Vous êtes sur la page 1sur 73

Boîtier

d’Automatisme
Réf. 261 93 – Réf. 261 94

Octobre 08
Y1958C
Table des matieres

1. Caractéristiques générales . . . . . . . . . . 4
1.1 Versions . . ... . . . . . . . . . . . . . . . . . . . . . 4
1.2 Description ... . . . . . . . . . . . . . . . . . . . . . 4
1.3 Applications .. . . . . . . . . . . . . . . . . . . . . . 4
1.4 Installation . ... . . . . . . . . . . . . . . . . . . . . . 4
1.5 Alimentation ... . . . . . . . . . . . . . . . . . . . . . 4

2. Description de la façade . . . . . . . . . . . . 5
2.1 Touches de sélection . . . . . . . . . . . . . . . . . . 5
2.2 Sélection mesures . . . . . . . . . . . . . . . . . . . 6
2.3 Indicateurs à diodes . . . . . . . . . . . . . . . . . . 6

3. Modes de fonctionnement . . . . . . . . . . . 8
3.1 Mode reset (voyant touche RESET rouge) . . . . 8
3.2 Mode manuelle (voyant touche MAN rouge) . 9
3.3 Mode automatique (voyant touche AUT rouge) . 9
3.4 Mode test off-load (hors-charge) . . . . . . . . . . . 9
3.5 Mode test on-load (en charge) . . . . . . . . . . . 9

4. Applications . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Application Secteur-Groupe . . . . . . . . . . . . . 10
4.2 Application Secteur-Secteur . . . . . . . . . . . . . . 10

5. Commande appareils . . . . . . . . . . . . . . 11
5.1 Avec feedback . . . . . . . . . . . . . . . . . . . . . 11
5.2 Sans feedback . . . . . . . . . . . . . . . . . . . . . 12

6. Contrôles de tension . . . . . . . . . . . . . . . 13

7. Programmation . . . . . . . . . . . . . . . . . . . 15
7.1 Programmation des paramètres . . . . . . . . . . . 15
7.2 Tableau des menus . . . . . . . . . . . . . . . . . . . 16
7.3 Menu P0 - Données nominale . . . . . . . . . . . . 16
7.4 Menu P1 - Données générales . . . . . . . . . . . 17
7.5 Menu P2 - Contrôle tension ligne principale . . 18
7.6 Menu P3 - Contrôle tension ligne secondaire . . 19
7.7 Menu P4 - Entrées programmables . . . . . . . . . 20
7.8 Menu P5 - Sorties programmables . . . . . . . . 20
7.9 Menu P6 - Communication série . . . . . . . . . . 21

8. Messages de diagnostic . . . . . . . . . . . . . 22

9. Alarmes . . . . . . . . . . . . . . . . . . . . . . . . . 23

10. Branchements . . . . . . . . . . . . . . . . . . . . 25

11. Caractéristiques techniques . . . . . . . . . . 26

3
1. Caractéristiques générales

1.1 Versions
• 261 93 - Version standard • 261 94 - Version évoluée + interface RS-485

1.2 Description
• Commutateur automatique de secteur à micro- • Clavier à membrane à 8 touches
processeur • Sortie série RS-232 (contrôle à distance et super-
• Deux entrées de mesure de tensions triphasées vision)
• Alimentation CC 12-24-48 Vcc • Sortie RS-485 isolée pour protocole MODBUS
• Alimentation CA 220-240 Vca (261 94)
• 2 moniteurs à diodes, 3 chiffres de 7 segments • 2 entrées TOR (tout ou rien) programmables
• 20 diodes de visualisation états et mesures • 3 sorties à relais (1 NO + 2 NO/NF) program-
mables

1.3 Applications
• Commutation entre ligne-ligne et ligne-groupe • Relevé tensions phase-phase (ou sur les tensions
électrogène phase-neutre dans le cas des lignes monophasés)
• Commande des appareils motorisés • Contrôles de tension minimum, de tension maxi-
• Marche/arrêt groupe électrogène mum, d’absence de phase, d’asymétrie, de fré-
quence minimum et de fréquence maximum avec
• Relevé tensions sur lignes triphasés, biphasés ou
validation et retard indépendants
monophasés
• Seuil de tension avec hystérésis programmable

1.4 Installation
• Installer l’appareil en suivant les schémas de bran- • Programmer les paramètres en fonction du sché-
chement (voir dernières pages du manuel) ma de branchement adopté, en faisant particu-
• Utiliser le schéma de branchement correspondant lièrement attention à la programmation des
à l’application entrées/sorties

1.5 Alimentation
• 261 93 et 261 94 ont un double circuit d’ali- • Quand le boîtier est alimenté en CA et CC en
mentation ; ils peuvent être alimentés en CA et même temps, l’énergie est prélevé en CA
CC en même temps, ou seulement en CA ou en
CC indifféremment

4
2. Description de la façade

2.1 Touches de sélection


• La façade du boîtier dispose de deux afficheurs à • Au centre la façade est représenté un synoptique
diodes pour indiquer les tensions des deux qui indique l’état des appareils pour la connexion
sources d’alimentation avec les deux touches cor- de la charge.
respondantes: ligne principale (A) et ligne secon- • Deux boutons (C) et (D) permettent d’ouvrir/fermer
daire (B) pour la sélection des mesures. les appareils (boutons actifs uniquement après
• Quatre touches SET (E) - AUT (F) - MAN (G) - RESET avoir appuyé sur la touche MAN).
(H) permettent de sélectionner la mode de fonction-
nement indiquée par le voyant correspondant.

A B

C D

5
2.2 Sélections des mesures
• En appuyant à plusieurs reprises sur la touche située • Au bout de 1 minute sans que la touche ait été
sous chaque moniteur (A) et (B), il est possible de enfoncée, est rétablie la mesure par défaut qui
visualiser successivement les différentes mesures de la peut être la première tension phase-phase ou la
ligne correspondante. première tension phase-neutre en fonction de la
• Pour chaque ligne, sont disponibles les tensions configuration du contrôle de tension.
phase-phase et les tensions phase-neutre (en pré- • En cas d’alarmes ou de messages, affichage du le
sence de ligne monophasée). message d’alarme.
• Les combinaisons des diodes rouges indiquent les En appuyant sur la touche de sélection, il est
mesures sélectionnées. La liste des mesures varie possible de masquer temporairement l’alarme et
selon que l’appareil est configuré pour le contrôle d’accéder aux mesures.
triphasé, biphasé ou monophasé.

Exemple de liste des mesures


sur un boîtier configuré pour le contrôle
triphasé.

2.3 Indicateurs à diodes


• Sur la façade sont présents un certain nombre de témoins qui indiquent l’état de l’appareil et/ou des
appareils qu’il commandent.

Diodes L1/L2/L3 Diodes L1/L2/L3 Diode ALARME


Présence tension ligne Présence tension ligne (rouge)
principale (rouges) secondaire (rouges)

Diode ALIMENTATION
(verte)

Diode touche SET


(rouge)

Diode touche AUT


Diode (rouge)
COMMANDES
ligne principale / Diode touche MAN
ligne secondaire (rouge)
(bicolore)
Diode touche RESET
(rouge)

Diode d’état Diode d’état


int. ligne int. ligne
principale secondaire
6
• Dans le tableau ci-dessus est indiquée la signification des différents témoins.
Certains d’entre eux sont bicolores à savoir que leur signification est différente selon la couleur.

Voyant Allumé Éteint Clignotant


Un ou plusieurs alarmes actives
ALARME Aucune alarme active
(ROUGE)
ALIMENTATION Boîtier alimentée (VERT) Absence alimentation
Commande fermeture
COMMANDE
(ROUGE)
OUVERTURE/ Aucune commande
Commande ouverture
FERMETURE
(VERT)

4 Appareil fermé (ROUGE) Contacts auxiliaires


FERMÉ/OUVERT
Appareil ouvert (VERT) non branchés

Appareil enclenché ou
44 Appareil non enclenché
NON ENCLENCHÉ contrôle enclenchement
sur la base
désactivé
Appareil non déclenché
44
DÉCLENCHÉ Appareil déclenché ou contact SD
non connecté
1HZ = Temps présence absence
PRÉSENCE
Présence tension Absence tension en cours
L1/L2/L3
5HZ = Sélection mesures moniteur

✱ Si les contacts auxiliaires ont été branchés, le voyant représente l’état de l’appareil, sinon il reste éteint.
✱✱ Si les contacts correspondants ont été branchés à cet effet, le voyant représente l’état de l’appareil, sinon les
voyants restent éteints.

7
3. Modes de fonctionnement

• A l’aide des quatre touches SET / AUT / MAN • Si le voyant qui indique le mode de fonctionne-
/ RESET il est possible de sélectionner le mode ment sélectionné clignote, cela indique que l’ap-
de fonctionnement voulu et indiqué par l’allumage pareil est en communication à travers l’interface
du voyant rouge correspondant. série et qu’il est susceptible d’effectuer des com-
mandes transmises à distance (par exemple une
commande de changement de mode).

A B

C D

3.1 Mode reset (voyant touche RESET rouge)


• Le boîtier n’effectue aucune opération et se limite • La sortie de commande générateur se positionne
à afficher l’état des tensions et des appareils. pour l’arrêt du groupe.
• Les sorties de commande de fermeture et ouvertu- • Les alarmes d’état des appareils sont désactivées.
re des appareils restent toutes ouvertes permettant • Lorsqu’une alarme se déclenche, elle doit être
la commande manuelle des motorisations. Si l’en- réarmée en appuyant sur la touche RESET. Dans le
trée «arrêt d’urgence» est activée, le boîtier com- cas où l’on se trouverait déjà dans ce mode,
mande l’ouverture des appareils. appuyer à nouveau sur la touche RESET.

8
3.2 Mode Manuel (voyant touche MAN rouge)
• Le mode manuel permet à l’opérateur d’ouvrir/fer- boîtier ouvre initialement l’autre appareil, laisse
mer électriquement les appareils à l’aide des s’écouler le temps d’inter-verrouillage puis ferme
touches présentes sur la façade de l’appareil. l’appareil voulu.
• Dans ce mode les tensions sont constamment • En Manuel toutes les alarmes relatives à l’état des
contrôlées mais le boîtier se limite à en visualiser appareils (non enclenchés et déclenchés) sont
l’état. désactivées. L’alarme est indiquée sur le voyant
• En appuyant pendant au moins 300 ms sur une correspondant mais n’est pas mémorisée.
des touches de commande, le boîtier commute • Il est possible de commander manuellement la
l’état de l’appareil correspondant (d’ouvert à mise en marche et l’arrêt du groupe électrogène
fermé et vice-versa). en maintenant enfoncée la touche (G) MAN pen-
• Dans le cas où serait commandé la fermeture dant 5 secondes d’affilée. Tant que l’on reste en
d’un appareil alors que l’autre est déjà fermé, le mode manuel, l’état du groupe reste celui voulu.

3.3 Mode Automatique (voyant touche AUT rouge)


• En mode Automatique l’appareil effectue de de l’éventuel groupe électrogène que les temps de
manière autonome les opérations d’ouverture et commande d’inter-verrouillage entre les appareils.
de fermeture des appareils ainsi que la mise en • Quand la ligne principale rentre à nouveau dans
marche et l’arrêt de l’éventuel groupe électrogène. les limites, le boîtier commute à nouveau la charge
• Quand la ligne principale (MAIN) se trouve hors sur la ligne principale et assure l’éventuel cycle de
des limites, à l’issue des temps de retard program- refroidissement du groupe électrogène.
més, l’appareil déconnecte la charge de la ligne • Les cycles de fonctionnement automatique varient
prioritaire et la connecte à la ligne secondaire en fonction du type d’application (secteur-secteur
(SEC), en contrôlant aussi bien la mise en marche ou secteur-groupe).

3.4 Mode test off-load


• En partant du mode Automatique et en appuyant sur la couverture de la charge. En conditions nor-
touche (F) pendant 5 secondes, alors s’enclenche un males, la charge reste connectée à la ligne
test du groupe électrogène d’une durée de 5 minutes. principale, à savoir que le groupe fonctionne
• Le groupe électrogène est mis en marche manuel- sans charge (off-load groupe électrogène).
lement pour qu’en soit contrôlé le fonctionnement, • L’exécution du test off-load est signalée par l’indi-
mais les contrôles de tension restent actifs puisque cation TES fixe sur le boîtier.
le boîtier est en mode automatique. • Pour anticiper la fin du test, appuyer à nouveau sur
• De la sorte il est possible de s’assurer du bon la touche (F) pendant 5 secondes ou bien passer
Attention:
L’ e x é c u t i o n fonctionnement du groupe en maintenant la en mode Reset.
de ce test pré-
voit le trans-
fert de la
charge, à 3.5 Mode test on-load
savoir une
coupure de • En partant du mode automatique et en appuyant paramètres programmés, de façon à en contrô-
l’alimentation simultanément sur les touches (F) et (D) pendant ler la validité.
sur celle-ci 5 secondes, alors est activé un test fonctionnel • L’exécution du test on-load est signalée par l’indi-
pendant la (test on-load) qui simule une coupure d’une durée cation TES clignotante sur le boîtier.
commutation d’une minute.
due aux
• Pour anticiper la fin du test, répéter la procédure à
• Le boîtier si comporte ensuite exactement comme l’aide des touches (F) et (D) pendant 5 secondes
temps d’inter-
si le secteur était sorti des limites, en utilisant ou bien passer en mode Reset.
verrouillage.
pour la commutation tous les temps et tous les

9
4. Applications

4.1 Application Secteur-Groupe


• Sur l’application secteur-groupe (U-G, configura- • Au retour de la ligne principale la charge est
tion par défaut) la charge est en principe connec- retransférée et le groupe est maintenu en marche
tée à la ligne principale. En présence d’une ano- sans charge pendant une durée préétablie de
malie sur le secteur ou en cas de signal de trans- façon à en permettre le refroidissement.
fert imposé de l’extérieur, il est transmis un signal • Le boîtier envoie au groupe une commande de
de mise en marche au groupe présent sur la ligne start/stop par l’intermédiaire d’une sortie à relais
secondaire. et peut recevoir des signaux numériques du grou-
• Quand la tension du groupe rentre dans les limites pe qui en indiquent l’état à travers des entrées
programmées, le boîtier commande la commuta- programmables.
tion sur la ligne secondaire.

4.2 Application Secteur-Secteur


• Sur l’application secteur-secteur (U-U, utility-utili- daire intervient en cas d’anomalie sur le secteur
ty), la charge est en principe connectée au sec- primaire ou de signal de transfert imposé de
teur prioritaire et le transfert sur le secteur secon- l’extérieur.

10
5. Commande appareils

• La commande de la motorisation des appareils est • Suite à une anomalie sur l’appareil provoquant
assurée par deux relais distincts, l’un pour la fer- une alarme, les sorties de commande sont toutes
meture et l’autre pour l’ouverture. deux ouvertes jusqu’à l’élimination de l’alarme.
• En mode Reset, les deux relais de commande restent • Ils existent deux modes distincts de contrôle des
ouverts, sauf en condition d’urgence dans laquelle appareils, sélectionnables par l’intermédiaire du
l’ouverture de l’appareil peut être commandée. paramètre P1.03

5.1 Avec feedback


• Les voyants bicolores frontaux indiquent l’état des sortie reste activée pendant une certaine durée
appareils en commutation grâce aux contacts (+1 seconde en phase de fermeture et +15
auxiliaires CA. secondes en phase d’ouverture pour permettre le
• Les alarmes Timeout sont actives. Elles se déclen- chargement complet des ressorts) puis elle est
Les contacts
auxiliares CA chent si l’appareil ne se place en position requise désactivée
de l’appareil au bout d’une durée programmable P1.04 ou • L’état normal des sorties de commande est l’état
sont câblés sur immédiatement s’il change de position sans ouvert pour les deux sorties.
les entrées qu’une commande n’ait été envoyée. • Le temps d’inter-verrouillage est décompté à partir
respectives du
boîtier.
• Les sorties de commande sont temporisées. Une de l’ouverture effective du premier appareil, et il
En modalité fois que l’appareil a effectué l’opération voulue, la est de 0,5 seconde.
feedback est
nécessaire
d’utiliser pour
l’ouverture du
DPX
250-630-1600
des
déclencheures a
emition de
courant ou a LED VMAIN OK
minimum
de tension.
LED VSEC OK

3 1s
Exemple de commande des appareils 1 15 s
avec feedback en supposant une 15
commutation secteur-secteur. En bleu est 0.5 s 0.5 s
indiqué l’état des entrées de feedback. 6 1s
En vert l’état des sorties de commande. 4 15 s
En jaune le temps de commutation. 18

11
5.2 Sans feedback
• Les voyants d’état de l’appareil restent éteints. • Les temps d’inter-verrouillage entre l’ouverture
• Les alarmes de Timeout sont désactivées. d’un appareil et la fermeture de l’autre est
décompté à partir de la commutation des sor-
• Les sorties des commandes Ouverture/Fermetu-
ties et il est de 6 secondes.
Les contacts re restent constamment dans la position requise
auxiliaires CA pour l’appareil.
de l’appareil ne
sont pas câblés
sur les entrées
respectives,
donc le boîtier
n’est pas
informée de leur
état effectif.

LED VMAIN OK

LED VSEC. OK

3
Exemple de commande des appareils 1
sans feedback. INT. MAIN
En bleu est indiqué l’état effectif des 6 sec 6 sec
appareils. 6
En vert l’état des sorties de commande. 4
En jaune le temps de commutation. INT. SEC.

12
6. Contrôles de tension

• Toutes les conditions, servant à établir si une sour- • Il est possible de programmer un rapport de trans-
ce d’alimentation est appropriée ou non, sont défi- formation TU dans le cas où serait appliquée aux
nies par l’utilisateur par l’intermédiaire du menu entrées de tension du boîtier une tension inférieure
P0 (données nominales de l’installation) et des à la tension effective de l’installation. Dans ce cas
menus P2 et P3 (respectivement contrôle tension également, la visualisation et la programmation
de la ligne principale et de la ligne secondaire). des seuils sont effectuées en grandeurs réelles par
• Par l’intermédiaire du menu P0 il est possible de rapport à l’installation.
définir les données nominales telles que tension et • Le boîtier peut être programmée pour effectuer
fréquence nominale, utilisées ensuite comme réfé- les contrôles de tension sur secteurs triphasés,
rence pour la programmation des seuils (en pour- biphasés ou monophasés (par l’intermédiaire du
centage) des menus suivants. paramètre P0.03).

Ci-après sont indiquées les anomalies dont la gestion est assuré par le contrôle de tension.
Les colonnes 261 93 et 261 94 indiquent la présence de la fonction sur les différents modèles du boîtier.

Contrôle 261 93 261 94 Description


Tension minimum • • Une ou plusieurs phases trop basses
Tension maximum • Une ou plusieurs phases trop hautes
Seuil en deçà duquel líappa reil intervient plus
Absence phase • •
rapidement par rapport à un abaissement normal
Asymétrie Phases comprises sur l’intervalle Maximum-Minimum

(déséquilibrage) mais trop différentes l’une de l’autre
Fréquence minimum • Fréquence trop basse
Fréquence maximum • Fréquence trop haute
Séquence phases • Rotation inverse des phases

13
• Chacune des anomalies a un temps de retard elle est de nouveau acceptable (ex. P2.02). La
indépendant. L’anomalie doit avoir une durée inin- distance entre ces deux points définit l’hystérésis.
terrompue supérieure au temps indiqué pour inva- Par exemple, on peut établir qu’en deçà de 80%
lider le signal de présence tension. de la valeur nominale, la tension n’est plus utili-
• Tous les contrôles, exception faite du contrôle de sable et qu’elle est à nouveau acceptable une fois
tension minimum, peuvent être exclus indépendam- qu’elle est à nouveau supérieure à 85%, l’hystéré-
ment les uns des autres en plaçant le paramètre sis étant dans ce cas de 5%.
correspondant sur OFF. Le même principe s’applique à la tension maximum.
• Les limites de tension minimum et maximum sont • Pour les seuils de fréquence existe une hystérésis
définies par la programmation de deux seuils spé- fixe de 1% de la fréquence nominale.
cifiques, l’un définissant le point au-delà duquel la • Le rétablissement à l’issue d’une absence de
tension est considérée comme n’étant plus accep- phase est obtenue quand la tension repasse au-
table (ex. P2.01), l’autre, plus proche de la ten- dessus du seuil de rétablissement de tension
sion nominale, définissant le point à partir duquel minimum.

P2.04
Exemple de variation de la tension de la P2.05
ligne principale à l’intérieur des seuils
minimum et maximum et compte tenu des V MAIN
hystérésis correspondantes,
avec indication des temps de retard P2.02
présence/absence. Sur l’exemple, P2.01
la tension de ligne secondaire est
considérée comme absente et l’appareil
correspondant ouvert, aussi les temps LED VOK
d’inter-verrouillage ne sont pas indiqués. P2.03 P2.15 < P2.06 P2.05 P2.15
La barre INTERR. représente l’état voulu
INTERR.
de l’appareil de la ligne principale.

14
7. Programmation

7.1 Programmation des paramètres


• Pour accéder à la programmation, appuyer sur les • Validation de la modification du paramètre avec
touches H et E simultanément pendant 5 secondes la touche B
d’affilée • Augmentation de la valeur du paramètre sélection-
• Le voyant de la touche E clignotant indique que la né avec la touche F
programmation est en cours • Diminution de la valeur du paramètre sélectionné
• L’afficheur de la ligne principale indique le para- avec la touche G
mètre sélectionné par l’intermédiaire du code (par • Confirmation en appuyant sur la touche B
exemple P0.01)
• Lors de la modification d’un paramètre, l’afficheur
• L’afficheur de la ligne secondaire indique la valeur de la ligne secondaire affiche la valeur actuelle
de programmation du paramètre sélectionné (par clignotante du paramètre. Durant cette phase il
exemple 400) n’est pas possible de se déplacer sur un autre
• Changement de paramètre d’un même groupe en paramètre avant d’avoir validé
appuyant sur la touche A • Pour quitter la programmation, appuyer simultané-
• Passage au groupe suivant avec la touche E ment sur les touches E et H
• Passage au groupe précédent avec la touche H

Touche A Touche B
Déplacement au - Validation modification
même niveau - Confirmation configuration

Touche E
- Accès programmation
- Quitter vers niveau supérieur

Touche F
Augmenter valeur paramètre

Touche G
Abaisser valeur paramètre

Touche H
Accès au niveau inférieur

15
7.2 Tableau des menus
Menu Description
P0 Données nominales de l’installation
P1 Données générales
P2 Contrôle tension ligne principale
P3 Contrôle tension ligne secondaire
P4 Entrées programmables
P5 Sorties programmables
P6 Port de communication

7.3 Menu P0 - Données nominales


Prog. Description Plage Par défaut
P0.01 B Tension nominale Ue 100 … 690 Vca 380 Vca
P0.02 B Rapport de transformation TU 1.00 … 9.99 1.00
3Ph = Triphasée
P0.03 B Type de reseau 2PH = Biphasée 3Ph
1Ph = Monophasée
50H = 50Hz
P0.04 B Fréquence nominale Fe 50Hz
60H = 60Hz
OFF = Sans batterie
12 = 12 Vcc
P0.05 B Tension nominale batterie OFF
24 = 24 Vcc
48 = 48 Vcc

P0.01 - Tension nominale utilisée pour le calcul des seuils


P0.02 - Maintenir la programmation par défaut en cas de non-utilisation de TU
P0.04 - Fréquence nominale utilisée comme référence pour le calcul des seuils de fréquence
P0.05 - Utilisé pour les alarmes sur la tension de batterie

16
7.4 Menu P1 - Données générales
Prog. Description Plage Par défaut
U-G = Secteur-Groupe
P1.01 Type d’application U-G
U-U = Secteur-Secteur
Les paramètres OFF - Désactivé
en évidence OFF
P1.02 Contrôle séquence phase 123 - Direct
sont présents 321 - Inverse
uniquement
FEE - Avec feedback
sur la version P1.03 Contrôle commutation FEE
NOF - Sans feedback
261 94
P1.04 Temps maximum de commande appareil OFF / 1…900s 5s
OFF (Contrôle désactivé)
P1.05 Activation contrôle appareils extraits OFF
ON (Contrôle activé)
Temps maximum charge non alimentée (retard
P1.06 OFF / 1…3600s OFF
intervention alarme A07)
P1.07 Temps de retard mise en marche groupe 0 …. 900 s 1s
P1.08 Temps de refroidissement groupe 1…3600s 120 s
P1.09 Seuil minimum tension batterie OFF / 70…100% 75%
P1.10 Seuil maximum tension batterie OFF / 110…140% 130%
P1.11 Temps de retard seuils batterie 0…60 s 10 s

P1.01 - Définit le type de commutation (secteur-secteur / secteur-groupe)


P1.04 - Dans le cas où après la transmission d’une commande d’ouverture ou de fermeture à un appareil, celui-ci ne se
positionnerait pas correctement avant que cette durée ne se soit écoulée, alors activation de l’alarme A03 ou
A04
P1.05 - Activer le contrôle uniquement si les contacts correspondants sont câblés
P1.06 - En mode Automatique, si aucune des deux sources n’est disponible avant la fin de cette temporisation, alors
activation de l’alarme A07
P1.07 - Temporisation enclenchée lors de l’absence de tension sur la ligne principale, si fin de tempo ordre de démarrage
groupe.
Il s’agit d’une durée indépendante du temps d’ouverture des appareils
P1.08 - Temps pendant lequel le groupe est maintenu en marche pour son refroidissement après qu’il ait été isolé de la
charge

17
7.5 Menu P2 - Contrôle tension ligne principale
Prog. Description Plage Par défaut
P2.01 Seuil tension minimum - décrochage 70…98% Ue 85% Ue
P2.02 Seuil tension minimum - rétablissement 75…100% Ue 90% Ue
Les paramètres
en évidence P2.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
sont présents P2.04 Seuil tension maximum - décrochage 102…120% Ue / OFF 115% Ue
uniquement
sur la version P2.05 Seuil tension maximum - rétablissement 100…115% Ue 110% Ue
261 94 P2.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P2.07 Seuil absence phase 60 … 85% Ue / OFF 70% Ue
P2.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
P2.09 Seuil déséquilibrage tensions 1 … 20% Ue / OFF 10%
P2.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
P2.11 Seuil minimum fréquence OFF / 80… 100% Fe 95% Fe
P2.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
P2.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105% Fe
P2.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
Retard retour tension ligne principale dans les limites
P2.15 1 … 3600 s 10 s
(quand int. ligne secondaire ouvert)
Retard retour tension ligne principale dans les limites
P2.16 1 … 3600 s 60 s
(quand charge sur ligne secondaire)

P2.01 - P2.02 - P2.03 - Les deux premiers paramètres définissent le seuil de tension minimum et l’hystérésis corres-
pondante au rétablissement. P2.02 ne peut pas être programmé sur une valeur inférieure à P2.01. P2.03 définit le temps
de retard pour l’intervention de cette protection. Voir chapitre Contrôles de tension
P2.04 - P2.05 - P2.06 - Les deux premiers paramètres définissent le seuil de tension maximum et l’hystérésis corres-
pondante au rétablissement. P2.05 ne peut être programmé sur une valeur supérieure à P2.04. En programmant P2.04
sur OFF, le contrôle de tension maximum est désactivé. P2.06 définit le retard d’intervention de tension maximum. Voir
chapitre Contrôles de tension
P2.07 - P2.08 - Seuil de tension en deçà duquel se déclenche une intervention pour absence de phase, géné-
ralement plus rapide que l’abaissement. Le temps de retard pour l’absence phase est indiqué par P2.08
P2.09 - P2.10 - P2.09 définit le seuil maximum de déséquilibre entre les phases, en rapport à la tension nominale,
et P2.10 le retard d’intervention correspondant.
Ce contrôle peut être désactivé en programmant P2.09 sur OFF
P2.11 - P2.12 - Seuil (désactivable) et retard d’intervention de fréquence minimum
P2.13 - P2.14 - Seuil (désactivable) et retard d’intervention de fréquence maximum
P2.15 - Temps de retard retour ligne principale dans les limites, utilisé quand la source de la ligne secondaire n’est pas
disponible. Généralement plus court que P2.16, puisque, la charge n’étant pas alimentée, il est urgent de fournir une
tension
P2.16 - Temps de retard retour ligne principale dans les limites, utilisé quand la charge peut être connectée à la
ligne secondaire. Généralement plus long que P2.15, puisque, la charge étant sous tension il est possible d’attendre
plus longtemps avant de considérer la tension comme rétablie et stable

18
7.6 Menu P3* - Contrôle tension ligne secondaire
Prog. Description Plage Par défaut
P3.01 Seuil tension minimum - décrochage 70…98 % Ue 85 % Ue
P3.02 Seuil tension minimum - rétablissement 75…100 % Ue 90 % Ue
Les paramètres
en évidence P3.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
sont présents P3.04 Seuil tension maximum - décrochage 102…120 % Ue / OFF 115 % Ue
uniquement
P3.05 Seuil tension maximum - rétablissement 100…115 % Ue 110 % Ue
sur la version
261 94 P3.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P3.07 Seuil absence phase 60 … 85% Ue / OFF 70 % Ue
P3.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
Note: Pour
l’explication P3.09 Seuil déséquilibrage tensions 1 … 20 % / OFF 10 %
de la fonc- P3.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
tion des
paramètres, P3.11 Seuil minimum fréquence 99 … 80 % Fe / OFF 95 % Fe
se reporter à P3.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
la page pré-
cédente P3.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105 % Fe
(menu ligne P3.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
principale).
P3.15 Retard tension ligne secondaire dans les limites 1 … 3600 s 20 s

* Commentaires identiques au Menu P2

19
7.7 Menu P4 - Entrées programmables
Prog. Description Plage Par défaut
For
P4.01 Fonction entrée - Programmable 1 Forçage sur ligne
Voir liste secondaire
“Fonctions entrées
programmables” In.r
P4.02 Fonction entrée - Programmable 2 Inhibition sur ligne
principale

Fonctions entrées programmables


Fonction Description Notes
OFF OFF Entrée non utilisée
Quand elle est fermée, force la commutation sur la ligne
secondaire y compris si la tension de la ligne principale
Commutation forcée sur ligne
For est dans les limites. La commutation sur la ligne principale
secondaire (fonction EJP)
intervient quand l’entrée est libérée ou dans le cas où la
tension de la ligne secondaire ne serait pas dans les limites
En mode automatique, quand elle est fermée, elle bloque
le retour en automatique sur la ligne principale après que
IN.R Inhibition retour sur ligne principale la tension soit revenue dans les limites. Sert à éviter que la
seconde interruption de courant due au re-transfert intervienne
automatiquement à un moment imprévisible
Mise en marche/arrêt volontaire En mode automatique, quand elle est fermée, provoque la
S.GE
groupe mise en marche du groupe
Contact NF: si ouvert provoque l’ouverture des appareils et
EME Urgence
déclenche une alarme
Si elle est fermée, indique que le générateur est en
G.rE Générateur prêt automatique et non en alarme. Si elle est ouverte, génère un
code d’alarme
Si elle est fermée bloque toutes les fonctions du clavier à
Loc Blocage total clavier
l’exception des mesures
L.PA Blocage accès paramètres Si elle est fermée bloque l’accès aux configurations

7.8 Menu P5 - Sorties programmables


Prog. Description Plage Par défaut
Fonction sortie S.GE
P5.01 Voir liste “Fonctions sorties programmables”
Programmable 1 Start generator
Fonction sortie RDY
P5.02 Voir liste “Fonctions sorties programmables”
Programmable 2 ATS Ready
Fonction sortie ALA
P5.03 Voir liste “Fonctions sorties programmables”
Programmable 3 Alarme générale

20
Fonctions sorties programmables
Fonction Description Notes
OFF OFF Sortie non utilisée
Quand elle est fermée, le générateur doit être à l’arrêt.
S.GE Validation mise en marche générateur Contact ouvert pour mettre en marche le générateur.
Si la boîtier n’est pas alimentée, le générateur se met en marche
Signal que le boîtier est en mode automatique et sans alarmes,
RDY Commutation transfert automatique prêt
prêt à intervenir
ALA Alarme générale Signalisation alarme à distance
Bobine à minimum de tension Commande bobine à minimum de tension de l’appareil ligne
MCM
Ligne principale principal
Bobine à minimum de tension Commande bobine à minimum de tension de l’appareil ligne
MCS
Ligne secondaire secondaire
Débranchement des charges non prioritaires qui ne sont pas
alimentées par la ligne secondaire.
Débranchement charges
L.SH Elle est également commandée sur ligne principale.
non prioritaires
Contact fermé avant la commande de fermeture ligne secondaire
et ouvert avant la commande de fermeture ligne principale

7.9 Menu P6 - Communication série


Prog. Description Plage Par défaut
P6.01 Adresse sérielle RS-232 1…245 01
240 = 2400
Les paramètres 480 = 4800
en évidence P6.02 Vitesse (bauds) RS-232 960 = 9600 960
sont présentes 19.2 = 19200
uniquement 38.4 = 38400
sur la version
261 94 Rtu = Modbus RTU
P6.03 Protocole RS-232 RTU
ASC = Modbus ASCII
No = Aucune
P6.04 Parité RS-232 EVE = Even (Paire) No
Odd = Odd (Impaire)
P6.05 Adresse série RS-485 1…245 01
240 = 2400
480 = 4800
P6.06 Vitesse (bauds) RS-485 960 = 9600 960
19.2 = 19200
38.4 = 38400
Rtu = Modbus RTU
P6.07 Protocole RS-485 RTU
ASC = Modbus ASCII
No = Aucune
P6.08 Parité RS-485 EVE = Even (Paire) No
Odd = Odd (Impaire)

P6.01…P6.04 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-232
P6.05…P6.08 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-485,
disponible uniquement sur la version 261 94

21
8. Messages de diagnostic

Sur les afficheurs peuvent être visualisés à différents moments les messages suivants:

Code Description
(Tirets) - La temporisation d’inter-verrouillage est active.
- - -
S’affichent du côté vers lequel la charge est en cours de transfert
Sta (Start) - Commande de mise en marche générateur
Coo (Cooling) - Le générateur est maintenu en marche pour effectuer le refroidissement
(Test) - Si fixe, test off-load en cours, à savoir un test du groupe électrogène avec les contrôles de tension
Tes
actifs
Tes (Test) - Si clignotant, test on-load en cours, à savoir une simulation de l’absence secteur en automatique
Loc (Locked) - Indique que la fonction que l’on tente d’exécuter depuis le clavier est bloqué

22
9. Alarmes

• Durant le fonctionnement du boîtier, peut se pré- • La sortie à relais Alarme générale est désactivée
senter toute une série de situations anormales, les- en condition alarme, alors qu’elle est activée en
quelles sont signalées de différentes manières. condition normale. Le non-fonctionnement du boî-
• Certaines alarmes (déclenché, non réarmé) ont tier pour cause d’anomalie ou problème d’alimen-
un voyant spécifique qui en cas d’intervention se tation déclenche par conséquent la condition
met à clignoter. d’alarme sur le contact correspondant.
• D’autres alarmes sont signalées par l’intermédiaire • Certaines alarmes sont automatiquement désacti-
d’un code constitué d’un A (alarme) et d’une réfé- vées lorsque les conditions qui ont donnés lieu à
rence numérique qui indique de quelle alarme il leurs déclenchements sont éliminées.
s’agit. Ce code se visualise en clignotant sur un • D’autres alarmes, indiquées dans le tableau de la
des afficheurs. Si le code est relatif à la ligne prin- colonne MEM, sont en revanche à retenue et sont
cipale, l’alarme est visualisée sur l’afficheur de mémorisées.
gauche. En revanche, s’il se réfère à la ligne • Une fois que l’alarme a été mémorisée, pour être
secondaire ou s’il s’agit d’une alarme générale (ex. désactivée, il est nécessaire que les conditions
batterie) il est visualisé sur l’afficheur de droite. anormales soient éliminées et que l’opérateur
• Quand une alarme se déclenche, le voyant rouge appuie sur la touche RESET ou envoie un message
“ALARME” clignote en synchronisation avec le spécifique par l’intermédiaire de l’interface série.
voyant spécifique ou le code d’alarme.

23
Liste alarmes
Description
Code Voyant Cause MEM RESET MAN AUT
alarme
Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la
Tension batterie
A01 tension de batterie mesurée reste inférieure au seuil % programmé OUI OUI OUI OUI
Les alarmes en trop basse
sur P1.09 pendant la durée programmée sur P1.11
évidence sont
présentes Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la
Tension batterie
A02 tension de batterie mesurée reste supérieure au seuil % programmé OUI OUI OUI OUI
uniquement trop élevée
sur P1.10 pendant la durée programmée sur P1.11
sur la version
261 94 Se déclenche si l’appareil de ligne principale ne se place
pas dans la position commandée par le boîtier avant que
Timeout appareil ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-
A03 OUI NON NON OUI
ligne principale même la position requise. L’alarme peut se déclencher aussi
bien en fermeture qu’en ouverture. Si la tension est absente
sur les deux lignes, l’alarme ne se déclenche pas
Se déclenche si l’appareil de ligne secondaire ne se place
pas dans la position commandée par la boitier avant que
Timeout appareil ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-
A04 OUI NON NON OUI
ligne secondaire même la position requise. L’alarme peut se déclencher aussi
bien en fermeture qu’en ouverture. Si la tension est absente
sur les deux lignes, l’alarme ne se déclenche pas
Si elle est activée par le paramètre P1.02, cette alarme
Erreur séquence se déclenche quand est détectée une séquence de phase
A05 phase sur ligne différente de celle prévue par le paramètre P1.02, après un OUI OUI OUI OUI
principale retard d’environ 500 ms. Pour que la séquence puisse être
détectée, les trois phases doivent être > 50Vca
Erreur séquence
Idem alarme précédente en référence à la tension de la
A06 phase sur ligne OUI OUI OUI OUI
ligne secondaire
secondaire
La charge est restée sans tension pendant une durée
Timeout charge supérieure à P1.06.
A07 NON NON NON YES
non alimentée Ligne principale et ligne secondaire sont restées indisponibles
(absence tension ou appareil non fermé)
Générateur Une des entrées programmables est programmée sur “Generator
A08 NON OUI OUI OUI
non disponible ready” et signale que le générateur n’est pas disponible
Une des entrées programmables est programmée sur bouton
A09 Urgence OUI OUI OUI OUI
d’arrêt d’urgence et le contact correspondant est ouvert
Fréquence ligne
La fréquence de la ligne principale est hors des limites
A11 principale hors NON OUI OUI OUI
définies par P2.11 et P2.13
limites
Fréquence ligne
La fréquence de la ligne secondaire est hors des limites
A12 secondaire hors NON OUI OUI OUI
définies par P3.11 et P3.13
limites
La différence entre la tension phase-phase la plus haute et
Asymétrie tensions
A13 la plus basse de la ligne principale excède la limite définie NON OUI OUI OUI
ligne principale
par P2.09
La différence entre la tension phase-phase la plus haute et
Asymétrie tensions
A14 la plus basse de la ligne secondaire excède la limite définie NON OUI OUI OUI
ligne secondaire
par P3.09
Ligne principale/
Le contrôle des entrées de “non activé” est validé par le
secondaire
• paramètre P1.05 et le contact correspondant d’entrée de OUI OUI OUI OUI
non enclenché.
ligne principale ou ligne secondaire est ouvert
Appareil extrait
Ligne principale/
Le contact d’entrée “déclenché” est fermé.
secondaire
Cette condition est ignorée pendant une durée de 15 sec.
déclenchement.
• décomptée aussitôt après avoir commandé l’ouverture d’un OUI VIS VIS OUI
Intervention
appareil, pour éviter les erreurs de signal quand est utilisée
protection.
une bobine de décrochage
Appareil

24
10. Branchements

Borne Fonction Borne Fonction


1 Ouverture appareil ligne principale 16 Entrée contact SD appareil ligne principale
2 Commun commande ligne principale Entrée contact appareil débrochable
17
ligne principale
3 Fermeture appareil ligne principale
18 Entrée contact CA appareil ligne secondaire
4 Ouverture appareil ligne secondaire
19 Entrée contact SD appareil ligne secondaire
5 Commun commandes ligne secondaire
Entrée contact appareil débrochable
6 Fermeture appareil ligne secondaire 20
ligne secondaire
Relais programmable 1
7 Entrée programmable 1
(Fonction par défaut = Start/Stop générateur) 21
(Par défaut = Fonction EJP)
8 Commun relais programmable
Entrée programmable 2
9 Commun relais programmable 2 22
(Par défaut = Inhibition retour sur ligne principale)
Relais programmable 2/NO 23 + Alimentation CC
10
(Fonction par défaut = Boîtier prête) 24 – Alimentation CC
Relais programmable 2/NF
11 25 Commun pour entrées (de 15 à 22)
(Fonction par défaut = Boîtier prête)
26 Alimentation AC
12 Commun relais programmable 3
27 Alimentation AC
Relais de programmable 3/NO
13 (Fonction par défaut = Alarme globale - MAIN
fermé quand ok) L1 L2 Entrée de mesure triphasée ligne principale
L3 N
Relais de programmable 3/NF
14
(Fonction par défaut = Alarme générale) SEC.
15 Entrée contact CA appareil ligne principale L1 L2 Entrée de mesure triphasée ligne secondaire
L3 N

25
11. Caractéristiques techniques

Alimentation auxiliaire
Champ d’alimentation CC 9...70Vcc (Us=12-24-48Vcc)
Champ d’alimentation CA 187…264Vca (Us=220…240Vca)
Fréquence 45…65Hz
Puissance absorbée max. 6VA (Us=240Vca)
Puissance dissipée max. 4,8W (Us= 240Vca ou Us=48Vcc)
Courant absorbé max. 420mA à 12Vcc; 200mA à 24Vcc; 100mA à 48Vcc
Temps d’immunité à la micro-coupure 50ms
Entrées voltmétriques
Tension nominale max. (Ue) 690Vca phase-phase (400Vca phase-neutre)
Donnée d’utilisation UL 600Vca phase-phase (340Vca phase-neutre)
Champ de mesure 80…800Vc phase--phase
Champ de fréquence 45…65Hz
Type de mesure TRMS (valeur efficace réelle)
Impédance de l’entrée de mesure >1,1M Ω phase-phase et > 0,5M Ω phase-neutre
Mode d’activation Monophasée, biphasée, triphasée
Erreur de mesure Classe 0,5 ±0,25% f.s. ±1digit
Entrées numériques
Type d’entrée Négative
Courant d’entrée ≤10mA
Signal d’entrée état logique “0” ≤1,5 (type 2,9V)
Signal d’entrée état logique “1” ≥5,3 (type 4,3V)
Retard du signal d’entrée ≥50msec
Sorties à relais bornes 1-2 et 4-5
Type de contact 1 NO
Portée nominale à 250VAC 12A
Portée nominale contact 16A sur AC1 250V - B300
Courant maximum sur la borne 1.2 12A
Sorties à relais bornes 2-3 et 5-6
Type de contact 1 NO
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Courant maximum sur la borne 2.2 12A
Sorties à relais bornes 7-8
Type de contact 1 NO
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Sorties à relais bornes 9-10-11 et 12-13-14
Type de contact 1 contact NO/NF
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Lignes de communication
Vitesse de transmission de 1200…38400 bauds
Interface série RS232
Connexion par l’intermédiaire du connecteur RJ6/6
Interface série RS485 Isolée avec vitesse de transmission programmable 1200…38400
(261 94 uniquement) bauds. Connexion par l’intermédiaire de bornes extractibles
Isolation
Tension nominale d’isolation (Ui) 690V
Conditions ambiantes de fonctionnement
Température d’utilisation -20…+60°C
Température de stockage -30…+80°C
Humidité relative <90%
Pollution ambiante maximum Degré 3
Catégorie de surtension 3
Branchements
Type de bornes Extractibles
Section des conducteurs (min. et max.) 0,2…2,5 mm 2 (24÷12 AWG)
Couple de serrage 0,5 Nm (4,5 LBin)
Boîtier
Matériau Thermoplastique LEXAN 3412R
Type Encastré
Dimensions L x H x P 144 x 144 x 94mm
Degré de protection IP41 sur partie frontale, IP20 sur partie arrière
Poids 950g
Références normatives
IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3,
IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95

26
Electronic
Control Box
Item 261 93 – Item 261 94

October 08
Y1958C
Contents

1. General features . . . . . . . . . . . . . . . . . . 30
1.1 Versions . . ... . . . . . . . . . . . . . . . . . . . . . 30
1.2 Description ... . . . . . . . . . . . . . . . . . . . . . 30
1.3 Applications .. . . . . . . . . . . . . . . . . . . . . . 30
1.4 Installation . ... . . . . . . . . . . . . . . . . . . . . . 30
1.5 Supply . . . ... . . . . . . . . . . . . . . . . . . . . . 30

2. Description of the front panel . . . . . . . . 31


2.1 Selection keys . . . . . . . . . . . . . . . . . . . . . . 31
2.2 Measurement selection . . . . . . . . . . . . . . . . 32
2.3 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

3. Operating mode . . . . . . . . . . . . . . . . . . . 34
3.1 Reset mode (red LED of RESET key) . . . . . . . . 34
3.2 Manual mode (red LED of MAN key) . . . . . . 35
3.3 Automatic mode (red LED of AUT key) . . . . . . 35
3.4 Off-load test mode (without load) . . . . . . . . . . 35
3.5 On-load test mode (under load) . . . . . . . . . . . 35

4. Applications . . . . . . . . . . . . . . . . . . . . . . 36
4.1 Utility-to-generator Application . . . . . . . . . . . 36
4.2 Utility-to-utility Application . . . . . . . . . . . . . . . 36

5. Circuit breakers Control . . . . . . . . . . . . 37


5.1 With feedback (default setup) . . . . . . . . . . . 37
5.2 Without feedback . . . . . . . . . . . . . . . . . . . 38

6. Voltage controls . . . . . . . . . . . . . . . . . . . 39

7. Programming . . . . . . . . . . . . . . . . . . . . . 41
7.1 Setting the parameters . . . . . . . . . . . . . . . . . 41
7.2 Table of menus . . . . . . . . . . . . . . . . . . . . . . 42
7.3 P0 menu - Nominal data . . . . . . . . . . . . . . . 42
7.4 P1 menu - General data . . . . . . . . . . . . . . . 43
7.5 P2 menu - Main line voltage control . . . . . . . 44
7.6 P3 menu - Secondary line voltage control . . . . 45
7.7 P4 menu - Programmable inputs . . . . . . . . . . . 46
7.8 P5 menu - Programmable outputs . . . . . . . . . 46
7.9 P6 menu - Serial communication . . . . . . . . . . 47

8. Diagnostic messages . . . . . . . . . . . . . . . 48

9. Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 49

10. Connections . . . . . . . . . . . . . . . . . . . . . . 51

11. Technical features . . . . . . . . . . . . . . . . . 52

29
1. General features

1.1 Versions
• 261 93 - Standard version • 261 94 - Evoluted version + interface RS-485

1.2 Description
• Electronic Control Box - microprocessor • 8-key membrane keypad
• Two inputs of three-phase voltage measurement • RS-232 serial interface for set-up, remote control
• Power supply DC 12-24-48 VDC and supervision
• Power supply AC 220-240 VAC • RS-485 opto-isolated interface for MODBUS pro-
tocol (261 94)
• 2 LED displays, 3 digits 7 segments
• 2 programmable digital inputs
• 20 status and measurement LED indicators
• 3 programmable relay outputs (1NO + 2 C/O)

1.3 Applications
• Changeover between utility-to-utility, utility-to- • L-L voltage (or L-N voltage in case of monophase
generator lines)
• Control of motorized circuit breakers, motorized • Controls on minimum voltage, maximum voltage,
switches phase loss, asymmetry, minimum frequency, max-
• Start/stop generator imum frequency, with independent enabling and
delay
• Three-phase, two-phase or single-phase voltage
controls • Voltage thresholds with programmable hysteresis

1.4 Installation
• Install the electronic control box according to the • Set the parameters according to the required
wiring diagrams shown in the last pages of the wiring diagram, paying special attention when
manual programming the inputs / outputs
• Use the right wiring diagram for the application

1.5 Supply
• 261 93 and 261 94 have a double power sup- • In presence of both power supplies, the energy is
ply circuit, that means that they can operate with taken from the AC source
both AC and DC supply or with only one of the
two indifferently

30
2. Description of the front panel

2.1 Selection keys


• The front panel of the electronic control box has • A mimic diagram is located at the center of the
two LED displays showing the voltages of the two front panel; it shows the status of the circuit break-
power sources with their correspondent keys – (A) ers for load connection.
for Main line and (B) for Secondary line – which • Two keys – (C) and (D) – can open and close the
allows to select the measurements. circuit breakers (buttons are active only after press-
• The following keys: SET (E) - AUT (F) - MAN (G) - ing the MAN key).
RESET (H) allow to select the operating mode,
which is indicated by the corresponding LED.

A B

C D

31
2.2 Measurement selection
• When the key located under each display (A) and • After 1 minute without touching the key, the meas-
(B) is pressed several times, it will be possible to view urement returns to the default measurement, which
the various measurements of the line sequentially. may be the first voltage line-to-line or the first volt-
• Line-to-line voltages, line-to-neutral voltages (in case age line-to-neutral, depending on how the voltage
of single-phase lines) are available for each line. control is set up.
• The combinations of the red LEDs indicate which • In case of alarms or messages, the display will be
measurement is selected. The list of measurements occupied by the alarm code.
may change depending on whether the electronic By pressing the selection key, it is possible to
control box is set up for the three-phase, two-phase temporarily hide the alarm and access the meas-
or single-phase control. urements.

Example of a list of measurements


on an electronic control box set up for a
three-phase control.

2.3 LEDs
• The front panel has some LEDs which indicate the status of the circuit breakers controlled by the electronic
control box.

Led L1/L2/L3 Led L1/L2/L3 ALARM LED


Presence of voltage Presence of voltage on (red)
on main line (red) secondary line (red)

POWER SUPPLY LED


(green)

SET key LED


(red)

AUT key LED


Main line / (red)
secondary line
CONTROLS LED MAN key LED
(two-colors) (red)

RESET key LED


(red)

Status LED, Status LED,


main line secondary line
circuit breaker circuit breaker

32
• The following table describes the meaning of the various LEDs.
Some of them are bicolor and have a different meaning according to the color.

LED On Off Flashing


ALARM No alarm enabled One or more alarms enabled (RED)
Device powered
POWER SUPPLY No power
(GREEN)
OPEN/CLOSE Close control (RED)
No control
CONTROL Open control (GREEN)
Circuit breaker closed
4 (RED) Auxiliary contacts
OPEN/CLOSED
Circuit breaker open not connected
(GREEN)
Circuit breaker inserted
44 Circuit breaker not
DISCONNECTED or not-inserted-control
inserted in its base
disabled
Circuit breaker not
44
TRIPPED Circuit breaker tripped tripped or AL contact
not connected
1HZ = Time of presence/absence
PRESENCE in progress
Voltage present No voltage
L1/L2/L3 5HZ = Display measurements
selection

✱ If the auxiliary contacts have been connected, the LED will represent the status of the circuit breakers, otherwise it will
remain off.
✱✱ If the contacts have been connected properly, the LED will represent the status of the circuit breakers, otherwise the
LEDs will remain off.

33
3. Operating mode

• The four keys SET / AUT / MAN / RESET can • If the LED indicating the selected operating mode
be used to select the required operating mode, flashes, it means that the device is communicating
which will be indicated when the corresponding through the serial interface and that it could exe-
red LED lights up. cute remote commands, including the mode
change as well.

A B

C D

3.1 Reset mode (red RESET key LED)


• The electronic control box does not execute oper- • The generator control output will set up for switch-
ations but it just displays the status of the voltages ing off the group.
and the circuit breakers. • The status alarms of the circuit breakers are
• The opening and closing control outputs of the disabled.
switches remain all open, hence allowing for the • When an alarm occurs, it must be reset by press-
manual control from the front side of the motor con- ing the RESET key. If you are already in this oper-
trols. If the emergency input is activated, the unit ating mode, press the RESET button again.
will in any case order the opening of the switches.

34
3.2 Manual mode (red MAN key LED)
• The manual mode allows the operator to electrical- interlocking time and then it will close the required
ly open/close the circuit breakers with the special circuit breaker.
keys located at the front side of the device. • In manual mode, all the status alarms of the circuit
• In this mode, the voltages are constantly monitored breakers (disconnected and tripped) are disabled.
but the device just displays their status. The anomalous condition is signaled on the LED
• When one of the control keys is pressed for at but it will not be stored or dealt with as an alarm.
least 300 ms, the electronic control box changes • It is possible to manually control the startup and
the status of the circuit breakers from open to shutdown of the generator by holding down the
closed and vice-versa. key (G) MAN for 5 consecutive seconds. As long
• If a command is given to close a circuit breaker as the manual mode is kept, the status of the gen-
while the other is already closed, the unit will ini- erator will remain the one required.
tially open the other circuit breaker, wait for the

3.3 Automatic mode (red AUT key LED)


• In automatic mode, the device independently exe- startup of the generator, if any, and the
cutes both opening and closing operations of the changeover times between the circuit breakers.
circuit breakers as well as the startup and shut- • When the main line falls within the limits, the device
down of the generator, if any. switches again the load on it and determines the
• When the main line (MAIN) goes beyond the lim- cooling cycle, if required, of the generator.
its, after the set delay times, the device disconnects • The automatic cycles of operation vary according
the load from the main line and connects it to the to the type of application (utility-to-utility, utility-to-
secondary line (SEC), thus controlling both the generator).

3.4 Off-load test mode


• By starting from the automatic mode and by press- the coverage of the load. Under normal condi-
ing the (F) key for 5 seconds, it will be possible to tions, the load remains connected to the main
test the generator for 5 minutes. line, hence the generator operates with no
• The generator is manually started in order to check load (off-load generator).
its operation but since the electronic control box is • The execution of the off-load test is determined by
in automatic mode, the voltage controls will TES written steadily on the display.
remain active. • To end the execution of the test in advance, press
• By doing so, it is possible to verify the correct the (F) key again for 5 seconds or start the reset
operation of the generator, thus maintaining mode.
P l e a s e
note: The
execution of
this test 3.5 On-load test mode
involves trans-
ferring the • By starting from the automatic mode and by press- grammed times and parameters for the
load, hence a ing the (F) and (D) key simultaneously for 5 con- changeover so as to verify their adequacy.
power failure secutive seconds, it will be possible to carry out an • The execution of the on-load test is determined by
during the operational test (on-load test) which will totally sim- TES flashing on the display.
changeover ulate a lack of the power line voltage lasting one
due to the • To end the execution of the test in advance, repeat
minute.
interlocking the procedure with keys (F) and (D) for 5 seconds
times.
• Hence, the unit behaves exactly as if the line has or start the reset mode.
fallen out of the limits, thereby using all pro-

35
4. Applications

4.1 Utility-to-generator Application


• In the Utility-to-generator application (U-G, default • When the main line returns, the load is transferred
setup) the load is normally connected to the main again and the generator is kept in operation with
line. If there is an anomaly on the line or in case no load for a certain period of time so as to allow
of a transfer signal set from the outside, a start sig- its cooling.
nal will be sent to the generator which supplies the • The unit sends a start/stop command to the group
secondary line. through a relay output and can receive digital sig-
• When the voltage of the generator reaches the nals from the group indicating its status through
programmed limits, the electronic control box will programmable inputs.
order the changeover on the secondary line.

4.2 Utility-to-utility Application


• In the utility-to-utility application (U-U), the load is an anomaly on the main line or in case there is a
normally connected to the main line and the transfer signal set from the outside.
changeover to the secondary line occurs if there is

36
5. Circuit breakers control

• The circuit breakers control is carried out through • In case of an anomaly on the switch, hence caus-
two separate relays, one for closing and one for ing an alarm, the control outputs will both be
opening. opened till the resetting of the alarm.
• In reset mode, both control relays remain open, • There are two separate modes for controlling the
except for the emergency condition where the circuit breakers. These can be selected by using
opening can be controlled. the parameter P1.03

5.1 With feedback (default setup)


• The status indicated by the two-color front LED is output still remains energized for a certain period
the one detected by the auxiliary contacts. of time (+1 second during closing and +15 sec-
• The timeout alarms are enabled. They are gener- onds during opening, in order to allow the springs
ated if the circuit breakers do not reach the of the motor operators to be completely charged)
The auxiliary
contacts of the required position within a programmable time and then it is released.
circuit breakers P1.04 or immediately if they change position • The normal status of the control outputs is open.
are wired in when no command has been sent. • The interlocking times start when the first circuit
their imputs.
• The control outputs are timed. When the circuit breaker is actually opened, detected by the input,
With the
feedback is
breaker has executed the required operation, the and last for 0.5 steady seconds.
necessary to use
for the opening
operation of
DPX
250-630-1600
the shunth trip LED VMAIN OK
relay or the
undervoltage LED VSEC OK
relay.

3 1s
Example of a changeover with feedback, 1 15 s
assuming a utility-to-utility commutation. 15
The feedback input status is shown 0.5 s 0.5 s
in blue. The status of the control outputs 6 1s
is shown in green. The changeover time 4 15 s
is shown in yellow. 18

37
5.2 Without feedback
• The circuit breakers status LEDs remain off. • The changeover times between the opening of
• The timeout alarms are disabled. a switch and the closing of another start during
the commutation of the outputs and are steady
• The Opening/Closing control outputs remain
at 6 sec.
The auxiliary constantly in the required position for the circuit
contacts of the breaker.
circuit breakers
are not wired in
their inputs,
hence the
electronic
control box is
not informed on
their actual
state.

LED VMAIN OK

LED VSEC. OK

3
Example of a changeover with no 1
feedback. The actual status of the circuit INT. MAIN
breakers is shown in blue. The status 6 sec 6 sec
of the control outputs is shown in green. 6
The changeover time is shown 4
in yellow. INT. SEC.

38
6. Voltage controls

• Any condition required to determine whether a • It is possible to set up a TV transformation ratio in


supply source is or is not suitable is determined by case a lower voltage, relative to the actual voltage
the user through the P0 menu (system nominal of the system, is applied to the voltage inputs of
data) and the P2 and P3 menus (voltage control, the unit. Here, again, the display and the setup of
main line and secondary line, respectively). the thresholds will be executed in actual sizes
• It is possible to set up the system nominal data, referred to the system.
such as nominal voltage and frequency, through • The electronic control box can be programmed
the P0 menu, which will be used as a reference to perform voltage controls on three-phase, two-
for setting up the percentage thresholds of the fol- phase or single-phase nets (via the P0.03
lowing menus. parameter).

The following describes the anomalies monitored by the voltage control.


Columns 261 93 and 261 94 point out the presence of the function within their unit models.

Control 261 93 261 94 Description


Minimum voltage • • One or more phases too low
Maximum voltage • One or more phases too high
Threshold under which the device can operate faster
Phase failure • •
compared to a normal reduction
Phases included in the Maximum-Minimum interval,
Asymmetry (unbalance) •
yet too different between each other
Minimum frequency • Frequency too low
Maximum frequency • Frequency too high
Sequence of phases • Reverse rotation of phases

39
• Each anomaly has an independent delay time. tance between these two thresholds determines the
The anomaly must last consecutively longer than hysteresis. For instance, it may be considered that
the time specified for invalidating the voltage pres- when the nominal value is below 80%, the voltage
ence signal. may no longer be useable and that in order to be
• All controls, except for the minimum voltage con- considered useful, it must rise over 85%, thereby
trol, can be excluded separately by setting the determining a 5% hysteresis.
related parameter to OFF. The same concept applies to the maximum
• The minimum and maximum voltage limits are voltage.
specified by setting up two thresholds each, one • As for the frequency thresholds, there is a fixed 1%
which determines the point beyond which the volt- hysteresis of the nominal frequency.
age is no longer considered acceptable (e.g. • The retrieval after a phase failure occurs when the
P2.01) and the other, closer to the nominal volt- voltage rises above the minimum voltage retrieval
age, which determines the point in which it threshold.
becomes compatible again (e.g. P2.02). The dis-

P2.04
P2.05
Example of variation of the main line
voltage within the minimum and V MAIN
maximum thresholds and relative
hystereses, with indication of the P2.02
presence / absence delay times. The P2.01
example considers the secondary line
voltage absent with its circuit breaker
open, hence the changeover times are LED VOK
not shown. The INTERR. bar P2.03 P2.15 < P2.06 P2.05 P2.15
represents the required status
INTERR.
of the main line switch.

40
7. Programming

7.1 Setting the parameters


• Press the H and E keys together for 5 consecutive • Enable modification of the parameter with key B
seconds to start programming • Increase the value of the selected parameter with
• The flashing LED of the E key indicates that pro- key F
gramming is in progress • Decrease the value of the selected parameter with
• Main line display indicates the parameter selected key G
via the code (for instance P0.01) • Confirm by pressing key B
• Secondary line display indicates the set value of • While modifying a parameter, the secondary line
the selected parameter (for instance 400) display flashes with the current value of the param-
• Changing of parameters of the same group by eter. In this situation it is not possible to move to
pressing the key A another parameter without first confirming
• Movement to next group with key E • Exit from Setup by pressing E and H simultaneously
• Movement to previous group with key H

Key A Key B
It moves - Enable modification
at same level - Confirms setup

Key E
- Goes to Setup
- Exits to higher level

Key F
Increases parameter value

Key G
Decreases parameter value

Key H
Goes to lower level

41
7.2 Table of menus
Menu Description
P0 System nominal data
P1 General Data
P2 Main line voltage control
P3 Secondary line voltage control
P4 Programmable inputs
P5 Programmable outputs
P6 Communication port

7.3 P0 menu - Nominal data


Setup Description Range Default
P0.01 B Nominal voltage Ue 100 … 690 VAC 380 VAC
P0.02 B Transformation ratio TV 1.00 … 9.99 1.00
3Ph = Three-phase
P0.03 B Type of Network 2PH = Two-phase 3Ph
1Ph = Single-phase
50H = 50Hz
P0.04 B Nominal frequency Fe 50Hz
60H = 60Hz
OFF = No battery
12 = 12 VDC
P0.05 B Nominal battery voltage OFF
24 = 24 VDC
48 = 48 VDC

P0.01 - Nominal voltage used for calculating the thresholds


P0.02 - Leave default setup in case a TV is not used
P0.04 - Nominal frequency used as a reference for calculating the frequency thresholds
P0.05 - Used for the alarms on the battery voltage

42
7.4 P1 menu - General data
Setup Description Range Default
U-G = Utility-to-Generator
P1.01 Type of application U-G
U-U = Utility-to-Utility
The highlighted OFF - Disabled
OFF
parameters are P1.02 Control of phase sequence 123 - Direct
included only in 321 - Opposite
version 261 94 FEE - With feedback
P1.03 Changeover control FEE
NOF - Without feedback
P1.04 Circuit breakers Timeout OFF / 1…900s 5s
OFF (Control disabled)
P1.05 Enable control of withdrawn OFF
ON (Control enabled)
P1.06 Maximum time load not powered (A07 alarm delay) OFF / 1…3600s OFF
P1.07 Startup delay time, generator 0 …. 900 s 1s
P1.08 Cooling time, generator 1…3600s 120 s
P1.09 Minimum battery voltage threshold OFF / 70…100% 75%
P1.10 Maximum battery voltage threshold OFF / 110…140% 130%
P1.11 Battery threshold delay time 0…60 s 10 s

P1.01 - Determines the type of commutation (utility-to-utility/utility-to-generator)


P1.04 - If, after sending an opening or closing command to a switch, it does not place itself correctly within this time,
the A03 or A04 alarms will be generated
P1.05 - Enable the control only if their contacts are wired
P1.06 - If both sources are simultaneously unavailable in automatic mode for a period of time longer than P1.06, the
A07 alarm will be generated
P1.07 - Time between the line failure used below and transmission of the startup signal to the generator on the secondary
line.
It is a time which is independent from the circuit breaker opening time
P1.08 - Time whereby the generator is left in operation in order to cool down after being disconnected from the load

43
7.5 P2 menu - Main line voltage control
Setup Description Range Default
P2.01 Minimum voltage threshold - release 70…98% Ue 85% Ue
P2.02 Minimum voltage threshold - retrieval 75…100% Ue 90% Ue
The highlighted
parameters are P2.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
included only in P2.04 Maximum voltage threshold - release 102…120% Ue / OFF 115% Ue
version 261 94
P2.05 Maximum voltage threshold - retrieval 100…115% Ue 110% Ue
P2.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P2.07 Threshold of phase failure 60 … 85% Ue / OFF 70% Ue
P2.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
P2.09 Voltage unbalance threshold 1 … 20% Ue / OFF 10 %
P2.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
P2.11 Threshold of minimum frequency OFF / 80… 100% Fe 95% Fe
P2.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
P2.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105% Fe
P2.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
Voltage return delay on main line within
P2.15 1 … 3600 s 10 s
the limits (when circuit breaker secondary line open)
Voltage return delay on main line within the limits
P2.16 1 … 3600 s 60 s
(when load on secondary line)

P2.01 - P2.02 - P2.03 - The first two parameters determine the minimum voltage threshold and its hysteresis when
retrieved. P2.02 cannot be set to a value which is lower than P2.01. P2.03 determines the delay time for the activation
of this protection. See chapter on Voltage controls
P2.04 - P2.05 - P2.06 - The first two parameters determine the maximum voltage threshold and its hysteresis when
retrieved. P2.05 cannot be set to a value which is higher than P2.04. Setting P2.04 to OFF will disable the maximum
voltage control. P2.06 determines the maximum voltage tripping delay. See chapter on Voltage controls
P2.07 - P2.08 - Voltage threshold under which there is an activation due to phase failure, usually faster than the
reduction. The delay time for the phase failure is specified by P2.08
P2.09 - P2.10 - P2.09 determines the maximum unbalance threshold between the phases, referred to the nominal
voltage; P2.10 determines the relative tripping delay.
This control can be disabled by setting P2.09 to OFF
P2.11 - P2.12 - Threshold (disabled) and minimum frequency tripping delay
P2.13 - P2.14 - Threshold (disabled) and maximum frequency tripping delay
P2.15 - Return delay time on main line within the limits, used when the source of the secondary line is not available.
Normally shorter than P2.16: since the load is not powered, it is necessary to supply voltage
P2.16 - Return delay time on main line within the limits, used when the load can be connected to the secondary line.
Normally longer than P2.15: since the load is “covered”, it is possible to wait longer before considering the voltage
stably retrieved

44
7.6 P3 menu - Secondary line voltage control
Setup Description Range Default
P3.01 Minimum voltage threshold - release 70…98 % Ue 85 % Ue
P3.02 Minimum voltage threshold - retrieval 75…100 % Ue 90 % Ue
The highlighted
parameters are P3.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
included only in P3.04 Maximum voltage threshold - release 102…120 % Ue / OFF 115 % Ue
version 261 94
P3.05 Maximum voltage threshold - retrieval 100…115 % Ue 110 % Ue
P3.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P3.07 Threshold of phase failure 60 … 85% Ue / OFF 70 % Ue
P3.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
Note: For
explanations P3.09 Voltage unbalance threshold 1 … 20 % / OFF 10 %
on the opera- P3.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
tion of
parameters, P3.11 Threshold of minimum frequency 99 … 80 % Fe / OFF 95 % Fe
see previous P3.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
page con-
cerning the P3.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105 % Fe
main line P3.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
menu.
P3.15 Voltage delay of secondary line within the limits 1 … 3600 s 20 s

45
7.7 P4 menu - Programmable inputs
Setup Description Range Default
For
P4.01 Programmable input function 1 Forced changeover
See list ìP rogrammable on secondary line
input functions” In.r
P4.02 Programmable input function 2 Inhibition return
on main line

Programmable input functions


Function Description Notes
OFF OFF Input not used
When closed, it forces the changeover on the secondary line
even if main line voltage is within the limits. Re-commutation
For Forced changeover on secondary line
occurs on the main line when the input is released or in case
the secondary line voltage is not within the limits
In automatic mode, when closed, it blocks the automatic
return on the main line after the main line voltage has returned
IN.R Inhibition return on main line within the limits. It is used for preventing the second power
cutoff, due to the re-transferal, from occurring automatically in
an unexpected moment
S.GE Generator voluntary Start/stop In automatic mode, when closed, it starts up the generator
NC contact which, if opened, opens both circuit breakers
EME Emergency
and generates an alarm
If closed, it refers to a Generator in automatic mode and not
G.rE Generator ready
in alarm mode. If opened, it generates an alarm code
If closed, it locks all keyboard functions except for measurement
Loc Keyboard total lock
views
L.PA Lock parameter access If closed, it locks the access to setups

7.8 P5 menu - Programmable outputs


Setup Description Range Default
Output function S.GE
P5.01 See list “Programmable output functions”
Programmable 1 Start generator
Output function RDY
P5.02 See list “Programmable output functions”
Programmable 2 ATS Ready
Output function ALA
P5.03 See list “Programmable output functions”
Programmable 3 Global alarm

46
Programmable output functions
Function Description Notes
OFF OFF Output not used
When closed, the generator must be inactive.
S.GE Consent to start up the generator Contact opens to start generator.
If the unit is not powered, the generator starts
Indicates unit automatically and without alarms, ready to
RDY Automatic transfer switch ready
start operating
ALA Global alarm De-energizes in case of an alarm
Minimum coil
MCM Main line switch voltage minimum opening coil command
Main line
Minimum coil Secondary line switch voltage minimum opening coil
MCS
Secondary line command
Disconnection of the non-priority loads that are not powered
by the secondary line branch.
It is also controlled on the secondary line.
L.SH Non-priority load disconnection
Contact which is closed before the secondary line closing
command and opened before the main line closing
command

7.9 P6 menu - Serial communication


Setup Description Range Default
P6.01 Serial address RS-232 1…245 01
240 = 2400
The highlighted 480 = 4800
parameters are P6.02 Speed (baudrate) RS-232 960 = 9600 960
included only in 19.2 = 19200
version 261 94 38.4 = 38400
Rtu = Modbus RTU
P6.03 Protocol RS-232 RTU
ASC = Modbus ASCII
No = None
P6.04 Parity RS-232 EVE = Even No
Odd = Odd
P6.05 Serial address RS-485 1…245 01
240 = 2400
480 = 4800
P6.06 Speed (baudrate) RS-485 960 = 9600 960
19.2 = 19200
38.4 = 38400
Rtu = Modbus RTU
P6.07 Protocol RS-485 RTU
ASC = Modbus ASCII
No = None
P6.08 Parity RS-485 EVE = Even No
Odd = Odd

P6.01…P6.04 - They determine the transmission format and the protocol used on communication port RS-232
P6.05…P6.08 - They determine the transmission format and the protocol used on communication port RS-485,
available only on 261 94

47
8. Diagnostic messages

The following messages can be displayed, at different moments:

Code Description
(Dashes) - The interlocking time is in progress.
- - -
They are displayed from the side in which the load is being transferred
Sta (Start) - Indicates that the Start Generator command has been sent
Coo (Cooling) - Indicates that the generator is being left running for the cooling
(Test) - When steady, it indicates that an off-load test - namely a power unit test with the voltage controls
Tes
active - is currently in progress
(Test) - When flashing, it indicates that an on-load test, namely an automatic net failure simulation, is
Tes
currently in progress
Loc (Locked) - It indicates that the keyboard function one is trying to execute is locked

48
9. Alarms

• When the unit is running, it is possible to verify a • The Global alarm relay output is de-energized dur-
number of abnormal situations which are signaled ing alarm conditions whereas it is energized under
in different ways. normal conditions. If the unit does not operate due
• Some alarms (tripped, withdrawn) have a dedi- to a failure or power supply problems, it will gen-
cated LED which begins to flash when the erate an alarm condition on its contact.
alarms go on. • Some alarms are automatically reset when the
• Other alarms are signaled through a code which conditions generating them fail to work.
consists of an A (alarm) and a number indicating • Other alarms, described in the chart in the RIT col-
which alarm it is. This code will be flashing on one umn, are retentive, thus they are stored.
of the displays. If the code refers to the main line • Once the alarm has been stored, the abnormal
branch, the alarm will be displayed on the left. conditions must be eliminated in order to be reset.
Conversely, if the code refers to the secondary line Also, the operator must press the RESET key or
branch or if it is a generic alarm (e.g. battery), it send a special message via the serial interface.
will be displayed on the right.
• When an alarm goes on, the red LED “ALARM”
flashes in sync with the dedicated LED or with the
alarm code.

49
Alarm list
Description
Code Led Causes RIT RESET MAN AUT
alarm
This occurs if the P0.06 parameter is OFF and if the battery
Battery voltage
A01 voltage measured remains lower than the threshold % set YES YES YES YES
The highlighted too low
with P1.09 for the time set with P1.11
alarm are
This occurs if the P0.06 parameter is not OFF and if the
included only in Battery voltage
A02 battery voltage measured remains higher than the threshold YES YES YES YES
version 261 94 too high
% set with P1.10 for the time set with P1.11
It is generated if the main line switch does not move to the
position controlled by the unit within the time determined
Main line by P1.04 or if it comes out of the required position on its
A03 YES NO NO YES
switch timeout own. The alarm can be generated when closing and when
opening. If there is no power on both lines, the alarm will
not be generated
It is generated if the secondary line switch does not move to
the position controlled by the unit within the time determined
Secondary line by P1.04 or if it comes out of the required position on its
A04 YES NO NO YES
switch timeout own. The alarm can be generated when closing and when
opening. If there is no power on both lines, the alarm will
not be generated
If enabled by parameter P1.02, it is generated when a
phase sequence – different from what has been specified in
Main line incorrect
A05 P1.02 – is detected, after a delay of about 500 ms. YES YES YES YES
phase sequence
In order for the sequence to be detected, all three phases
must be > 50VAC
Secondary line
A06 incorrect phase As the previous, referred to the secondary line voltage YES YES YES YES
sequence
The load was left with no voltage for a period of time longer
Timeout load than P1.06.
A07 NO NO NO YES
not powered The main line and the secondary line were not available (no
power or switch not closed)
Generator One of the programmable inputs is set to “Generator ready”,
A08 NO YES YES YES
not available hence signaling that the generator is not available
One of the programmable inputs is set to the emergency
A09 Emergency YES YES YES YES
button and the corresponding input contact is open
Main line
The frequency of the main line is not within the limits
A11 frequency NO YES YES YES
determined with P2.11 and P2.13
outside limits
Secondary line
The frequency of the secondary line is not within the limits
A12 frequency NO YES YES YES
determined with P3.11 and P3.13
outside limits
The difference between the higher and lower voltage
Main line voltage
A13 between lines of the main line exceeds the limit determined NO YES YES YES
asymmetry
with P2.09
The difference between the higher and lower voltage
Secondary line
A14 between lines of the secondary line exceeds the limit NO YES YES YES
voltage asymmetry
determined with P3.09
Main/secondary The withdrawn input control is enabled by parameter P1.05
• line withdrawn. and the corresponding main line or secondary line input YES VIS VIS YES
Switch removed contact is open
Main/secondary The tripped input contact it is closed.
line tripped. This condition is ignored for 15 seconds which begins
• YES VIS VIS YES
Protection immediately after giving the command to open a switch so
activation. Switch as to avoid false signalings when using a release coil

50
10. Connections

Mors. Function Mors. Function


1 Main line circuit breaker opening 16 AL input of Main line circuit breaker
2 Common main line commands DISCONNECTED input of Main line circuit
17
breaker
3 Main line circuit breaker closing
18 AUX input of Secondary line circuit breaker
4 Secondary line circuit breaker opening
19 AL input of Secondary line circuit breaker
5 Common secondary line commands
DISCONNECTED input of Secondary line
6 Secondary line circuit breaker closing 20
circuit breaker
Programmable relay 1
7 Programmable input 1
(Default function = Start/Stop generator) 21
(Default = Forcing on secondary line)
8 Common programmable relay 1
Programmable input 2
Common programmable relay 2 22
9 (Default = Inhibition return on main line)
Programmable relay 2/NO 23 + VDC supply
10
(Default function = Unit ready) 24 – VDC supply
Programmable relay 2/NC
11 25 Common for inputs (from 15 to 22)
(Default function = Unit ready)
26 AC supply
12 Common programmable relay 3
27 AC supply
Programmable relay 3/NO
13 (Default function = Global alarm - MAIN
closed when ok) L1 L2 Main line three-phase measurement input
L3 N
Programmable relay 3/NC
14
(Default function = Global alarm) SEC.
Secondary line three-phase
15 AUX input of Main line circuit breaker L1 L2
measurement input
L3 N

51
11. Technical features

Auxiliary power supply


DC power supply operating limits 9...70VDC (Us=12-24-48VDC)
AC power supply operating limits 187…264VAC (Us=220…240VAC)
Frequency 45…65Hz
Max. absorbed power 6VA (Us=240VAC)
Max. dissipated power 4,8W (Us= 240VAC or Us=48VDC)
Max. absorbed current 420mA to 12VDC; 200mA to 24VDC; 100mA to 48VDC
Micro-breaking immunity time 50ms
Voltage inputs
Max. rated voltage (Ue) 690VAC phase-phase (400VAC phase-neutral)
UL usage data 600VAC phase-phase (340VAC phase-neutral)
Measuring range 80…800VAC phase--phase
Frequency range 45…65Hz
Type of measurement TRMS (true effective value)
Measurement input impedance > 1,1 M Ω phase-phase and > 0,5 M Ω phase-neutral
Type of connection One, two or three phase
Measurement error Class 0,5 ±0,25% f.s. ±1digit
Digital inputs
Type of input Negative
Input current ≤10mA
Input current “0” state ≤1,5 (typical 2,9V)
Input current “1” state ≥5,3 (typical 4,3V)
Input signal delay ≥50msec
Relay outputs terminals 1-2 and 4-5
Type of contact 1 NO
Nominal range at 250VAC 12A
Contact nominal range 16A in AC1 250V - B300
Maximum current on terminal 1.2 12A
Relay outputs terminals 2-3 and 5-6
Type of contact 1 NO
8A in AC1 250V - B300
Contact nominal range
30VDC 1A Auxiliary service supply
Maximum current on terminal 2.2 12A
Relay outputs terminals 7-8
Type of contact 1 NO
8A in AC1 250V - B300
Contact nominal range
30VDC 1A Auxiliary service supply
Relay outputs terminals 9-10-11 and 12-13-14
Type of contact 1 change-over contact
8A in AC1 250V - B300
Contact nominal range
30VDC 1A Auxiliary service supply
Communication interfaces
Programmable Baud-rate 1200…38400 bps
RS232 serial interface
Connection via RJ6/6 connector
RS485 serial interface Isolated with programmable Baud-rate 1200…38400 bps
(COM only) Connection via removable terminals
Insulation
Rated insulation Voltage (Ui) 690V
Environmental operating conditions
Operating temperature -20…+60°C
Temperature -30…+80°C
Relative humidity <90%
Maximum Pollution degree Degree 3
Overvoltage category 3
Connections
Type of terminal Removable
Conductor section (min. and max.) 0,2…2,5 mmq (24÷12 AWG)
Tightening torque 0,5 Nm (4,5 LBin)
Housing
Material Thermoplastic LEXAN 3412R
Version Flush mounting
Dimensions L x H x D 144 x 144 x 94mm
Protection degree IP41 on front, IP20 on back
Weight 950g
Certifications and compliance
IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3,
IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95

52
Schéma
Wiring diagram

Alimentation boitier et moteurs en 12-24-48Vdc


Electronic Control Box and motors supply in 12-24-48Vdc LG1B
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.05 24

Principal Secondaire
Main Sec

ref. 04055

Pour DPX 125/160 ➞ 1000W filtré


Pour DPX 250/630/1600 et DMX ➞ 1000W 230Vac / 24Vdc
For DPX 125/160 ➞ 1000W filtred
For DPX 250/630/1600 et DMX ➞ 1000W _~

Moteurs
Motors

23 24 25 26 27
0V~
Commun entrées
Com digital inputs

220-240V~

+ -

ALIM. AUX. ALIM. AUX.


DC AC
DC AUX AC AUX
SUPPLY SUPPLY

53
Schéma
Wiring diagram

Alimentation boitier en 230Vac et 12Vdc et moteurs en 230Vac


Electronic Control Box supply 230Vac and 12Vdc and motor supply in 230Vac LG3
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P1.04 OFF

Principal Secondaire
Main Sec

3A 3A

ref. 04055

ref. 04210 Moteurs


12Vcc 0,8A Motors

23 24 25 26 27
Commun entrées
Com digital inputs

220-240V~
0V~

+ -

ALIM. AUX. ALIM. AUX.


DC AC
DC AUX AC AUX
SUPPLY SUPPLY

54
Schéma
Wiring diagram

Relevé de tensions monophasées


Single-phase voltage inputs LG4
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 1Ph

N 100 - 690 Vac N


50/60 Hz

Principal Secondaire
Main Sec 1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

55
Schéma
Wiring diagram

Relevé de tensions monophasées


Single-phase voltage inputs LG5
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 1Ph

N 100 - 690 Vac N


50/60 Hz

Principal Secondaire
Main Sec 1A

1A

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

56
Schéma
Wiring diagram

Relevé de tensions biphasées


Two-phase voltage inputs LG8
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 2Ph

R S 100 - 690 Vac R S


50/60 Hz

Principal Secondaire
Main Sec. 1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

57
Schéma
Wiring diagram

Relevé de tensions biphasées


Two-phase voltage inputs LG9
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 2Ph

R S 100 - 690 Vac R S


50/60 Hz

Principal Secondaire
Main Sec. 1A

1A

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

58
Schéma
Wiring diagram

Relevé de tensions triphasées


Three-phase voltage inputs LG6
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 3Ph

N R S T 100 - 690 Vac N R S T


50/60 Hz

Principal Secondaire
Main Sec 1A gG

1A gG

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

59
Schéma
Wiring diagram

Relevé de tensions triphasées


Three-phase voltage inputs LG7
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P0.03 3Ph

N R S T 100 - 690 Vac N R S T


50/60 Hz

Principal Secondaire
Main Sec 1A

1A

N L1 L2 L3 N L1 L2 L3

PRINCIPAL SECONDAIRE
MAIN SEC.

RELEVE DE TENSION
VOLTAGE INPUTS

100-690 Vac 50/60 Hz

60
P1.04
P1.03

P1.05
Alimentation

Parameter
Paramètre
Schéma

électrique des
moteurs
Tension
electric motors

OFF
OFF
NOF
Setting
Wiring diagram

Programmation

Red
Red

Black
Black
1 2 1 2
DPX 125/160 sans feedback

Moteur Moteur
DPX 125/160 without feedback

normal secours
Parameter setting for the wiring diagram in picture:

Main motor Sec. motor


3 4 5 3 4 5

Blue

Blue
Violet

Violet
Orange

Orange

DPX 125: mechanical interlock not available


DPX 125: verrouillage mécanique non disponible
Programmation des paramètres pour le schéma représenté sur la figure:
LG10

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX

61
réf: 261 93/94
62
P1.03
P1.05
Alimentation

Parameter
Paramètre
Schéma

électrique des
moteurs

12-Red
12-Red
14-White

14-White
Tension CA Principal CA Secondaire
Aux. main Aux. Sec.
electric motors

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

Programmation

52-White
52-White

54-Red
54-Red
SD Principal SD Secondaire

Red
Red

Black
Black
Trip Trip
main sec.
1 2 1 2
DPX 125/160 with feedback
DPX 125/160 avec feedback

51-Black
51-Black
Moteur Moteur
principal secondaire
Parameter setting for the wiring diagram in picture:

Main motor Sec. motor


3 4 5 3 4 5

Blue

Blue
Violet

Violet
Orange

Orange
2-Red
3-White
2-Red
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn

DPX 125: not-inserted contact not available


main sec.

DPX 125: mechanical interlock not available


1-Black
1-Black

DPX 125: verrouillage mécanique non disponible


Programmation des paramètres pour le schéma représenté sur la figure:

DPX 125: contact de condition “non enclenché” non disponible


LG11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
P1.03
P1.05
Alimentation

Parameter
Paramètre
Schéma

électrique des

12-Red
14-White
moteurs

12-Red
14-White
Tension CA Principal CA Secondaire
electric motors Feedback Feedback
main Sec.

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

Programmation

52-White
54-Red

52-White
54-Red

Red
Red

Black
Black
SD Principal SD Secondaire
Trip Trip
1 2 1 2 main sec.

51-Black

51-Black
Moteur Moteur
principal secondaire
Parameter setting for the wiring diagram in picture:

Main motor Sec. motor


DPX 125/160 avec EJP + feedback

3 4 5 3 4 5
DPX 125/160 with EJP and feedback

Blue

Blue
Violet

Violet
Orange

Orange
2-Red
3-White
2-Red
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn

DPX 125: not-inserted contact not available


main sec.

DPX 125: mechanical interlock not available


1-Black
1-Black

DPX 125: verrouillage mécanique non disponible


Programmation des paramètres pour le schéma représenté sur la figure:

DPX 125: contact de condition “non enclenché” non disponible


EJP
LG12

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX

63
réf: 261 93/94
64
Alimentation

P1.04
P1.03

P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension
electric motors

OFF
OFF
NOF
Setting
Wiring diagram

Bl
Bl

Rd
Wh
Rd
Wh
2 4 6 2 4 6

Moteur Moteur Programmation


principal secondaire
Main motor Sec. motor
DPX 250/630 sans feedback

1 3 5 1 3 5

Bl
Bl

Rd
Wh
Rd
Wh
DPX 250/630 without feedback

Parameter setting for the wiring diagram in picture:


Programmation des paramètres pour le schéma représenté sur la figure:
LG13

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
66
Alimentation

P1.03
P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension
electric motors

12-Red
12-Red
14-White

14-White
CA Principal CA Secondaire
Aux. main Aux. Sec.

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

Bl
Bl

Rd
Wh
Rd
Wh
2 4 6 2 4 6

Moteur Moteur Programmation

C1

C1
54-Red
54-Red

52-White
52-White
Principal principal Secondaire secondaire
Main Sec SD Principal SD Secondaire
Main motor Sec. motor Trip Trip
main sec.

C2

C2
51-Black

51-Black
1 3 5 1 3 5

Bl
Bl

Rd
Wh
Rd
Wh
Parameter setting for the wiring diagram in picture:

2-Red
2-Red

3-White
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.

1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:
DPX 250/630 with EJP + feedback + shunt trip
DPX 250/630 avec EJP + feedback + declencheur EM

EJP
LG15

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
Alimentation

P1.03
P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension
electric motors

12-Red
12-Red
14-White

14-White
CA Principal CA Secondaire
Aux. main Aux. Sec.

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

Bl
Bl

Rd
Rd

Wh
Wh
2 4 6 2 4 6

Programmation

C1

C1
Moteur Moteur

54-Red
54-Red

52-White
52-White
Principal principal Secondaire secondaire SD Principal SD Secondaire
Main Main motor Sec Sec. motor Trip Trip
main sec.

C2

C2
51-Black

51-Black
1 3 5 1 3 5

Bl
Bl

Rd
Wh
Rd
Wh
Parameter setting for the wiring diagram in picture:

2-Red
2-Red
3-White

3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.

1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:

Arrêt
d’urgence
Emergency
DPX 250/630 with feedback + shunt trip + emergency stop

stop
DPX 250/630 avec feedback + declencheur EM + arrêt d’urgence
LG16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX

67
réf: 261 93/94
68
Alimentation

P1.04
P1.03

P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension
electric motors

OFF
OFF
NOF
Setting
Wiring diagram

1 3 5 7 1 3 5 7

Moteur Moteur Programmation


principal secondaire
DPX 1600 sans feedback

Main motor Sec. motor


DPX 1600 without feedback

2 4 6 8 2 4 6 8
Parameter setting for the wiring diagram in picture:
Programmation des paramètres pour le schéma représenté sur la figure:
LG17

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
70
Alimentation

P1.03
P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension

14-White

14-White
electric motors

12-Red
12-Red
CA Normal CA Secours
Feedback Feedback
main Sec.

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

1 3 5 7 1 3 5 7

Programmation

C1

C1
Moteur Moteur

54-Red

54-Red

52-White
52-White
Principal principal Secondaire secondaire
Main Sec SD Normal SD Secours
Main motor Sec. motor Trip Trip
main sec.

C2

C2
51-Black
51-Black
2 4 6 8 2 4 6 8
Parameter setting for the wiring diagram in picture:

3-White

3-White

2-Red
2-Red
Débro normal Débro secours
Withdrawn Withdrawn
main sec.
1-Black

1-Black
Programmation des paramètres pour le schéma représenté sur la figure:

Arrêt
d’urgence
Emergency
stop
DPX 1600 with feedback + shunt trip + emergency stop
DPX 1600 avec feedback + declencheur EM + arrêt d’urgence
LG19

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
Alimentation

P1.03
P1.05
électrique des
moteurs

Parameter
Paramètre
Schéma

Tension

14-White

12-Red
14-White
electric motors

12-Red
CA Principal CA Secondaire
Aux. main Aux. Sec.

11-Black

11-Black
FEE
ON
Setting
Wiring diagram

1 3 5 7 1 3 5 7

Programmation

C1

C1
Moteur Moteur

54-Red

52-White

52-White
54-Red
Principal principal Secondaire secondaire
Main Sec SD Principal
Main motor SD Secondaire
Sec. motor Trip
Trip
main
sec.

C2
C2
51-Black

51-Black
2 4 6 8 2 4 6 8
DPX 1600 with EJP + feedback
DPX 1600 avec EJP + feedback

Parameter setting for the wiring diagram in picture:

3-White

3-White

2-Red
2-Red
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.

1-Black

1-Black
Programmation des paramètres pour le schéma représenté sur la figure:

EJP
LG20

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3

+ - PRINCIPAL SECONDAIRE
0V~

Trip sec.

Aux. sec.

Trip main

MAIN SEC.
Aux. main
SD normal

CA normal
SD secours

CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2

Entrée prog. 1

Withdrawn sec.

Withdrawn main
220-240V~

Com digital inputs


Commun entrées

Contact débro normal


Contact débro secours

Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz

BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX

71
réf: 261 93/94
Schéma
Wiring diagram

DPX 125  1600 avec declencheur MT + arrêt d’urgence


DPX 125  1600 with UVR and emergency stop LG24B
Programmation des paramètres pour le schéma représenté sur la figure:
Parameter setting for the wiring diagram in picture:
Paramètre Programmation
Parameter Setting

P5.02 MCM
P5.03 MCS
P1.03 FEE

Tension électrique des


bobines
Tension
electric releases

Arrêt
d’urgence
Emergency
stop

U< Principal U< Secondaire


Sec
Main

9 10 11 12 13 14

RELAIS RELAIS
PROGRAMMABLE 2 PROGRAMMABLE 3
PROG. 2 RELAY PROG. 3 RELAY

L’alimentation des commandes motorisées doit être secours


Safety supply of the motor operators is required

72
Programmation des paramètres
Setting of parameters

Valeur Valeur
Setup Setup
Value Value
P0.01 P3.01
P0.02 P3.02
P0.03 P3.03
P0.04 P3.04
P0.05 P3.05
P1.01 P3.06
P1.02 P3.07
P1.03 P3.08
P1.04 P3.09
P1.05 P3.10
P1.06 P3.11
P1.07 P3.12
P1.08 P3.13
P1.09 P3.14
P1.10 P3.15
P1.11 P4.01
P2.01 P4.02
P2.02 P5.01
P2.03 P5.02
P2.04 P5.03
P2.05 P6.01
P2.06 P6.02
P2.07 P6.03
P2.08 P6.04
P2.09 P6.05
P2.10 P6.06
P2.11 P6.07
P2.12 P6.08
P2.13
P2.14
P2.15
P2.16

Schémas de branchement utilisés:


Wiring diagram used:

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

...............................................................................................................................................................................................................

A compléter et à retourner au Service clients en cas de besoin


To be filled in and sent to Customer Service, if needed

73