d’Automatisme
Réf. 261 93 – Réf. 261 94
Octobre 08
Y1958C
Table des matieres
1. Caractéristiques générales . . . . . . . . . . 4
1.1 Versions . . ... . . . . . . . . . . . . . . . . . . . . . 4
1.2 Description ... . . . . . . . . . . . . . . . . . . . . . 4
1.3 Applications .. . . . . . . . . . . . . . . . . . . . . . 4
1.4 Installation . ... . . . . . . . . . . . . . . . . . . . . . 4
1.5 Alimentation ... . . . . . . . . . . . . . . . . . . . . . 4
2. Description de la façade . . . . . . . . . . . . 5
2.1 Touches de sélection . . . . . . . . . . . . . . . . . . 5
2.2 Sélection mesures . . . . . . . . . . . . . . . . . . . 6
2.3 Indicateurs à diodes . . . . . . . . . . . . . . . . . . 6
3. Modes de fonctionnement . . . . . . . . . . . 8
3.1 Mode reset (voyant touche RESET rouge) . . . . 8
3.2 Mode manuelle (voyant touche MAN rouge) . 9
3.3 Mode automatique (voyant touche AUT rouge) . 9
3.4 Mode test off-load (hors-charge) . . . . . . . . . . . 9
3.5 Mode test on-load (en charge) . . . . . . . . . . . 9
4. Applications . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Application Secteur-Groupe . . . . . . . . . . . . . 10
4.2 Application Secteur-Secteur . . . . . . . . . . . . . . 10
5. Commande appareils . . . . . . . . . . . . . . 11
5.1 Avec feedback . . . . . . . . . . . . . . . . . . . . . 11
5.2 Sans feedback . . . . . . . . . . . . . . . . . . . . . 12
6. Contrôles de tension . . . . . . . . . . . . . . . 13
7. Programmation . . . . . . . . . . . . . . . . . . . 15
7.1 Programmation des paramètres . . . . . . . . . . . 15
7.2 Tableau des menus . . . . . . . . . . . . . . . . . . . 16
7.3 Menu P0 - Données nominale . . . . . . . . . . . . 16
7.4 Menu P1 - Données générales . . . . . . . . . . . 17
7.5 Menu P2 - Contrôle tension ligne principale . . 18
7.6 Menu P3 - Contrôle tension ligne secondaire . . 19
7.7 Menu P4 - Entrées programmables . . . . . . . . . 20
7.8 Menu P5 - Sorties programmables . . . . . . . . 20
7.9 Menu P6 - Communication série . . . . . . . . . . 21
8. Messages de diagnostic . . . . . . . . . . . . . 22
9. Alarmes . . . . . . . . . . . . . . . . . . . . . . . . . 23
10. Branchements . . . . . . . . . . . . . . . . . . . . 25
3
1. Caractéristiques générales
1.1 Versions
• 261 93 - Version standard • 261 94 - Version évoluée + interface RS-485
1.2 Description
• Commutateur automatique de secteur à micro- • Clavier à membrane à 8 touches
processeur • Sortie série RS-232 (contrôle à distance et super-
• Deux entrées de mesure de tensions triphasées vision)
• Alimentation CC 12-24-48 Vcc • Sortie RS-485 isolée pour protocole MODBUS
• Alimentation CA 220-240 Vca (261 94)
• 2 moniteurs à diodes, 3 chiffres de 7 segments • 2 entrées TOR (tout ou rien) programmables
• 20 diodes de visualisation états et mesures • 3 sorties à relais (1 NO + 2 NO/NF) program-
mables
1.3 Applications
• Commutation entre ligne-ligne et ligne-groupe • Relevé tensions phase-phase (ou sur les tensions
électrogène phase-neutre dans le cas des lignes monophasés)
• Commande des appareils motorisés • Contrôles de tension minimum, de tension maxi-
• Marche/arrêt groupe électrogène mum, d’absence de phase, d’asymétrie, de fré-
quence minimum et de fréquence maximum avec
• Relevé tensions sur lignes triphasés, biphasés ou
validation et retard indépendants
monophasés
• Seuil de tension avec hystérésis programmable
1.4 Installation
• Installer l’appareil en suivant les schémas de bran- • Programmer les paramètres en fonction du sché-
chement (voir dernières pages du manuel) ma de branchement adopté, en faisant particu-
• Utiliser le schéma de branchement correspondant lièrement attention à la programmation des
à l’application entrées/sorties
1.5 Alimentation
• 261 93 et 261 94 ont un double circuit d’ali- • Quand le boîtier est alimenté en CA et CC en
mentation ; ils peuvent être alimentés en CA et même temps, l’énergie est prélevé en CA
CC en même temps, ou seulement en CA ou en
CC indifféremment
4
2. Description de la façade
A B
C D
5
2.2 Sélections des mesures
• En appuyant à plusieurs reprises sur la touche située • Au bout de 1 minute sans que la touche ait été
sous chaque moniteur (A) et (B), il est possible de enfoncée, est rétablie la mesure par défaut qui
visualiser successivement les différentes mesures de la peut être la première tension phase-phase ou la
ligne correspondante. première tension phase-neutre en fonction de la
• Pour chaque ligne, sont disponibles les tensions configuration du contrôle de tension.
phase-phase et les tensions phase-neutre (en pré- • En cas d’alarmes ou de messages, affichage du le
sence de ligne monophasée). message d’alarme.
• Les combinaisons des diodes rouges indiquent les En appuyant sur la touche de sélection, il est
mesures sélectionnées. La liste des mesures varie possible de masquer temporairement l’alarme et
selon que l’appareil est configuré pour le contrôle d’accéder aux mesures.
triphasé, biphasé ou monophasé.
Diode ALIMENTATION
(verte)
Appareil enclenché ou
44 Appareil non enclenché
NON ENCLENCHÉ contrôle enclenchement
sur la base
désactivé
Appareil non déclenché
44
DÉCLENCHÉ Appareil déclenché ou contact SD
non connecté
1HZ = Temps présence absence
PRÉSENCE
Présence tension Absence tension en cours
L1/L2/L3
5HZ = Sélection mesures moniteur
✱ Si les contacts auxiliaires ont été branchés, le voyant représente l’état de l’appareil, sinon il reste éteint.
✱✱ Si les contacts correspondants ont été branchés à cet effet, le voyant représente l’état de l’appareil, sinon les
voyants restent éteints.
7
3. Modes de fonctionnement
• A l’aide des quatre touches SET / AUT / MAN • Si le voyant qui indique le mode de fonctionne-
/ RESET il est possible de sélectionner le mode ment sélectionné clignote, cela indique que l’ap-
de fonctionnement voulu et indiqué par l’allumage pareil est en communication à travers l’interface
du voyant rouge correspondant. série et qu’il est susceptible d’effectuer des com-
mandes transmises à distance (par exemple une
commande de changement de mode).
A B
C D
8
3.2 Mode Manuel (voyant touche MAN rouge)
• Le mode manuel permet à l’opérateur d’ouvrir/fer- boîtier ouvre initialement l’autre appareil, laisse
mer électriquement les appareils à l’aide des s’écouler le temps d’inter-verrouillage puis ferme
touches présentes sur la façade de l’appareil. l’appareil voulu.
• Dans ce mode les tensions sont constamment • En Manuel toutes les alarmes relatives à l’état des
contrôlées mais le boîtier se limite à en visualiser appareils (non enclenchés et déclenchés) sont
l’état. désactivées. L’alarme est indiquée sur le voyant
• En appuyant pendant au moins 300 ms sur une correspondant mais n’est pas mémorisée.
des touches de commande, le boîtier commute • Il est possible de commander manuellement la
l’état de l’appareil correspondant (d’ouvert à mise en marche et l’arrêt du groupe électrogène
fermé et vice-versa). en maintenant enfoncée la touche (G) MAN pen-
• Dans le cas où serait commandé la fermeture dant 5 secondes d’affilée. Tant que l’on reste en
d’un appareil alors que l’autre est déjà fermé, le mode manuel, l’état du groupe reste celui voulu.
9
4. Applications
10
5. Commande appareils
• La commande de la motorisation des appareils est • Suite à une anomalie sur l’appareil provoquant
assurée par deux relais distincts, l’un pour la fer- une alarme, les sorties de commande sont toutes
meture et l’autre pour l’ouverture. deux ouvertes jusqu’à l’élimination de l’alarme.
• En mode Reset, les deux relais de commande restent • Ils existent deux modes distincts de contrôle des
ouverts, sauf en condition d’urgence dans laquelle appareils, sélectionnables par l’intermédiaire du
l’ouverture de l’appareil peut être commandée. paramètre P1.03
3 1s
Exemple de commande des appareils 1 15 s
avec feedback en supposant une 15
commutation secteur-secteur. En bleu est 0.5 s 0.5 s
indiqué l’état des entrées de feedback. 6 1s
En vert l’état des sorties de commande. 4 15 s
En jaune le temps de commutation. 18
11
5.2 Sans feedback
• Les voyants d’état de l’appareil restent éteints. • Les temps d’inter-verrouillage entre l’ouverture
• Les alarmes de Timeout sont désactivées. d’un appareil et la fermeture de l’autre est
décompté à partir de la commutation des sor-
• Les sorties des commandes Ouverture/Fermetu-
ties et il est de 6 secondes.
Les contacts re restent constamment dans la position requise
auxiliaires CA pour l’appareil.
de l’appareil ne
sont pas câblés
sur les entrées
respectives,
donc le boîtier
n’est pas
informée de leur
état effectif.
LED VMAIN OK
LED VSEC. OK
3
Exemple de commande des appareils 1
sans feedback. INT. MAIN
En bleu est indiqué l’état effectif des 6 sec 6 sec
appareils. 6
En vert l’état des sorties de commande. 4
En jaune le temps de commutation. INT. SEC.
12
6. Contrôles de tension
• Toutes les conditions, servant à établir si une sour- • Il est possible de programmer un rapport de trans-
ce d’alimentation est appropriée ou non, sont défi- formation TU dans le cas où serait appliquée aux
nies par l’utilisateur par l’intermédiaire du menu entrées de tension du boîtier une tension inférieure
P0 (données nominales de l’installation) et des à la tension effective de l’installation. Dans ce cas
menus P2 et P3 (respectivement contrôle tension également, la visualisation et la programmation
de la ligne principale et de la ligne secondaire). des seuils sont effectuées en grandeurs réelles par
• Par l’intermédiaire du menu P0 il est possible de rapport à l’installation.
définir les données nominales telles que tension et • Le boîtier peut être programmée pour effectuer
fréquence nominale, utilisées ensuite comme réfé- les contrôles de tension sur secteurs triphasés,
rence pour la programmation des seuils (en pour- biphasés ou monophasés (par l’intermédiaire du
centage) des menus suivants. paramètre P0.03).
Ci-après sont indiquées les anomalies dont la gestion est assuré par le contrôle de tension.
Les colonnes 261 93 et 261 94 indiquent la présence de la fonction sur les différents modèles du boîtier.
13
• Chacune des anomalies a un temps de retard elle est de nouveau acceptable (ex. P2.02). La
indépendant. L’anomalie doit avoir une durée inin- distance entre ces deux points définit l’hystérésis.
terrompue supérieure au temps indiqué pour inva- Par exemple, on peut établir qu’en deçà de 80%
lider le signal de présence tension. de la valeur nominale, la tension n’est plus utili-
• Tous les contrôles, exception faite du contrôle de sable et qu’elle est à nouveau acceptable une fois
tension minimum, peuvent être exclus indépendam- qu’elle est à nouveau supérieure à 85%, l’hystéré-
ment les uns des autres en plaçant le paramètre sis étant dans ce cas de 5%.
correspondant sur OFF. Le même principe s’applique à la tension maximum.
• Les limites de tension minimum et maximum sont • Pour les seuils de fréquence existe une hystérésis
définies par la programmation de deux seuils spé- fixe de 1% de la fréquence nominale.
cifiques, l’un définissant le point au-delà duquel la • Le rétablissement à l’issue d’une absence de
tension est considérée comme n’étant plus accep- phase est obtenue quand la tension repasse au-
table (ex. P2.01), l’autre, plus proche de la ten- dessus du seuil de rétablissement de tension
sion nominale, définissant le point à partir duquel minimum.
P2.04
Exemple de variation de la tension de la P2.05
ligne principale à l’intérieur des seuils
minimum et maximum et compte tenu des V MAIN
hystérésis correspondantes,
avec indication des temps de retard P2.02
présence/absence. Sur l’exemple, P2.01
la tension de ligne secondaire est
considérée comme absente et l’appareil
correspondant ouvert, aussi les temps LED VOK
d’inter-verrouillage ne sont pas indiqués. P2.03 P2.15 < P2.06 P2.05 P2.15
La barre INTERR. représente l’état voulu
INTERR.
de l’appareil de la ligne principale.
14
7. Programmation
Touche A Touche B
Déplacement au - Validation modification
même niveau - Confirmation configuration
Touche E
- Accès programmation
- Quitter vers niveau supérieur
Touche F
Augmenter valeur paramètre
Touche G
Abaisser valeur paramètre
Touche H
Accès au niveau inférieur
15
7.2 Tableau des menus
Menu Description
P0 Données nominales de l’installation
P1 Données générales
P2 Contrôle tension ligne principale
P3 Contrôle tension ligne secondaire
P4 Entrées programmables
P5 Sorties programmables
P6 Port de communication
16
7.4 Menu P1 - Données générales
Prog. Description Plage Par défaut
U-G = Secteur-Groupe
P1.01 Type d’application U-G
U-U = Secteur-Secteur
Les paramètres OFF - Désactivé
en évidence OFF
P1.02 Contrôle séquence phase 123 - Direct
sont présents 321 - Inverse
uniquement
FEE - Avec feedback
sur la version P1.03 Contrôle commutation FEE
NOF - Sans feedback
261 94
P1.04 Temps maximum de commande appareil OFF / 1…900s 5s
OFF (Contrôle désactivé)
P1.05 Activation contrôle appareils extraits OFF
ON (Contrôle activé)
Temps maximum charge non alimentée (retard
P1.06 OFF / 1…3600s OFF
intervention alarme A07)
P1.07 Temps de retard mise en marche groupe 0 …. 900 s 1s
P1.08 Temps de refroidissement groupe 1…3600s 120 s
P1.09 Seuil minimum tension batterie OFF / 70…100% 75%
P1.10 Seuil maximum tension batterie OFF / 110…140% 130%
P1.11 Temps de retard seuils batterie 0…60 s 10 s
17
7.5 Menu P2 - Contrôle tension ligne principale
Prog. Description Plage Par défaut
P2.01 Seuil tension minimum - décrochage 70…98% Ue 85% Ue
P2.02 Seuil tension minimum - rétablissement 75…100% Ue 90% Ue
Les paramètres
en évidence P2.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
sont présents P2.04 Seuil tension maximum - décrochage 102…120% Ue / OFF 115% Ue
uniquement
sur la version P2.05 Seuil tension maximum - rétablissement 100…115% Ue 110% Ue
261 94 P2.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P2.07 Seuil absence phase 60 … 85% Ue / OFF 70% Ue
P2.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
P2.09 Seuil déséquilibrage tensions 1 … 20% Ue / OFF 10%
P2.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
P2.11 Seuil minimum fréquence OFF / 80… 100% Fe 95% Fe
P2.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
P2.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105% Fe
P2.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
Retard retour tension ligne principale dans les limites
P2.15 1 … 3600 s 10 s
(quand int. ligne secondaire ouvert)
Retard retour tension ligne principale dans les limites
P2.16 1 … 3600 s 60 s
(quand charge sur ligne secondaire)
P2.01 - P2.02 - P2.03 - Les deux premiers paramètres définissent le seuil de tension minimum et l’hystérésis corres-
pondante au rétablissement. P2.02 ne peut pas être programmé sur une valeur inférieure à P2.01. P2.03 définit le temps
de retard pour l’intervention de cette protection. Voir chapitre Contrôles de tension
P2.04 - P2.05 - P2.06 - Les deux premiers paramètres définissent le seuil de tension maximum et l’hystérésis corres-
pondante au rétablissement. P2.05 ne peut être programmé sur une valeur supérieure à P2.04. En programmant P2.04
sur OFF, le contrôle de tension maximum est désactivé. P2.06 définit le retard d’intervention de tension maximum. Voir
chapitre Contrôles de tension
P2.07 - P2.08 - Seuil de tension en deçà duquel se déclenche une intervention pour absence de phase, géné-
ralement plus rapide que l’abaissement. Le temps de retard pour l’absence phase est indiqué par P2.08
P2.09 - P2.10 - P2.09 définit le seuil maximum de déséquilibre entre les phases, en rapport à la tension nominale,
et P2.10 le retard d’intervention correspondant.
Ce contrôle peut être désactivé en programmant P2.09 sur OFF
P2.11 - P2.12 - Seuil (désactivable) et retard d’intervention de fréquence minimum
P2.13 - P2.14 - Seuil (désactivable) et retard d’intervention de fréquence maximum
P2.15 - Temps de retard retour ligne principale dans les limites, utilisé quand la source de la ligne secondaire n’est pas
disponible. Généralement plus court que P2.16, puisque, la charge n’étant pas alimentée, il est urgent de fournir une
tension
P2.16 - Temps de retard retour ligne principale dans les limites, utilisé quand la charge peut être connectée à la
ligne secondaire. Généralement plus long que P2.15, puisque, la charge étant sous tension il est possible d’attendre
plus longtemps avant de considérer la tension comme rétablie et stable
18
7.6 Menu P3* - Contrôle tension ligne secondaire
Prog. Description Plage Par défaut
P3.01 Seuil tension minimum - décrochage 70…98 % Ue 85 % Ue
P3.02 Seuil tension minimum - rétablissement 75…100 % Ue 90 % Ue
Les paramètres
en évidence P3.03 Retard seuil tension minimum 0.1 …. 900 s 1.0 s
sont présents P3.04 Seuil tension maximum - décrochage 102…120 % Ue / OFF 115 % Ue
uniquement
P3.05 Seuil tension maximum - rétablissement 100…115 % Ue 110 % Ue
sur la version
261 94 P3.06 Retard seuil tension maximum 0.1 …. 900 s 1.0 s
P3.07 Seuil absence phase 60 … 85% Ue / OFF 70 % Ue
P3.08 Retard seuil absence phase 0.1 … 30.0 s 0.1 s
Note: Pour
l’explication P3.09 Seuil déséquilibrage tensions 1 … 20 % / OFF 10 %
de la fonc- P3.10 Retard seuil déséquilibrage tensions 0.1 … 900 s 5.0 s
tion des
paramètres, P3.11 Seuil minimum fréquence 99 … 80 % Fe / OFF 95 % Fe
se reporter à P3.12 Retard seuil minimum fréquence 0.1 … 900 s 5.0 s
la page pré-
cédente P3.13 Seuil maximum fréquence 101 … 120% Fe / OFF 105 % Fe
(menu ligne P3.14 Retard seuil maximum fréquence 0.1 … 900 s 3.0 s
principale).
P3.15 Retard tension ligne secondaire dans les limites 1 … 3600 s 20 s
19
7.7 Menu P4 - Entrées programmables
Prog. Description Plage Par défaut
For
P4.01 Fonction entrée - Programmable 1 Forçage sur ligne
Voir liste secondaire
“Fonctions entrées
programmables” In.r
P4.02 Fonction entrée - Programmable 2 Inhibition sur ligne
principale
20
Fonctions sorties programmables
Fonction Description Notes
OFF OFF Sortie non utilisée
Quand elle est fermée, le générateur doit être à l’arrêt.
S.GE Validation mise en marche générateur Contact ouvert pour mettre en marche le générateur.
Si la boîtier n’est pas alimentée, le générateur se met en marche
Signal que le boîtier est en mode automatique et sans alarmes,
RDY Commutation transfert automatique prêt
prêt à intervenir
ALA Alarme générale Signalisation alarme à distance
Bobine à minimum de tension Commande bobine à minimum de tension de l’appareil ligne
MCM
Ligne principale principal
Bobine à minimum de tension Commande bobine à minimum de tension de l’appareil ligne
MCS
Ligne secondaire secondaire
Débranchement des charges non prioritaires qui ne sont pas
alimentées par la ligne secondaire.
Débranchement charges
L.SH Elle est également commandée sur ligne principale.
non prioritaires
Contact fermé avant la commande de fermeture ligne secondaire
et ouvert avant la commande de fermeture ligne principale
P6.01…P6.04 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-232
P6.05…P6.08 - Définissent le format de transmission et le protocole utilisé sur le port de communication RS-485,
disponible uniquement sur la version 261 94
21
8. Messages de diagnostic
Sur les afficheurs peuvent être visualisés à différents moments les messages suivants:
Code Description
(Tirets) - La temporisation d’inter-verrouillage est active.
- - -
S’affichent du côté vers lequel la charge est en cours de transfert
Sta (Start) - Commande de mise en marche générateur
Coo (Cooling) - Le générateur est maintenu en marche pour effectuer le refroidissement
(Test) - Si fixe, test off-load en cours, à savoir un test du groupe électrogène avec les contrôles de tension
Tes
actifs
Tes (Test) - Si clignotant, test on-load en cours, à savoir une simulation de l’absence secteur en automatique
Loc (Locked) - Indique que la fonction que l’on tente d’exécuter depuis le clavier est bloqué
22
9. Alarmes
• Durant le fonctionnement du boîtier, peut se pré- • La sortie à relais Alarme générale est désactivée
senter toute une série de situations anormales, les- en condition alarme, alors qu’elle est activée en
quelles sont signalées de différentes manières. condition normale. Le non-fonctionnement du boî-
• Certaines alarmes (déclenché, non réarmé) ont tier pour cause d’anomalie ou problème d’alimen-
un voyant spécifique qui en cas d’intervention se tation déclenche par conséquent la condition
met à clignoter. d’alarme sur le contact correspondant.
• D’autres alarmes sont signalées par l’intermédiaire • Certaines alarmes sont automatiquement désacti-
d’un code constitué d’un A (alarme) et d’une réfé- vées lorsque les conditions qui ont donnés lieu à
rence numérique qui indique de quelle alarme il leurs déclenchements sont éliminées.
s’agit. Ce code se visualise en clignotant sur un • D’autres alarmes, indiquées dans le tableau de la
des afficheurs. Si le code est relatif à la ligne prin- colonne MEM, sont en revanche à retenue et sont
cipale, l’alarme est visualisée sur l’afficheur de mémorisées.
gauche. En revanche, s’il se réfère à la ligne • Une fois que l’alarme a été mémorisée, pour être
secondaire ou s’il s’agit d’une alarme générale (ex. désactivée, il est nécessaire que les conditions
batterie) il est visualisé sur l’afficheur de droite. anormales soient éliminées et que l’opérateur
• Quand une alarme se déclenche, le voyant rouge appuie sur la touche RESET ou envoie un message
“ALARME” clignote en synchronisation avec le spécifique par l’intermédiaire de l’interface série.
voyant spécifique ou le code d’alarme.
23
Liste alarmes
Description
Code Voyant Cause MEM RESET MAN AUT
alarme
Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la
Tension batterie
A01 tension de batterie mesurée reste inférieure au seuil % programmé OUI OUI OUI OUI
Les alarmes en trop basse
sur P1.09 pendant la durée programmée sur P1.11
évidence sont
présentes Se déclenche si le paramètre P0.06 n’est pas sur OFF et si la
Tension batterie
A02 tension de batterie mesurée reste supérieure au seuil % programmé OUI OUI OUI OUI
uniquement trop élevée
sur P1.10 pendant la durée programmée sur P1.11
sur la version
261 94 Se déclenche si l’appareil de ligne principale ne se place
pas dans la position commandée par le boîtier avant que
Timeout appareil ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-
A03 OUI NON NON OUI
ligne principale même la position requise. L’alarme peut se déclencher aussi
bien en fermeture qu’en ouverture. Si la tension est absente
sur les deux lignes, l’alarme ne se déclenche pas
Se déclenche si l’appareil de ligne secondaire ne se place
pas dans la position commandée par la boitier avant que
Timeout appareil ne s’écoule la temporisation sur P1.04 ou s’il quitte de lui-
A04 OUI NON NON OUI
ligne secondaire même la position requise. L’alarme peut se déclencher aussi
bien en fermeture qu’en ouverture. Si la tension est absente
sur les deux lignes, l’alarme ne se déclenche pas
Si elle est activée par le paramètre P1.02, cette alarme
Erreur séquence se déclenche quand est détectée une séquence de phase
A05 phase sur ligne différente de celle prévue par le paramètre P1.02, après un OUI OUI OUI OUI
principale retard d’environ 500 ms. Pour que la séquence puisse être
détectée, les trois phases doivent être > 50Vca
Erreur séquence
Idem alarme précédente en référence à la tension de la
A06 phase sur ligne OUI OUI OUI OUI
ligne secondaire
secondaire
La charge est restée sans tension pendant une durée
Timeout charge supérieure à P1.06.
A07 NON NON NON YES
non alimentée Ligne principale et ligne secondaire sont restées indisponibles
(absence tension ou appareil non fermé)
Générateur Une des entrées programmables est programmée sur “Generator
A08 NON OUI OUI OUI
non disponible ready” et signale que le générateur n’est pas disponible
Une des entrées programmables est programmée sur bouton
A09 Urgence OUI OUI OUI OUI
d’arrêt d’urgence et le contact correspondant est ouvert
Fréquence ligne
La fréquence de la ligne principale est hors des limites
A11 principale hors NON OUI OUI OUI
définies par P2.11 et P2.13
limites
Fréquence ligne
La fréquence de la ligne secondaire est hors des limites
A12 secondaire hors NON OUI OUI OUI
définies par P3.11 et P3.13
limites
La différence entre la tension phase-phase la plus haute et
Asymétrie tensions
A13 la plus basse de la ligne principale excède la limite définie NON OUI OUI OUI
ligne principale
par P2.09
La différence entre la tension phase-phase la plus haute et
Asymétrie tensions
A14 la plus basse de la ligne secondaire excède la limite définie NON OUI OUI OUI
ligne secondaire
par P3.09
Ligne principale/
Le contrôle des entrées de “non activé” est validé par le
secondaire
• paramètre P1.05 et le contact correspondant d’entrée de OUI OUI OUI OUI
non enclenché.
ligne principale ou ligne secondaire est ouvert
Appareil extrait
Ligne principale/
Le contact d’entrée “déclenché” est fermé.
secondaire
Cette condition est ignorée pendant une durée de 15 sec.
déclenchement.
• décomptée aussitôt après avoir commandé l’ouverture d’un OUI VIS VIS OUI
Intervention
appareil, pour éviter les erreurs de signal quand est utilisée
protection.
une bobine de décrochage
Appareil
24
10. Branchements
25
11. Caractéristiques techniques
Alimentation auxiliaire
Champ d’alimentation CC 9...70Vcc (Us=12-24-48Vcc)
Champ d’alimentation CA 187…264Vca (Us=220…240Vca)
Fréquence 45…65Hz
Puissance absorbée max. 6VA (Us=240Vca)
Puissance dissipée max. 4,8W (Us= 240Vca ou Us=48Vcc)
Courant absorbé max. 420mA à 12Vcc; 200mA à 24Vcc; 100mA à 48Vcc
Temps d’immunité à la micro-coupure 50ms
Entrées voltmétriques
Tension nominale max. (Ue) 690Vca phase-phase (400Vca phase-neutre)
Donnée d’utilisation UL 600Vca phase-phase (340Vca phase-neutre)
Champ de mesure 80…800Vc phase--phase
Champ de fréquence 45…65Hz
Type de mesure TRMS (valeur efficace réelle)
Impédance de l’entrée de mesure >1,1M Ω phase-phase et > 0,5M Ω phase-neutre
Mode d’activation Monophasée, biphasée, triphasée
Erreur de mesure Classe 0,5 ±0,25% f.s. ±1digit
Entrées numériques
Type d’entrée Négative
Courant d’entrée ≤10mA
Signal d’entrée état logique “0” ≤1,5 (type 2,9V)
Signal d’entrée état logique “1” ≥5,3 (type 4,3V)
Retard du signal d’entrée ≥50msec
Sorties à relais bornes 1-2 et 4-5
Type de contact 1 NO
Portée nominale à 250VAC 12A
Portée nominale contact 16A sur AC1 250V - B300
Courant maximum sur la borne 1.2 12A
Sorties à relais bornes 2-3 et 5-6
Type de contact 1 NO
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Courant maximum sur la borne 2.2 12A
Sorties à relais bornes 7-8
Type de contact 1 NO
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Sorties à relais bornes 9-10-11 et 12-13-14
Type de contact 1 contact NO/NF
8A sur AC1 250V - B300
Portée nominale contact
30Vcc 1A Service auxiliaire
Lignes de communication
Vitesse de transmission de 1200…38400 bauds
Interface série RS232
Connexion par l’intermédiaire du connecteur RJ6/6
Interface série RS485 Isolée avec vitesse de transmission programmable 1200…38400
(261 94 uniquement) bauds. Connexion par l’intermédiaire de bornes extractibles
Isolation
Tension nominale d’isolation (Ui) 690V
Conditions ambiantes de fonctionnement
Température d’utilisation -20…+60°C
Température de stockage -30…+80°C
Humidité relative <90%
Pollution ambiante maximum Degré 3
Catégorie de surtension 3
Branchements
Type de bornes Extractibles
Section des conducteurs (min. et max.) 0,2…2,5 mm 2 (24÷12 AWG)
Couple de serrage 0,5 Nm (4,5 LBin)
Boîtier
Matériau Thermoplastique LEXAN 3412R
Type Encastré
Dimensions L x H x P 144 x 144 x 94mm
Degré de protection IP41 sur partie frontale, IP20 sur partie arrière
Poids 950g
Références normatives
IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3,
IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95
26
Electronic
Control Box
Item 261 93 – Item 261 94
October 08
Y1958C
Contents
1. General features . . . . . . . . . . . . . . . . . . 30
1.1 Versions . . ... . . . . . . . . . . . . . . . . . . . . . 30
1.2 Description ... . . . . . . . . . . . . . . . . . . . . . 30
1.3 Applications .. . . . . . . . . . . . . . . . . . . . . . 30
1.4 Installation . ... . . . . . . . . . . . . . . . . . . . . . 30
1.5 Supply . . . ... . . . . . . . . . . . . . . . . . . . . . 30
3. Operating mode . . . . . . . . . . . . . . . . . . . 34
3.1 Reset mode (red LED of RESET key) . . . . . . . . 34
3.2 Manual mode (red LED of MAN key) . . . . . . 35
3.3 Automatic mode (red LED of AUT key) . . . . . . 35
3.4 Off-load test mode (without load) . . . . . . . . . . 35
3.5 On-load test mode (under load) . . . . . . . . . . . 35
4. Applications . . . . . . . . . . . . . . . . . . . . . . 36
4.1 Utility-to-generator Application . . . . . . . . . . . 36
4.2 Utility-to-utility Application . . . . . . . . . . . . . . . 36
6. Voltage controls . . . . . . . . . . . . . . . . . . . 39
7. Programming . . . . . . . . . . . . . . . . . . . . . 41
7.1 Setting the parameters . . . . . . . . . . . . . . . . . 41
7.2 Table of menus . . . . . . . . . . . . . . . . . . . . . . 42
7.3 P0 menu - Nominal data . . . . . . . . . . . . . . . 42
7.4 P1 menu - General data . . . . . . . . . . . . . . . 43
7.5 P2 menu - Main line voltage control . . . . . . . 44
7.6 P3 menu - Secondary line voltage control . . . . 45
7.7 P4 menu - Programmable inputs . . . . . . . . . . . 46
7.8 P5 menu - Programmable outputs . . . . . . . . . 46
7.9 P6 menu - Serial communication . . . . . . . . . . 47
8. Diagnostic messages . . . . . . . . . . . . . . . 48
9. Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10. Connections . . . . . . . . . . . . . . . . . . . . . . 51
29
1. General features
1.1 Versions
• 261 93 - Standard version • 261 94 - Evoluted version + interface RS-485
1.2 Description
• Electronic Control Box - microprocessor • 8-key membrane keypad
• Two inputs of three-phase voltage measurement • RS-232 serial interface for set-up, remote control
• Power supply DC 12-24-48 VDC and supervision
• Power supply AC 220-240 VAC • RS-485 opto-isolated interface for MODBUS pro-
tocol (261 94)
• 2 LED displays, 3 digits 7 segments
• 2 programmable digital inputs
• 20 status and measurement LED indicators
• 3 programmable relay outputs (1NO + 2 C/O)
1.3 Applications
• Changeover between utility-to-utility, utility-to- • L-L voltage (or L-N voltage in case of monophase
generator lines)
• Control of motorized circuit breakers, motorized • Controls on minimum voltage, maximum voltage,
switches phase loss, asymmetry, minimum frequency, max-
• Start/stop generator imum frequency, with independent enabling and
delay
• Three-phase, two-phase or single-phase voltage
controls • Voltage thresholds with programmable hysteresis
1.4 Installation
• Install the electronic control box according to the • Set the parameters according to the required
wiring diagrams shown in the last pages of the wiring diagram, paying special attention when
manual programming the inputs / outputs
• Use the right wiring diagram for the application
1.5 Supply
• 261 93 and 261 94 have a double power sup- • In presence of both power supplies, the energy is
ply circuit, that means that they can operate with taken from the AC source
both AC and DC supply or with only one of the
two indifferently
30
2. Description of the front panel
A B
C D
31
2.2 Measurement selection
• When the key located under each display (A) and • After 1 minute without touching the key, the meas-
(B) is pressed several times, it will be possible to view urement returns to the default measurement, which
the various measurements of the line sequentially. may be the first voltage line-to-line or the first volt-
• Line-to-line voltages, line-to-neutral voltages (in case age line-to-neutral, depending on how the voltage
of single-phase lines) are available for each line. control is set up.
• The combinations of the red LEDs indicate which • In case of alarms or messages, the display will be
measurement is selected. The list of measurements occupied by the alarm code.
may change depending on whether the electronic By pressing the selection key, it is possible to
control box is set up for the three-phase, two-phase temporarily hide the alarm and access the meas-
or single-phase control. urements.
2.3 LEDs
• The front panel has some LEDs which indicate the status of the circuit breakers controlled by the electronic
control box.
32
• The following table describes the meaning of the various LEDs.
Some of them are bicolor and have a different meaning according to the color.
✱ If the auxiliary contacts have been connected, the LED will represent the status of the circuit breakers, otherwise it will
remain off.
✱✱ If the contacts have been connected properly, the LED will represent the status of the circuit breakers, otherwise the
LEDs will remain off.
33
3. Operating mode
• The four keys SET / AUT / MAN / RESET can • If the LED indicating the selected operating mode
be used to select the required operating mode, flashes, it means that the device is communicating
which will be indicated when the corresponding through the serial interface and that it could exe-
red LED lights up. cute remote commands, including the mode
change as well.
A B
C D
34
3.2 Manual mode (red MAN key LED)
• The manual mode allows the operator to electrical- interlocking time and then it will close the required
ly open/close the circuit breakers with the special circuit breaker.
keys located at the front side of the device. • In manual mode, all the status alarms of the circuit
• In this mode, the voltages are constantly monitored breakers (disconnected and tripped) are disabled.
but the device just displays their status. The anomalous condition is signaled on the LED
• When one of the control keys is pressed for at but it will not be stored or dealt with as an alarm.
least 300 ms, the electronic control box changes • It is possible to manually control the startup and
the status of the circuit breakers from open to shutdown of the generator by holding down the
closed and vice-versa. key (G) MAN for 5 consecutive seconds. As long
• If a command is given to close a circuit breaker as the manual mode is kept, the status of the gen-
while the other is already closed, the unit will ini- erator will remain the one required.
tially open the other circuit breaker, wait for the
35
4. Applications
36
5. Circuit breakers control
• The circuit breakers control is carried out through • In case of an anomaly on the switch, hence caus-
two separate relays, one for closing and one for ing an alarm, the control outputs will both be
opening. opened till the resetting of the alarm.
• In reset mode, both control relays remain open, • There are two separate modes for controlling the
except for the emergency condition where the circuit breakers. These can be selected by using
opening can be controlled. the parameter P1.03
3 1s
Example of a changeover with feedback, 1 15 s
assuming a utility-to-utility commutation. 15
The feedback input status is shown 0.5 s 0.5 s
in blue. The status of the control outputs 6 1s
is shown in green. The changeover time 4 15 s
is shown in yellow. 18
37
5.2 Without feedback
• The circuit breakers status LEDs remain off. • The changeover times between the opening of
• The timeout alarms are disabled. a switch and the closing of another start during
the commutation of the outputs and are steady
• The Opening/Closing control outputs remain
at 6 sec.
The auxiliary constantly in the required position for the circuit
contacts of the breaker.
circuit breakers
are not wired in
their inputs,
hence the
electronic
control box is
not informed on
their actual
state.
LED VMAIN OK
LED VSEC. OK
3
Example of a changeover with no 1
feedback. The actual status of the circuit INT. MAIN
breakers is shown in blue. The status 6 sec 6 sec
of the control outputs is shown in green. 6
The changeover time is shown 4
in yellow. INT. SEC.
38
6. Voltage controls
39
• Each anomaly has an independent delay time. tance between these two thresholds determines the
The anomaly must last consecutively longer than hysteresis. For instance, it may be considered that
the time specified for invalidating the voltage pres- when the nominal value is below 80%, the voltage
ence signal. may no longer be useable and that in order to be
• All controls, except for the minimum voltage con- considered useful, it must rise over 85%, thereby
trol, can be excluded separately by setting the determining a 5% hysteresis.
related parameter to OFF. The same concept applies to the maximum
• The minimum and maximum voltage limits are voltage.
specified by setting up two thresholds each, one • As for the frequency thresholds, there is a fixed 1%
which determines the point beyond which the volt- hysteresis of the nominal frequency.
age is no longer considered acceptable (e.g. • The retrieval after a phase failure occurs when the
P2.01) and the other, closer to the nominal volt- voltage rises above the minimum voltage retrieval
age, which determines the point in which it threshold.
becomes compatible again (e.g. P2.02). The dis-
P2.04
P2.05
Example of variation of the main line
voltage within the minimum and V MAIN
maximum thresholds and relative
hystereses, with indication of the P2.02
presence / absence delay times. The P2.01
example considers the secondary line
voltage absent with its circuit breaker
open, hence the changeover times are LED VOK
not shown. The INTERR. bar P2.03 P2.15 < P2.06 P2.05 P2.15
represents the required status
INTERR.
of the main line switch.
40
7. Programming
Key A Key B
It moves - Enable modification
at same level - Confirms setup
Key E
- Goes to Setup
- Exits to higher level
Key F
Increases parameter value
Key G
Decreases parameter value
Key H
Goes to lower level
41
7.2 Table of menus
Menu Description
P0 System nominal data
P1 General Data
P2 Main line voltage control
P3 Secondary line voltage control
P4 Programmable inputs
P5 Programmable outputs
P6 Communication port
42
7.4 P1 menu - General data
Setup Description Range Default
U-G = Utility-to-Generator
P1.01 Type of application U-G
U-U = Utility-to-Utility
The highlighted OFF - Disabled
OFF
parameters are P1.02 Control of phase sequence 123 - Direct
included only in 321 - Opposite
version 261 94 FEE - With feedback
P1.03 Changeover control FEE
NOF - Without feedback
P1.04 Circuit breakers Timeout OFF / 1…900s 5s
OFF (Control disabled)
P1.05 Enable control of withdrawn OFF
ON (Control enabled)
P1.06 Maximum time load not powered (A07 alarm delay) OFF / 1…3600s OFF
P1.07 Startup delay time, generator 0 …. 900 s 1s
P1.08 Cooling time, generator 1…3600s 120 s
P1.09 Minimum battery voltage threshold OFF / 70…100% 75%
P1.10 Maximum battery voltage threshold OFF / 110…140% 130%
P1.11 Battery threshold delay time 0…60 s 10 s
43
7.5 P2 menu - Main line voltage control
Setup Description Range Default
P2.01 Minimum voltage threshold - release 70…98% Ue 85% Ue
P2.02 Minimum voltage threshold - retrieval 75…100% Ue 90% Ue
The highlighted
parameters are P2.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
included only in P2.04 Maximum voltage threshold - release 102…120% Ue / OFF 115% Ue
version 261 94
P2.05 Maximum voltage threshold - retrieval 100…115% Ue 110% Ue
P2.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P2.07 Threshold of phase failure 60 … 85% Ue / OFF 70% Ue
P2.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
P2.09 Voltage unbalance threshold 1 … 20% Ue / OFF 10 %
P2.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
P2.11 Threshold of minimum frequency OFF / 80… 100% Fe 95% Fe
P2.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
P2.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105% Fe
P2.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
Voltage return delay on main line within
P2.15 1 … 3600 s 10 s
the limits (when circuit breaker secondary line open)
Voltage return delay on main line within the limits
P2.16 1 … 3600 s 60 s
(when load on secondary line)
P2.01 - P2.02 - P2.03 - The first two parameters determine the minimum voltage threshold and its hysteresis when
retrieved. P2.02 cannot be set to a value which is lower than P2.01. P2.03 determines the delay time for the activation
of this protection. See chapter on Voltage controls
P2.04 - P2.05 - P2.06 - The first two parameters determine the maximum voltage threshold and its hysteresis when
retrieved. P2.05 cannot be set to a value which is higher than P2.04. Setting P2.04 to OFF will disable the maximum
voltage control. P2.06 determines the maximum voltage tripping delay. See chapter on Voltage controls
P2.07 - P2.08 - Voltage threshold under which there is an activation due to phase failure, usually faster than the
reduction. The delay time for the phase failure is specified by P2.08
P2.09 - P2.10 - P2.09 determines the maximum unbalance threshold between the phases, referred to the nominal
voltage; P2.10 determines the relative tripping delay.
This control can be disabled by setting P2.09 to OFF
P2.11 - P2.12 - Threshold (disabled) and minimum frequency tripping delay
P2.13 - P2.14 - Threshold (disabled) and maximum frequency tripping delay
P2.15 - Return delay time on main line within the limits, used when the source of the secondary line is not available.
Normally shorter than P2.16: since the load is not powered, it is necessary to supply voltage
P2.16 - Return delay time on main line within the limits, used when the load can be connected to the secondary line.
Normally longer than P2.15: since the load is “covered”, it is possible to wait longer before considering the voltage
stably retrieved
44
7.6 P3 menu - Secondary line voltage control
Setup Description Range Default
P3.01 Minimum voltage threshold - release 70…98 % Ue 85 % Ue
P3.02 Minimum voltage threshold - retrieval 75…100 % Ue 90 % Ue
The highlighted
parameters are P3.03 Minimum voltage threshold delay 0.1 …. 900 s 1.0 s
included only in P3.04 Maximum voltage threshold - release 102…120 % Ue / OFF 115 % Ue
version 261 94
P3.05 Maximum voltage threshold - retrieval 100…115 % Ue 110 % Ue
P3.06 Maximum voltage threshold delay 0.1 …. 900 s 1.0 s
P3.07 Threshold of phase failure 60 … 85% Ue / OFF 70 % Ue
P3.08 Phase failure threshold delay 0.1 … 30.0 s 0.1 s
Note: For
explanations P3.09 Voltage unbalance threshold 1 … 20 % / OFF 10 %
on the opera- P3.10 Voltage unbalance threshold delay 0.1 … 900 s 5.0 s
tion of
parameters, P3.11 Threshold of minimum frequency 99 … 80 % Fe / OFF 95 % Fe
see previous P3.12 Minimum frequency threshold delay 0.1 … 900 s 5.0 s
page con-
cerning the P3.13 Threshold of maximum frequency 101 … 120% Fe / OFF 105 % Fe
main line P3.14 Maximum frequency threshold delay 0.1 … 900 s 3.0 s
menu.
P3.15 Voltage delay of secondary line within the limits 1 … 3600 s 20 s
45
7.7 P4 menu - Programmable inputs
Setup Description Range Default
For
P4.01 Programmable input function 1 Forced changeover
See list ìP rogrammable on secondary line
input functions” In.r
P4.02 Programmable input function 2 Inhibition return
on main line
46
Programmable output functions
Function Description Notes
OFF OFF Output not used
When closed, the generator must be inactive.
S.GE Consent to start up the generator Contact opens to start generator.
If the unit is not powered, the generator starts
Indicates unit automatically and without alarms, ready to
RDY Automatic transfer switch ready
start operating
ALA Global alarm De-energizes in case of an alarm
Minimum coil
MCM Main line switch voltage minimum opening coil command
Main line
Minimum coil Secondary line switch voltage minimum opening coil
MCS
Secondary line command
Disconnection of the non-priority loads that are not powered
by the secondary line branch.
It is also controlled on the secondary line.
L.SH Non-priority load disconnection
Contact which is closed before the secondary line closing
command and opened before the main line closing
command
P6.01…P6.04 - They determine the transmission format and the protocol used on communication port RS-232
P6.05…P6.08 - They determine the transmission format and the protocol used on communication port RS-485,
available only on 261 94
47
8. Diagnostic messages
Code Description
(Dashes) - The interlocking time is in progress.
- - -
They are displayed from the side in which the load is being transferred
Sta (Start) - Indicates that the Start Generator command has been sent
Coo (Cooling) - Indicates that the generator is being left running for the cooling
(Test) - When steady, it indicates that an off-load test - namely a power unit test with the voltage controls
Tes
active - is currently in progress
(Test) - When flashing, it indicates that an on-load test, namely an automatic net failure simulation, is
Tes
currently in progress
Loc (Locked) - It indicates that the keyboard function one is trying to execute is locked
48
9. Alarms
• When the unit is running, it is possible to verify a • The Global alarm relay output is de-energized dur-
number of abnormal situations which are signaled ing alarm conditions whereas it is energized under
in different ways. normal conditions. If the unit does not operate due
• Some alarms (tripped, withdrawn) have a dedi- to a failure or power supply problems, it will gen-
cated LED which begins to flash when the erate an alarm condition on its contact.
alarms go on. • Some alarms are automatically reset when the
• Other alarms are signaled through a code which conditions generating them fail to work.
consists of an A (alarm) and a number indicating • Other alarms, described in the chart in the RIT col-
which alarm it is. This code will be flashing on one umn, are retentive, thus they are stored.
of the displays. If the code refers to the main line • Once the alarm has been stored, the abnormal
branch, the alarm will be displayed on the left. conditions must be eliminated in order to be reset.
Conversely, if the code refers to the secondary line Also, the operator must press the RESET key or
branch or if it is a generic alarm (e.g. battery), it send a special message via the serial interface.
will be displayed on the right.
• When an alarm goes on, the red LED “ALARM”
flashes in sync with the dedicated LED or with the
alarm code.
49
Alarm list
Description
Code Led Causes RIT RESET MAN AUT
alarm
This occurs if the P0.06 parameter is OFF and if the battery
Battery voltage
A01 voltage measured remains lower than the threshold % set YES YES YES YES
The highlighted too low
with P1.09 for the time set with P1.11
alarm are
This occurs if the P0.06 parameter is not OFF and if the
included only in Battery voltage
A02 battery voltage measured remains higher than the threshold YES YES YES YES
version 261 94 too high
% set with P1.10 for the time set with P1.11
It is generated if the main line switch does not move to the
position controlled by the unit within the time determined
Main line by P1.04 or if it comes out of the required position on its
A03 YES NO NO YES
switch timeout own. The alarm can be generated when closing and when
opening. If there is no power on both lines, the alarm will
not be generated
It is generated if the secondary line switch does not move to
the position controlled by the unit within the time determined
Secondary line by P1.04 or if it comes out of the required position on its
A04 YES NO NO YES
switch timeout own. The alarm can be generated when closing and when
opening. If there is no power on both lines, the alarm will
not be generated
If enabled by parameter P1.02, it is generated when a
phase sequence – different from what has been specified in
Main line incorrect
A05 P1.02 – is detected, after a delay of about 500 ms. YES YES YES YES
phase sequence
In order for the sequence to be detected, all three phases
must be > 50VAC
Secondary line
A06 incorrect phase As the previous, referred to the secondary line voltage YES YES YES YES
sequence
The load was left with no voltage for a period of time longer
Timeout load than P1.06.
A07 NO NO NO YES
not powered The main line and the secondary line were not available (no
power or switch not closed)
Generator One of the programmable inputs is set to “Generator ready”,
A08 NO YES YES YES
not available hence signaling that the generator is not available
One of the programmable inputs is set to the emergency
A09 Emergency YES YES YES YES
button and the corresponding input contact is open
Main line
The frequency of the main line is not within the limits
A11 frequency NO YES YES YES
determined with P2.11 and P2.13
outside limits
Secondary line
The frequency of the secondary line is not within the limits
A12 frequency NO YES YES YES
determined with P3.11 and P3.13
outside limits
The difference between the higher and lower voltage
Main line voltage
A13 between lines of the main line exceeds the limit determined NO YES YES YES
asymmetry
with P2.09
The difference between the higher and lower voltage
Secondary line
A14 between lines of the secondary line exceeds the limit NO YES YES YES
voltage asymmetry
determined with P3.09
Main/secondary The withdrawn input control is enabled by parameter P1.05
• line withdrawn. and the corresponding main line or secondary line input YES VIS VIS YES
Switch removed contact is open
Main/secondary The tripped input contact it is closed.
line tripped. This condition is ignored for 15 seconds which begins
• YES VIS VIS YES
Protection immediately after giving the command to open a switch so
activation. Switch as to avoid false signalings when using a release coil
50
10. Connections
51
11. Technical features
52
Schéma
Wiring diagram
P0.05 24
Principal Secondaire
Main Sec
ref. 04055
Moteurs
Motors
23 24 25 26 27
0V~
Commun entrées
Com digital inputs
220-240V~
+ -
53
Schéma
Wiring diagram
P1.04 OFF
Principal Secondaire
Main Sec
3A 3A
ref. 04055
23 24 25 26 27
Commun entrées
Com digital inputs
220-240V~
0V~
+ -
54
Schéma
Wiring diagram
P0.03 1Ph
Principal Secondaire
Main Sec 1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
55
Schéma
Wiring diagram
P0.03 1Ph
Principal Secondaire
Main Sec 1A
1A
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
56
Schéma
Wiring diagram
P0.03 2Ph
Principal Secondaire
Main Sec. 1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
57
Schéma
Wiring diagram
P0.03 2Ph
Principal Secondaire
Main Sec. 1A
1A
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
58
Schéma
Wiring diagram
P0.03 3Ph
Principal Secondaire
Main Sec 1A gG
1A gG
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
59
Schéma
Wiring diagram
P0.03 3Ph
Principal Secondaire
Main Sec 1A
1A
N L1 L2 L3 N L1 L2 L3
PRINCIPAL SECONDAIRE
MAIN SEC.
RELEVE DE TENSION
VOLTAGE INPUTS
60
P1.04
P1.03
P1.05
Alimentation
Parameter
Paramètre
Schéma
électrique des
moteurs
Tension
electric motors
OFF
OFF
NOF
Setting
Wiring diagram
Programmation
Red
Red
Black
Black
1 2 1 2
DPX 125/160 sans feedback
Moteur Moteur
DPX 125/160 without feedback
normal secours
Parameter setting for the wiring diagram in picture:
Blue
Blue
Violet
Violet
Orange
Orange
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
61
réf: 261 93/94
62
P1.03
P1.05
Alimentation
Parameter
Paramètre
Schéma
électrique des
moteurs
12-Red
12-Red
14-White
14-White
Tension CA Principal CA Secondaire
Aux. main Aux. Sec.
electric motors
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
Programmation
52-White
52-White
54-Red
54-Red
SD Principal SD Secondaire
Red
Red
Black
Black
Trip Trip
main sec.
1 2 1 2
DPX 125/160 with feedback
DPX 125/160 avec feedback
51-Black
51-Black
Moteur Moteur
principal secondaire
Parameter setting for the wiring diagram in picture:
Blue
Blue
Violet
Violet
Orange
Orange
2-Red
3-White
2-Red
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
P1.03
P1.05
Alimentation
Parameter
Paramètre
Schéma
électrique des
12-Red
14-White
moteurs
12-Red
14-White
Tension CA Principal CA Secondaire
electric motors Feedback Feedback
main Sec.
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
Programmation
52-White
54-Red
52-White
54-Red
Red
Red
Black
Black
SD Principal SD Secondaire
Trip Trip
1 2 1 2 main sec.
51-Black
51-Black
Moteur Moteur
principal secondaire
Parameter setting for the wiring diagram in picture:
3 4 5 3 4 5
DPX 125/160 with EJP and feedback
Blue
Blue
Violet
Violet
Orange
Orange
2-Red
3-White
2-Red
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
63
réf: 261 93/94
64
Alimentation
P1.04
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
electric motors
OFF
OFF
NOF
Setting
Wiring diagram
Bl
Bl
Rd
Wh
Rd
Wh
2 4 6 2 4 6
1 3 5 1 3 5
Bl
Bl
Rd
Wh
Rd
Wh
DPX 250/630 without feedback
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
66
Alimentation
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
electric motors
12-Red
12-Red
14-White
14-White
CA Principal CA Secondaire
Aux. main Aux. Sec.
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
Bl
Bl
Rd
Wh
Rd
Wh
2 4 6 2 4 6
C1
C1
54-Red
54-Red
52-White
52-White
Principal principal Secondaire secondaire
Main Sec SD Principal SD Secondaire
Main motor Sec. motor Trip Trip
main sec.
C2
C2
51-Black
51-Black
1 3 5 1 3 5
Bl
Bl
Rd
Wh
Rd
Wh
Parameter setting for the wiring diagram in picture:
2-Red
2-Red
3-White
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.
1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:
DPX 250/630 with EJP + feedback + shunt trip
DPX 250/630 avec EJP + feedback + declencheur EM
EJP
LG15
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
Alimentation
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
electric motors
12-Red
12-Red
14-White
14-White
CA Principal CA Secondaire
Aux. main Aux. Sec.
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
Bl
Bl
Rd
Rd
Wh
Wh
2 4 6 2 4 6
Programmation
C1
C1
Moteur Moteur
54-Red
54-Red
52-White
52-White
Principal principal Secondaire secondaire SD Principal SD Secondaire
Main Main motor Sec Sec. motor Trip Trip
main sec.
C2
C2
51-Black
51-Black
1 3 5 1 3 5
Bl
Bl
Rd
Wh
Rd
Wh
Parameter setting for the wiring diagram in picture:
2-Red
2-Red
3-White
3-White
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.
1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:
Arrêt
d’urgence
Emergency
DPX 250/630 with feedback + shunt trip + emergency stop
stop
DPX 250/630 avec feedback + declencheur EM + arrêt d’urgence
LG16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
67
réf: 261 93/94
68
Alimentation
P1.04
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
electric motors
OFF
OFF
NOF
Setting
Wiring diagram
1 3 5 7 1 3 5 7
2 4 6 8 2 4 6 8
Parameter setting for the wiring diagram in picture:
Programmation des paramètres pour le schéma représenté sur la figure:
LG17
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
70
Alimentation
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
14-White
14-White
electric motors
12-Red
12-Red
CA Normal CA Secours
Feedback Feedback
main Sec.
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
1 3 5 7 1 3 5 7
Programmation
C1
C1
Moteur Moteur
54-Red
54-Red
52-White
52-White
Principal principal Secondaire secondaire
Main Sec SD Normal SD Secours
Main motor Sec. motor Trip Trip
main sec.
C2
C2
51-Black
51-Black
2 4 6 8 2 4 6 8
Parameter setting for the wiring diagram in picture:
3-White
3-White
2-Red
2-Red
Débro normal Débro secours
Withdrawn Withdrawn
main sec.
1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:
Arrêt
d’urgence
Emergency
stop
DPX 1600 with feedback + shunt trip + emergency stop
DPX 1600 avec feedback + declencheur EM + arrêt d’urgence
LG19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
réf: 261 93/94
Alimentation
P1.03
P1.05
électrique des
moteurs
Parameter
Paramètre
Schéma
Tension
14-White
12-Red
14-White
electric motors
12-Red
CA Principal CA Secondaire
Aux. main Aux. Sec.
11-Black
11-Black
FEE
ON
Setting
Wiring diagram
1 3 5 7 1 3 5 7
Programmation
C1
C1
Moteur Moteur
54-Red
52-White
52-White
54-Red
Principal principal Secondaire secondaire
Main Sec SD Principal
Main motor SD Secondaire
Sec. motor Trip
Trip
main
sec.
C2
C2
51-Black
51-Black
2 4 6 8 2 4 6 8
DPX 1600 with EJP + feedback
DPX 1600 avec EJP + feedback
3-White
3-White
2-Red
2-Red
Débro principal Débro secondaire
Withdrawn Withdrawn
main sec.
1-Black
1-Black
Programmation des paramètres pour le schéma représenté sur la figure:
EJP
LG20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 N L1 L2 L3 N L1 L2 L3
+ - PRINCIPAL SECONDAIRE
0V~
Trip sec.
Aux. sec.
Trip main
MAIN SEC.
Aux. main
SD normal
CA normal
SD secours
CA secours
Input prog. 1
Input prog. 2
Entrée prog. 2
Entrée prog. 1
Withdrawn sec.
Withdrawn main
220-240V~
Ouverture Com Fermeture Ouverture Com Fermeture RELAIS PROG. RELAIS RELAIS ENTREES DIGITALES ALIM. AUX. ALIM. AUX. RELEVE DE TENSION
Opening Com Closing Opening Com Closing
1 PROGRAMMABLE 2 PROGRAMMABLE 3 DIGITAL INPUTS DC AC VOLTAGE INPUTS
RELAIS NORMAL RELAIS SECOURS PROG. 1 PROG. 2 RELAY PROG. 3 RELAY DC AUX AC AUX
MAIN RELAY SEC. RELAY RELAY SUPPLY SUPPLY 100-690 Vac 50/60Hz
BOÎTIER D’AUTOMATISME
ELECTRONIC CONTROL BOX
71
réf: 261 93/94
Schéma
Wiring diagram
P5.02 MCM
P5.03 MCS
P1.03 FEE
Arrêt
d’urgence
Emergency
stop
9 10 11 12 13 14
RELAIS RELAIS
PROGRAMMABLE 2 PROGRAMMABLE 3
PROG. 2 RELAY PROG. 3 RELAY
72
Programmation des paramètres
Setting of parameters
Valeur Valeur
Setup Setup
Value Value
P0.01 P3.01
P0.02 P3.02
P0.03 P3.03
P0.04 P3.04
P0.05 P3.05
P1.01 P3.06
P1.02 P3.07
P1.03 P3.08
P1.04 P3.09
P1.05 P3.10
P1.06 P3.11
P1.07 P3.12
P1.08 P3.13
P1.09 P3.14
P1.10 P3.15
P1.11 P4.01
P2.01 P4.02
P2.02 P5.01
P2.03 P5.02
P2.04 P5.03
P2.05 P6.01
P2.06 P6.02
P2.07 P6.03
P2.08 P6.04
P2.09 P6.05
P2.10 P6.06
P2.11 P6.07
P2.12 P6.08
P2.13
P2.14
P2.15
P2.16
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
73