump will fill up the potable water hydro pneumatic tank.
One potable water supply pump will be in stand by condition and will start, in case of
the running pump electrical common fault or if the discharge header pressure falls
low(5.5 bar(g) for certain time when the other pump is running. The discharge
pressure is monitored by pressure transmitter (00GKB09CP101), which provides
signal to DCS.
Compressed air connection is provided to the tank at a pressure of 5.5 bar (g),
which will be the minimum pressure available throughout.
Based on consumption in potable water distribution network, the water volume in the
tank decreases along with the pressure in the tank. At a pressure of 5.5 bar (g),
pump will automatically start and the pneumatic on-off valve at the inlet of hydro
pneumatic tank would open. Hence, potable water starts entering the pneumatic
tank and once the tank pressure reaches 7.0 bar (g) the pump is switched off and
the pneumatic on-off valve at the inlet of hydro pneumatic tank would close. Potable
water supply pump operates always between the set pressures of 5.5 bar (g) and
7.0 bar (g.
In case of any sudden failure of both the pumps, the flow of remaining water in the
tank to the consumers is ensured by the compressed air connection at 5.5 bar (g).
(Values will be confirmed later). Pressure safety valve is provided on the tank to take
care of any pressure increase beyond 7.0 bar (g).
i. Municipal water buffer tank level not low (00GKB20CL101) (more than 200 mm)
ii. Potable water storage tank level not high (less than 3400 mm)
i. When the potable water storage tank level (00GKB10CL101) becomes low, the
municipal water supply pump would be started.
ii. Working municipal water supply pump (00GKB13/14AP001) was running and
has tripped on electrical common fault.
iii. Municipal water supply pump running and discharge header pressure
(00GKB19CP101) falls low (less than 0.8 bar (g)) for certain time.
This valve can be operated manually from the DCS or in the auto mode based on the
following conditions.
i. Potable water storage tank level not low (00GKB10CL101) (more than 900 mm)
ii. Potable water hydro pneumatic tank pressure low (00GKB30CP101) (less than
5.5 bar(g)
iii. Potable water hydro pneumatic tank on/off valve (00GKB09AA061) open
feedback
ii. Working potable water supply pump (00GKB11/12AP001) was running and has
tripped on electrical common fault.
iii. Potable water supply pump is running and discharge header pressure
(00GKB09CP101) falls low (less than 5.5bar (g)) for certain time.
i. Potable water storage tank level(00GKB10CL101) low low (less than 900 mm)
ii. When the potable water supply pump discharge header pressure is very
high(00GKB09CP101)(more than (7.1 bar(g)) for certain time.
6.2.10Override close
Nil
No Design parameters
Particular Nos.
. Capacity Pressure Material
A573 Gr 485 for Shell
Potable water Plate and A283 Gr C for
1. 1 57 m3 Atm
storage tank roof and bottom plate
ASTM A 743 Gr
Casing
CF8
Potable water 7.0 bar
2. 2x100% 2.5 m3/h Impelle ASTM A 743 Gr
supply pumps (g)
r CF8
Shaft ASTM A276-304
Potable water
10.0 bar SA 516 Gr.70 for Dished
3. hydro 1 10 m3
(g) end and shell material
pneumatic tank
Projet N°. Client Rev Feuille Suit F.
KAIS 1 266,71 MW-site KIS EM 641 053 02 11 11
No Design parameters
Particular Nos.
. Capacity Pressure Material
Municipal
Shell SA 240
3 water buffer 1 10 m3 Atm
Type 304
tank
ASTM A 743 Gr
Casing
Municipal CF8
4 water supply 2x100% 2.5 m3/h 1.0 bar(g) Impelle ASTM A 743 Gr
pumps r CF8
Shaft ASTM A276-304