DELTA VF
SOMMAIRE
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
0 MIN-C 20 Min Doortime Car:
0 (0.1) 25.5 s
1 MAX-C 40 Max Doortime Car:
0 (0.1) 25.5 s
2 MIN-H 40 Min Doortime Car:
0 (0.1) 25.5 s
3 MAX-H 60 Max Doortime Hall:
0 (0.1) 25.5 s
4 DHB-T 120 DHB Doortime:
0 (1) 255 s
5 CPR-T 20 Car Call Preference:
0 (0.1) 25.5 s
6 TOP 7 Top Position:
0 (1) 53
7 LOBBY 1 Lobby Position:
0 (1) 53
8 BOTTOM 0 Bottom Position:
0 (1) 53
9 ARD 255 Automatic Return:
0 (1) 53 ARD
else XARD
10 EPO 255 Type of EPO
0 (1) 53 EPO A/C,
54 EPO B/D,
else XEPO
11 EPO-DC 0 Door closing after EPO A/B:
0 (1) 255 s,
0 XDC,
else time until door closes
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
12 EFO-P 255 EFO/EFS Landing:
0 (1) 53 EFO/EFS
else XEFO/EFS
13 EFS 0 Type of EFS:
0 EFO,
1 EFS 1 (Aut.),
2 EFS 2 (Man.),
3 ANSI (USA),
4 British Standard,
5 Swiss Standard,
6 Australia,
7 New Zealand,
8 EFS 2 (Man. with ESK Switch),
14 ASL-P 255 Alternate Service Landing for EFO/EFS:
0 (1) 53,
else same as EFO
15 EN-ESB 0 Emerg. Stop Button:
0 XESB,
1 ESB
16 EN-PMO 0 Monitor Doortime:
0 XPMO,
1 PMO
17 EN-NDG 0 Nudging:
0 XNDG,
1 NDG
18 CTL-P 255 CTL Position:
0 (1) 53 CTL
else XCTL
19 ISC 255 Independent Service:
0 Stat on CCB,
1 Start on DCB,
2 Start on ISD/ISU,
3 NAO (USA)
20 EN-EPS 0 Express Priority Service:
0 EHS,
1 EPS
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
21 EN-SFR 0 Signal Flicker Operation:
0 XSFR,
1 SFR
22 PI 0 Type of Pos. Indic.:
0 7/16 Seg. HPI/CPI
1 7/16 Seg. HPI Multilight CPI,
2 Multilight HPI 7/16 Seg. CPI,
3 Multilight HPI/CPI
23 RCB-NO 1 Car Identifier in Group:
0 - 8 valid,
else invalid
24 GROUP 1 Number of cars in Group:
0 - 8 valid,
else invalid
25 PARK-1 1 Perf. park pos for 1 car:
0 (1) 53 enabled,
else disabled
26 PARK-2 255 Perf. park pos for 2 car:
0 (1) 53 enabled,
else disabled
27 PARK-3 255 Perf. park pos for 3 car:
0 (1) 53 enabled,
else disabled
28 PARK-4 255 Perf. park pos for 4 car:
0 (1) 53 enabled,
else disabled
29 PARK-5 255 Perf. park pos for 5 car:
0 (1) 53 enabled,
else disabled
30 PARK-6 255 Perf. park pos for 6 car:
0 (1) 53 enabled,
else disabled
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
31 PARK-7 255 Perf. park pos for 7 car:
0 (1) 53 enabled,
else disabled
32 PARK-8 255 Perf. park pos for 8 car:
0 (1) 53 enabled,
else disabled
33 LDR 255 Limited Door Reversal:
0 full DOB full EDP full LRD,
1 full DOB lim. EDP full LRD,
2 full DOB lim. EDP lim. LRD,
else like 1
34 DCP-T 50 Delayed Car Protection:
0 (1) 255 s,
35 PKS-P 255 PKS Position:
0 (1) 53 enabled,
else disabled
36 EFO-DC 0 Door Closing at EFO-Landing:
0 (1) 255 s,
0 XDC,
else time until door closes
37 LOB-NT 40 Lobby Door Time:
0 (0.1) 25.5 s,
38 ANS 3 Ans:
0 XANS,
else number of calls to trigger ANS
39 EN-DDO 0 Double Door Operation:
0 XDDO,
else DDO
40 TPOS-1 255 Test Position 1:
0 (1) 53 Target landing 1 if car idle,
else disabled
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
41 TPOS-2 255 Test Position 2:
0 (1) 53 Target landing 2 if car idle,
else disabled
42 TDELAY 255 Test Delay:
0 (1) 255 s idle Time at landing,
only if TPOS1 or TPOS2 set
43 LR-T 20 LR-Timout:
0 (1) 255 s,
44 CFT-P 255 Cafeteria Position:
0 (1) 53 enabled,
else disabled
45 CFT-NT 40 Cafeteria Doortime:
0 (0.1) 25.5 s,
46 CNL 1 Cars Parking in Lobby:
0 (1) 8 Cars
47 MIT-ST 0 MIT Startdelay:
0 (1) 255 s
48 MIT-T 0 MIT Timeout:
0 (1) 255 s
49 EN-NLB 0 No Lobby Bypass:
0 disable,
else enabled
50 MIT-LD 0 MIT Load Welghing Default:
0 (1) 4
51 MIT-VD 0 MIT Variable Interval Dispatch:
0 (1) 255 s
52 DURK-P 0 Dual Up Peak Border Position:
0 (1) 53
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
53 DUPK-G 0 Dual Up Peak Group:
0 - 1
54 MOT-T 0 MOT Timeout:
0 (1) 255 s
55 EN-UCB 0 Up Call Bypass:
0 disabled,
else enabled
56 EN-HLC 0 Enable Hall Lantern:
0 gong on hall calls,
1 gong on car and hall calls
57 IST-P 255 Enable Intermittent Stop:
0 (1) 53 enabled,
else disabled
58 EN-CK 0 Enable Cancel Doortime:
0 disabled,
else cancel doortime with ccb
59 ATT 0 ATT Type:
0 start with dcb/rdcb,
1 start with isd/isu (attu/attd),
2 NAO (USA)
60 NDG-T 20 Nudging Time:
0 (1) 255 s
61 DTC-T 50 Door Time Protection Closing:
0 (1) 255 s
62 DTO-T 20 Door Time Protection Opening:
0 (1) 255 s
63 EN-SHB 0 Enable Separate Hall-Buttons:
0 normal Hall Button Operation,
else rear Hall Button as front Button
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
64 HL-SET 0 Hall Lantern Setup:
0 Lantern/Gong on different Pins,
1 Lantern/Gong on same Pins,
2 Lantern/Gong for JICA Operation,
65 EN-CRO 0 Enable Card Reader Operation:
0 disabled,
1 single contact reader,
2 Australian Card Key Sec type 2,
3 Australian Card Key Sec type 1,
4 Multi Contact Reader
66 GCBTYP 0 General Control of Buttons Type:
0 XGCB,
1 GCB-1,
2 GCB-2,
67 RIOT-P 255 RIOT position (for car riot operation):
0 (1) 53 riot target landing
68 MG-TIM 0 Motor Generator Time:
0 no power down,
1 (1) 255 s time until power down
69 SPB-NT 0 Special Button Door Time:
0 (0.1) 25.5 s
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
74 AMF-P 0 Above Mid Shaft Position:
0 (1) valid position
75 EN-PKS 0 Enable Parking Shutoff Type:
0 ETO,
1 NAO
76 PKS-T 0 Parking Shutoff Time:
0 (1) 255 s untel door closes
77 EN-CTL 0 Enable Car To Lobby Type:
0 ETO,
1 NAO
78 TFS-P 0 Transfer Floor Position:
0 (1) 53 valid position,
must be within bottom and top,
else disabled
79 MG-PRF 0 Motor Generator Profile for EPO:
0 default profile,
1 reduced profile,
2 reducer profile
80 EQO 0 Earthquake Operation:
0 California,
1 New Zealand
81 CR-DIR 0 Correction Run Direction:
0 down to Bottom Pos,
1 up to Top Pos
82 WCO-T 0 Wild Car Operation Door Time:
0 (0.1) 25.5 s
83 SHO-T 0 Shabat Door Time:
0 (0.1) 25.5 s
84 SHO-LT 0 Shabat Lobby Door Time:
0 (1) 255 s
85 Speech 0 Speech Synthesizer mode:
0 Floor Msg on Car Call only,
1 Floor message on every call type
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
0 TOP 7 Top Position:
0 (1) 107
1 BOTTOM 0 Bottom Position:
0 (1) 107
2 DRIVE 1 Drive:
0 1-SP,
1 2-SP XADO,
2 G-S/D XADO,
3 G-L short XADO,
4 G-L short ADO,
5 2-SP ADO,
6 G-S/D ADO,
7 SPEC60,
8 G-D NAO XADO,
9 G-D NAO ADO,
3 SPEEP 100 Speed (fast run mode):
25,
40,
63,
100,
160,
175,
250 cm/sec
4 CR-DIR 0 Correction Run Direction:
0 down,
1 up
5 DOP-T 32 DDP Time:
0 (1) 255 s
6 3P 32 3P Time:
0 (1) 255 s
7 RLEV-T 16 Relevel Time:
0 (1) 255 s
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
8 1AT 0 1A Time:
0 (0.1) 25.5 s
9 2AT 0 2A Time:
0 (0.1) 25.5 s
10 PI 0 Type of Pos. Indic.:
0 7/16 Seg.,
1 Multil.
11 EN-SR 0 Enable Shortrise:
0 disabled,
1 enabled
12 EN-NDG 0 Enable Nudging:
0 disabled,
1 enabled
13 EN-ESB 0 Enable Emergency Stop Button:
0 disabled,
1 enabled
14 SEC-P 0 Secured Floor:
Not used
15 CONFIG 0 Soft-and Hardware configuration:
0 = ETO,
1 = NAO
50 FDOOR 2 Type of Front Doors:
0 FLH,
1 9550T & ACG,
2 9550T & TLD,
3 OVL,
4 OVL & ACG,
51 FDOR-T 0 Front Door Reversal Time:
0 (.004) 1 sec
52 MIXDOR 0 Mixed Doors:
0 same operator front and rear
1 different operators front/rear
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
53 RDOOR 2 Type of Rear Doors:
0 FLH,
1 9550T & ACG,
2 9550T & TLD,
3 OVL,
4 OVL & ACG,
54 RDOR-T 0 Rear Door Reversal Time:
0 (.004) 1 sec
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
0 MIN-C 20 Min Doortime Car:
0 (0.1) 25.5 s
1 MAX-C 40 Max Doortime Car:
0 (0.1) 25.5 s
2 MIN-H 40 Min Doortime Hall:
0 (0.1) 25.5 s
3 MAX-H 60 Max Doortime Hall:
0 (0.1) 25.5 s
4 CRP-T 20 Car Call Preference:
0 (0.1) 25.5 s
5 TOP 7 Top Position:
0 (1) 31
6 LOBBY 0 Lobby Position:
0 (1) 31
7 BOTTOM 0 Bottom Position:
0 (1) 31
8 ARD 255 Automatic Return:
0 (1) 31 ARD,
> 31 XARD
9 OPERAT 0 Operation DCL/FCL:
0 FCL,
1 DCL
10 DRIVE 1 Drive:
0 1-SP,
1 2-SP XADO,
2 G-S/D XADO,
3 G-L sr XADO,
4 G-L sr ADO,
5 2-SP ADO,
6 G-S/D ADO,
7 SPEC60,
8 G-D NAO XADO,
9 G-D NAO ADO,
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
11 1AT 0 1A Time:
0 (0.1) 25.5 s
12 2AT 0 2A Time:
0 (0.1) 25.5 s
13 DDP-T 32 DDP Time:
0 (0.1) 255 s
14 3P 32 3P Time:
0 (0.1) 255 s
15 RLEV-T 16 Relevel Time:
0 (0.1) 255 s
16 DOOR 2 Type of Doors:
0 FLH,
1 9550T & ACG,
2 9550T & TLD,
3 OVL,
4 OVL & ACG
17 EPO 255 Type of EPO (emergency power operation):
0 (1) 31 EPO A/C,
> 31 XEPO
18 EFS 0 Type of EFS (emergency firemen service):
(if EFK (ASL) connected),
0 EFO
1 EFS 1 (Aut.),
2 EFS 2 (Man.),
3 ANSI (USA),
4 British Standard,
5 Swiss Standard,
6 Australia,
7 New Zealand
19 EN-ESB 0 Enable Emergency Stop Button:
0 XESB,
1 ESB
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
20 COP 0 Must be O:
not used for this version
21 PI 0 Type of serial Pos. Indic.:
0 7/16 Seg.,
1 Multi.,
2 Australian Dot Matrix,
3 Like 2 with CUDL/CDDL
22 EFO-P 0 EFO (emerg. firemen oper.) position:
0 (1) 31
23 LOB-T 28 LOBBY preference value (2-car only):
0 (1) 255
24 EN-FPD 0 Enable FPD (fireproof doors):
0 XFPD,
1 FPD
25 CONFIG 0 General configuration:
0 = ETO,
1 = NAO
26 SPEED 100 Speed (fast run mode):
25,
40,
63,
100,
160,
175,
250 cm/sec
27 CTL-P 0 CTL (car to any landing) position:
0 (1) 31
28 PRKDST 2 Distance to initial parkrun:
0 = no parkrun,
0 (1) 31 = distance value
29 DCP-T 50 Time until DCP-mode (delayed car protection):
0 (1) 255 s
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
30 PKS-P 0 PKS (parking servive) position:
0 (1) 31
31 ASL-P 0 ASL (alternate service landing) position:
0 (1) 31
32 EPO-DC 255 EPO (emerg. power oper.) with doors closed:
0 and 255 XDC,
1 (1) 254 s DC time
33 EN-PMO 0 Enable PMO (door time monitoring):
0 XPMO,
1 PMO
34 EN-SFR 0 Enable SFR (signal flicker):
0 XSFR,
1 SFR
35 EN-NDG 0 Enable NDG (nudging):
0 XSFR,
1 SFR
36 EN-EPS 0 Enable EPS (express priority service):
0 XEPS (EHS),
1 EPS
37 GCBTYP 0 GCBTYP (generall control of buttons):
0 XGCB,
1 GCB-1
2 GCB-2
38 RIOT-P 0 RIOT position (for RIOT operation):
0 (1) 31
39 LR-T 20 FAN (LR) time:
0 (1) 255 s
40 EN-SR 0 Enable SHORTRISE (SR):
0 XSR,
1 SR
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
41 HL-SET 0 Hall LANTERN/GONG setup:
0 HL/G at same pins
1 HL/G at same 1 2/3 4,
2 HL/G at same 3 4/1 2
42 EFO-DC 255 EFO (emerg. fire serv.) with doors closed:
0 and 255 XDC,
1 (1) 254 s DC time
43 EN-TST 0 Enable engineering tests (for internal use):
0 XTST,
1 TST
44 DOR-T 0 Door reserve time:
0 (.004) 1 second
45 EN-DDO 0 Enable DDO (double door operation):
0 XDDO,
1 DDO
46 EN-SEC 0 Must be O:
not used for this version
47 CR-DIR 0 Correction fast run preferred direction:
0 down,
1 up
48 SPARE 0 Spare:
not used
49 TPOS 1 0 Test position 1 (for automatic test run):
0 (1) 31
50 TPOS 2 0 Test position 2 (for automatic test run):
0 (1) 31
51 TDELAY 0 Test delay (delay time for automatic test run):
0 (1) 255 sec
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
52 EN-HLC 0 Enable Hall Lanterns on car calls:
0 XHLC,
1 HLC,
2 HL also during door closing,
3 HLC and also during door closing,
53 HDG-T 20 Nudging Time:
0 (1) 255 s
54 DTC-T 20 Door Close Protection Time:
0 (1) 255 s
55 DTO-T 20 Door Open Protection Time:
0 (1) 255 s
56 ANS 0 ANS:
0 XANS,
else number of calls to trigger ANS
57 ATT 0 ATT Type:
0 start with dcb/rdcb,
1 start with attu/attd,
2 NAO (USA)
58 LOB-NT 40 Lobby Door Time:
0 (0.1) 25.5 s
59 CFT-P 255 Cafeteria position:
0 (1) 31 enabled,
else disabled
60 CFT-NT 40 Cafeteria Doortime:
0 (0.1) 25.5 s
61 EN-CK 0 Enable Cancel Doortime:
0 disabled,
else cancel doortime with ccb
62 DHB-T 120 DHB Doortime:
0 (1) 255 s
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
63 LDR 0 Limited Door Reversal:
0 full DOB full EDP full LRD,
1 full DOB lim. EDP full LRD,
2 full DOB lim. EDP lim. LRD,
64 ISC 0 Independant Service:
0 Start on CCB,
1 Start on DCB,
2 Start on ISD/ISU,
3 NAO (USA)
65 IST-P 255 Intermittent Stop Position:
0 (1) 31 valid stop position,
else disabled
66 EN-CRO 0 Enable Card Reader:
0 disabled,
1 single contact reader,
2 Australian Card key sec type 2,
3 Australian Card key sec type 1,
4 multi contact reader
67 SPB-NT 0 Special DOB Door Time:
0 (0.1) 25.5 s
68 AMF-P 0 Above Mid Shaft Position:
0 (1) 31 valid position
69 EN-IST 0 Enable intermittent Stop:
0 disabled,
1 enabled
70 EN-PKS 0 Enable Parking Shutoff Type:
0 ETO,
1 NAO
71 PKS-T 0 Parking Shutoff Time:
0 (1) 255 s until door closes
72 EN-CTL 0 Enable Car To Lobby Type:
0 ETO,
1 NAO
DELTA VF
VALEUR
N° SYMBOLE PAR APPLICATION
DEFAUT
73 EQO 0 Earthquake Operation Type:
0 California,
1 New Zealand
74 EN-SHB 0 Enable Seperate Hall Buttons:
0 normal Hall Button Operation
1 rear Hall Butt. as Seperate Riser
75 MG-PRF 0 Motor-Generator Profile:
Currently not used
76 MIXDOR 0 Mixed dooroperators:
0 same operators front/rear,
1 different operators front/rear
77 RDOOR 0 Type of Rear Doors:
0 FLH,
0 9550T & ACG,
0 9550T & TLD,
0 OVL,
0 OVL & ACG
78 RDOR-T 0 Rear door reserve time:
0 (.004) 1 second
79 SPEECH 0 Speech mode:
0 floor messages on CC only,
1 floor messages also on HC
80 WCO-T 0 Wild Car Door Time:
0 (0.1) 25.5 s
81 SHOT-T 0 Shabat Door Time:
0 (0.1) 25.5 s
82 SHO-LT 0 Shabat Lobby Door Time:
0 (0.1) 25.5 s
DELTA VF
RÉGLAGE
Le toit de cabine est utilisé comme une plateforme de travail ; la vitesse de déplacement
ne doit pas être supérieure à 0,4 m/s.
A ce stade du montage:
- le frein a été démonté, nettoyé et pré-réglé (levée des mâchoires et pression des ressorts),
- les réserves sur/sous cabine et sur/sous contrepoids sont réalisées de telle manière que, le
contrepoids en butée basse, la réserve sur le toit de cabine soit de 2 m minimum (madriers
sous contrepoids),
DELTA VF
b) moteur,
d) encodeur,
f) le module ERO,
Dans le contrôleur, seuls les connecteurs AMP 6 fils des circuits de sécurités, de la boîte
d’inspection et du circuit lumière sont à raccorder.
1 - Mesure d’isolement
Les mesures se font à l’aide d’un multimètre utilisé en ohmmètre sur le plus grand calibre,
l’installation hors tension (puissance/lumière).
DELTA VF
minimum 250 KΩ
Contrôle opérationnel:
MCS 312 RCB A9693D1
LCB B9693A2
MCS 310 LCB B9693A3
Contrôle moteur:
SC I/0 Interface board
CUB Contrôle board
b) Connecter les connecteurs/outils livrés avec les contrôleurs afin de pouvoir fonctionner sans
les cartes logiques.
Sur la L.C.B:
Connecteur G027BN5 sur connecteur P7
Connecteur G027BN7 sur connecteur Pl
Sur la SC I/0:
Connecteur G027BN6 sur connecteur J4
Connecteur G027BN8 entre les connecteurs J3 et J5 de la SC I/0
DELTA VF
DELTA VF
20KW x 15Ω
R.DBR =
P.moteur
17 CT
15KW 19Ω
13VTR
17CT
22KW 13Ω
18CT
h) Vérifier le pré-réglage usine de la carte logique JO 6840 PM 1 du rack VFCU 10260 W9.
Voir les tableaux pages 8 et 9 en fonction du type de moteur (la charge nominale n’a pas
d’influence).
DELTA VF
CARTE LOGIQUE VF
DELTA VF
1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s
Iu/Iw Set 6 6 6 6 UD F F F F
Iu/Iv IG 5 5 5 5 UHL L L L L
UPG/WPG 0 0 0 0 DHL L L L L
T.Gain 2 2,5 2,5 2,5 2,5 Slip set 2 off off off off
Speed F 0 0 0 0 W1 F F F F
P. Gain 5 5 5 5 W2
I. Gain 5 5 5 5 NL 0 0 0 0
Dec. time P 0 0 0 0 FL 0 0 0 0
Brk-off 2 2 2 2 MLB 0 0 0 0
Brk-on 2 2 2 2
Cavaliers sur 1U et W
DELTA VF
1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s 1.00 m/s 1.60 m/s
Iu/Iw Set 4 4 4 4 UD F F F F
Iu/Iv IG 4 4 4 4 UHL L L L L
UPG/WPG 5 5 5 5 DHL L L L L
T.Gain 1 3 3 3 3 T. Bias 1 on on on on
Speed F 0 0 0 0 W1 F F F F
P. Gain 5 5 5 5 W2
I. Gain 5 5 5 5 NL 0 0 0 0
Dec. time P 0 0 0 0 FL 0 0 0 0
Brk-off 2 2 2 2 MLB 0 0 0 0
Brk-on 2 2 2 2
Cavaliers sur 1U et W
DELTA VF
Sur la carte logique du rack VFCU, les LED + 5 V, 15 V et - 15 V doivent être allumées.
Les LED "READY" et "INS" sont allumées si le circuit des sécurités est correct et si
l’appareil est en inspection.
a) Basculer le TCI sur le toit de cabine en NORMAL afin de pouvoir faire déplacer la cabine
avec le module ERO.
b) Tester et établir les circuits nécessaires pour le bon fonctionnement du module ERO
DELTA VF
DELTA VF
DELTA VF
b) Interrupteurs et aimants
Les détecteurs sont disposés en 2 rangées et montés sur une perche fixée sur la cabine
(Plan 9895 B).
1,00 1640
1,60 2300
Nota: les contacts des impulseurs IPU et IPD sont des contacts à ouverture.
DELTA VF
DELTA VF
DELTA VF
II - MISE EN INSPECTION
A ce stade du montage :
2) Vérifier sur les connecteurs à l’aide d’un voltmètre les tensions alimentant les circuits imprimés
MCS 310 - LCB * 9693 A3, idem LCB * 9693 A2 du MCS 312
* indice de mise à jour
DELTA VF
réduction x mouflage x Vn x 60
Nn= Π x φ poulie
φ = diamètre de la poulie en mm
Nn x pulse/tr encodeur
p/mm =
Vn x 60
13VTR Meidensha 260 72 13,67 575 2/1 270 p 4,086 1,60 m/s
13VTR Reivaj 260 49 13,67 575 2/1 180 p 2,724 1,60 m/s
DELTA VF
DELTA VF
p/mm = 4,086
196,57
SC = 99 - ∼ 51
4,086
SC = 51 => SW1 = 1
SW2 = 5
DELTA VF
DELTA VF
PTD
(DISPOPSITIF DE
DETECTION
DE POSITION)
NIVEAU
OCSS POSITION-
(CONTROLEUR NEMENT COMPTE A REBOURS IP
OPERATIONNEL DU
-LCD + SC I/O COMPTEUR
+ CUB) IP
LRST
(STI) SRST
LV
0-1
cm
CIRCUITS
VFCU
ST
3 cm/s
ST
DELTA VF
DETECTEUR
MAGNETIQUE IP
177
IP comptage x p/mm
IP compteur =
Programmation du JMP9
DELTA VF
IP compt x P/mm
IP compt =
Progr. JMP9
IRST x P/mm
LRST compt =
Progr. JMP9
L’étage court provoquera le collage du relais SRR et le VFCU utilisera une référence à
1 m/s au lieu de 1,6 m/s.
DELTA VF
MEIDENSHA 13 VTR
2300 2 1 6 0 2 1 4 0 1 3 4 0 4 HS
2/1 - 13,67 - 1,60 m/s
MEIDENSHA 13 VTR
1640 1 4 9 0 1 3 4 0 0 0 0 0 4 LS
2/1 - 13,67 - 1,00 m/s
REIVAJ 13 VTR
2300 2 8 8 0 2 7 6 0 1 7 5 0 2 HS
2/1 - 13,67 - 1,60 m/s
REIVAJ 13 VTR
1640 1 9 7 0 1 5 5 0 0 0 0 0 2 LS
2/1 - 13,67 - 1,00 m/s
MEIDENSHA 13 VTR
1450 1 9 7 3 1 6 4 4 0 0 0 0 4 LS
2/1 - 22 - 1,00 m/s
REIVAJ 13 VTR
1450 1 3 9 5 1 3 4 0 0 0 0 0 4 LS
2/1 - 22 - 1,00 m/s
MEIDENSHA 17 CT
REIVAJ 17 CT 2300 2 8 8 0 2 7 6 0 1 7 5 0 2 HS
2/1 - 25 - 1,60 m/s
MEIDENSHA 17 CT
REIVAJ 17 CT 1610 1 9 7 0 1 5 5 0 0 0 0 0 2 LS
2/1 - 25 - 1,00 m/s
REIVAJ 17 CT
2300 2 8 8 0 2 7 0 0 1 7 0 9 2 HS
1/1 - 30 - 1,60 m/s
REIVAJ 17 CT
2300 2 8 8 0 2 7 0 0 1 7 0 0 2 HS
1/1 - 29 - 1,60 m/s
DELTA VF
c) Contrôler et ajuster si nécessaire les tensions des alimentations PS1 (24V) et PS2 (5V) à
l’aide des potentiomètres correspondants:
3.DDSS
LCB - B9693 A2 I/O .adressage des entrées sorties
Eprom GOC616G49 (plan GO 26 XM)
DELTA VF
MCS310:
DELTA VF
1 - Mise en normal
Basculer le TCI sur le toit de la cabine sur la position NORMAL.
Basculer le module ERO en NORMAL cabine vide.
2 - Initialisation
Le système fait une initialisation, la cabine se déplace vers un niveau extrême.
3 - Test de fonctionnement
A l’aide de l’outil test 9693Bl, faire les essais de fonctionnement avec des envois cabine et
appels paliers à différents niveaux.
4 - R é g lage usin e
Contrôler les réglages usine de carte logique JO 6840 PM 1 du rack VFCU. Pour faire ces
réglages sur site, un multimètre/fréquencemètre (Fluke 85) est nécessaire.
4.4 Basculer l’interrupteur "T. Bias" 1 sur OFF (afin de supprimer la compensation électrique
fournie par l’intermédiaire de la carte T. Bias).
4.5 Basculer les interrupteurs "PW" et "SP" MODE sur la position ON (afin de neutraliser
le déclenchement des défauts).
DELTA VF
4.7 Vérifier et ajuster à l’aide d’un voltmètre les tensions des alimentations stabilisées des
circuits logiques SCIO et CUB:
PS1: 24 V ± 0,05 V
PS2: 5 V ± 0,05 V
Etablir à l’aide d’un shunt une liaison entre les bornes + 5V et CN 7-2.
Connecter le voltmètre entre les bornes tests JU et OV
DELTA VF
DELTA VF
OFF ON 450-1200
ON OFF 750-1850
ON ON 340-900
- Déconnecter le voltmètre.
- Dans le graphique ci après, relever la tension OVT pour la tension du réseau mesurée.
DELTA VF
DELTA VF
Interrupteurs et Potentiomètres
CARTE LOGIQUE VF
DELTA VF
Les tableaux suivants sont valables pour les machines 17CT, 18CT ou 13VTR équipées d'un
moteur MEIDENSHA ou d'un moteur REIVAJ.
1.00 m/s / 1,60 m/s 1.60 m/s 1.60 m/s 1,00 m/s / 1.60 m/s
Zéro Adj 0V 0V 0V 0V
SP. Adj 10 V 10 V 10 V 10 V
TRQ. Set 9V 10 V 9V 9V
DELTA VF
UD F F F F
UHL L L L L
DHL L L L L
Slip Set 1 ON ON ON ON
T. Bias 1 ON ON ON ON
Cavaliers 1U 1W 1U 1W
DELTA VF
Tous les réglages (sauf carte de contrôle du couple) se font cabine vide.
a) Référence vitesse:
La vitesse en rotation du moteur sera prise avec un tachymètre sur le volant supérieur.
DELTA VF
6 - Réglage de la décélération
b) Régler le potentiomètre DDC. Time (R) (en tournant le potentiomètre dans le sens des
aiguilles d’une montre) pour obtenir une vitesse de nivellement stabilisée sur 10 cm environ
Régler le potentiomètre DCC. Time (P) pour obtenir la vitesse de nivellement stabilisée
pendant 0,5 a 0,3 s avant l’arrêt.
c) Régler le potentiomètre BRK. ON de telle manière que le frein retombe à 0,2 s après
l’arrêt.
7 - R é g lage de l’accélération
- Le potentiomètre ACC. Time permet une accélération de 1,2 m/s2 sur la position 0
à 0,5 m/s2 sur la position 10
Le confort d’une course d’étage à étage (SRR et étage court sur MCS) est tributaire du
réglage de l’accélération.
8 - Réglage confort
a) P. GAIN:
P. GAIN élevé provoque des oscillations.
P. GAIN faible provoque un manque de précision d’arrêt et provoque le défaut SFB
(écart trop important entre la référence et la vitesse vraie).
b) I. GAIN:
Temps de réponse du contrôle. I. GAIN moins élevé provoque un choc au départ.
Une augmentation de la valeur I. GAIN compense une diminution de P. GAIN.
I. GAIN faible provoque le défaut SFB.
DELTA VF
Sur la carte CUB, à l’aide des cavaliers du réglage de SRST, augmenter ou diminuer la valeur
pour obtenir la même décélération que lors d’une grande course.
Vitesse de nivellement stabilisée sur 2 à 5 cm (0,3 à 0,5 s).
Les potentiomètres de réglage de cette compensation sont situés sur la carte de contrôle du
couple JO 6840 NF 2 (Torque Bias).
L'interrupteur MSVF/60 VF doit toujours être sur la position 60 VF (tirer vers soi).
DELTA VF
Tourner le pot "Brk-time (off)" au maxi pour obtenir un dévirage en montée et descente.
Régler le potentiomètre NL de telle manière qu’au départ il n’y ait pas de retour en
arrière.
Relever la valeur lue sur le voltmètre:
A=
Régler le potentiomètre NL de telle manière qu’au départ il n’y ait pas de choc
(confort en cabine).
Relever la valeur lue sur le voltmètre:
B=
A+B
NL =
2
DELTA VF
Simuler le pèse charge LWl actionné, LED LWl allumée sur la carte T. Bias.
Régler le potentiomètre MLD1 de façon à obtenir un départ en descente sans retour en
arrière et en montée sans à-coup (confort en cabine).
k) Déconnecter le voltmètre.
l) Régler le potentiomètre brk-time (off) pour obtenir un départ sans à-coup dans les 2 sens
de déplacement.
DELTA VF
. Lorsque la vitesse nominale est atteinte, procéder à un arrêt par coupure de l’interrupteur
principal au moment ou le repère sur la poulie et le repère sur la partie fixe coïncident.
Mesurer sur la poulie la distance parcourue.
Nota: après chaque essai de 1LS, repositionner le cavalier "x 1000" sur sa postion
pour un fonctionnement normal.
Procéder de la même manière que pour le 1LS, mais en partant du niveau bas et
avec la cabine vide.
DELTA VF
Nota: après chaque essai, repositionner le cavalier "x 1000" de la CUB sur sa
position pour un fonctionnement normal.
Nota: après chaque essai, repositionner le cavalier "x l000" de la CUB sur sa
position initiale pour un déplacement en nominal.